1.<br />

Point of installation<br />

1c<br />

GB<br />

For an all-embracing protection of houses smoke <strong>de</strong>tectors should be installed<br />

in all rooms, halls, storage areas, cellars and lofts. Minimum protection<br />

envisages the installation of a smoke <strong>de</strong>tector on each landing and one in the<br />

bedroom. In buildings with several flats each family should have their own<br />

smoke <strong>de</strong>tectors.<br />

50 cm<br />

Do not mount on or behind beams if these are thicker than 20 cm<br />

Do not install in bathrooms or garages, and only in the kitchen if a minimum<br />

distance of 4 meters from cookers and similar emission sources can be<br />

maintained.<br />

1d<br />

50 cm<br />

Do not locate in draughty points, e. g. in the vicinity of ventilation shafts, as<br />

air movement could prevent smoke from reaching the <strong>de</strong>tector. The most<br />

effective point of installation is the middle of the ceiling.<br />

Maintain a distance of at least 50 cm from fluorescent lights.<br />

Do not install in very dusty areas or at points with very high humidity levels.<br />

1e<br />

Dining Eßzimmer room<br />

Kitchen Küche<br />

1a<br />

Ceiling installation<br />

Middle of the room<br />

Bedroom Schlafen<br />

Distance from a fireplace, cooker, etc.<br />

>4 m<br />

Wohnzimmer Lounge<br />

Loft<br />

Flur<br />

Bedroom Schlafen<br />

1b<br />

30-50 cm<br />

Do not install insi<strong>de</strong> the roof ridge as smoke-free air<br />

could collect at this point in the event of fire.<br />

In rooms with a roof inclination exceeding 30°<br />

and an overall height of up to 6 m, a<br />

distance of at least 30 to 50 cm must<br />

be maintained from the top.<br />

6 m<br />

Points of installation for smoke <strong>de</strong>tectors in a flat with two bedrooms<br />

> 30°<br />

Smoke <strong>de</strong>tector for<br />

minimal safety<br />

Smoke <strong>de</strong>tector for<br />

ad<strong>de</strong>d safety