Set reference range<br />
NB!<br />
<strong>VLT</strong> 2880-2882 do not have the AMT function.<br />
Min. reference, RefMIN Parameter 204<br />
Max. reference, RefMAX Parameter 205<br />
Set ramp time<br />
Ramp-up time [s] Parameter 207<br />
Ramp-down time [s] Parameter 208<br />
In parameter 002, Local/remote control, the frequency converter mode can be selected as Remote<br />
operation [0], i.e. via the control terminals, or Local [1], i.e. via the control unit.<br />
Set the control location to Local [1]<br />
Local/remote operation = Local [1], Par. 002<br />
Set the motor speed by adjusting the<br />
Local reference<br />
Local reference, Par. 003<br />
1.6 Motor Start<br />
Press [START] to start the motor. Set the motor speed by adjusting par. 003, Local reference.<br />
Check whether the direction of rotation of the motor shaft is clockwise. If not, exchange any two<br />
phases on the motor cable.<br />
Press [STOP/RESET] to stop the motor.<br />
Press [QUICK MENU] to return to display mode.<br />
[QUICK MENU] + [+] keys must be pressed simultaneously to give access to all parameters.<br />