04.03.2013 Views

ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S

ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S

ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

TECHNICAL<br />

SPECIFICATIONS<br />

Conceptpower TM <strong>Slim</strong>-Line<br />

<strong>10</strong>-15-20-30-<strong>40kVA</strong><br />

Uninterruptible Power Supply (UPS)<br />

n+1 redundant, three-phase<br />

On-Line, Double-Conversion, VFI<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 1<br />

Printed in Switzerland <strong>–</strong> Modifications reserved


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

TECHNICAL SPECIFICATIONS<br />

<strong>10</strong>, 15, 20, 30 and 40 kVA (three phase input and output)<br />

GENERAL DATA<br />

Output Rated Power kVA <strong>10</strong> 15 20 30 40<br />

Output Power Factor 0.8<br />

Topology On-Line, Double Conversion, VFI<br />

Technology Second Generation, Tansformerless<br />

For redundancy and/or capacity:<br />

Parallel Configuration (optional)<br />

Double Conversion AC-AC efficiency with batt.fully<br />

charged<br />

- Standard up to <strong>10</strong> modules<br />

- Without limitation on request<br />

<strong>10</strong>0%/75%/50%25% Linear Load (cos =0.8ind) % 94.5/94.5/93/91 94.5/94.5/93/91 94.5/94.5/93/91 95/95/93.5/92 95/95/93.5/92<br />

<strong>10</strong>0%/75%/50%/25% Linear Load (Resistive cos =1) % 94/94/92/90 94/94/92/90 94/94/92/90 94/94/92.5/91 94/94/92.5/91<br />

<strong>10</strong>0%/75%/50%/25% Non-linear Load (EN 62040-1-<br />

1:2003)<br />

% 93/93/91/90 93/93/91/90 93/93/91/90 93/93/92/91 93/93/92/91<br />

Eco-mode efficiency (load on by-pass) at <strong>10</strong>0% load % 98 98 98 98 98<br />

Heat Dissipation With <strong>10</strong>0% Load (cos =0.8ind) W 400 600 800 1200 1600<br />

Heat Dissipation With <strong>10</strong>0% Load (Resistive cos =1) W 480 720 960 1450 1920<br />

Heat Dissipation With <strong>10</strong>0% Non-linear Load<br />

(EN 62040-1-1:2003)<br />

Airflow (25° - 30°C) with Non-linear load<br />

(EN 62040-1-1:2003)<br />

W 560 840 1120 1680 2240<br />

m 3 /h 1<strong>10</strong> 150 200 300 400<br />

Audible Noise with <strong>10</strong>0%/50% Load dBA 55/49 57/49 57/49 59/51 63/53<br />

Ambient Temperature for UPS °C 0 <strong>–</strong> 40<br />

Ambient Temperature for Batteries (recommended) °C 20 <strong>–</strong> 25<br />

Storage Temperature °C -25 - +70<br />

Battery Storage Time at Ambient Temperature Max. 6 months<br />

Cooling Fan-assisted<br />

Relative Air-humidity Max. 95% (non-condensing)<br />

Standards<br />

- Safety EN 62040-1-1:2003, EN 60950-1:2001/A11:2004<br />

- Electromagnetic Compatibility<br />

EN 50091-2:1995, EN6<strong>10</strong>00-3-2:2000, EN6<strong>10</strong>0-3-3:1995/A1:2001, EN6<strong>10</strong>00-<br />

6-2:2001, EN6<strong>10</strong>00-6-4:2001<br />

- Performance EN62040-3:2001<br />

Transportation Palette Provided with UPS<br />

Accessibility Front and right side access for service and maintenance<br />

Positioning Min. <strong>10</strong>cm rear space (required for fan)<br />

Input and Output Power Cabling From front and bottom<br />

Dry Port (Volt-free contacts) For remote signalling and automatic computer shutdown<br />

Smart Port (RS 232) For monitoring and integration in network management<br />

Input Terminals<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 2<br />

Printed in Switzerland <strong>–</strong> Modifications reserved<br />

EMERGENCY OFF (Normally closed)<br />

GEN-ON (Normally open)<br />

BATTERY TEMPERATURE SENSOR


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

RECTIFIER DATA<br />

Input Voltage V 3x380/220V+N, 3x400V/230V+N, 3x415/240V+N<br />

For Loads:


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

POWER MANAGEMENT DISPLAY (PMD)<br />

The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides<br />

the necessary monitoring information about the UPS.<br />

MIMIC DIAGRAM<br />

The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow<br />

status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the<br />

corresponding LED-indicators will change colour from green (normal) to red (warning). The LED’s LINE 1<br />

(rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s INVERTER and<br />

BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator<br />

BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is<br />

a visual indication of any internal or external alarm condition. At the same time the audible alarm will be<br />

activated.<br />

PUSHBUTTONS<br />

The pushbuttons serve to manage the UPS by performing commands. The 2xON/OFF pushbuttons serve to<br />

start-up or shutdown the UPS if pressed simultaneously. The pushbuttons UP and DOWN allow working<br />

through the PMD-menu. The RESET pushbutton serves to cancel the audible alarm in the event of a<br />

disturbance. If the alarm condition was only transient the LED-indicator ALARM would also extinguish otherwise<br />

it will remain on (red).<br />

DISPLAY<br />

The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the<br />

access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other<br />

Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer from<br />

INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for<br />

adjustments and testing (for more details see the USER MANUAL of <strong>ConceptpowerTM</strong> ).<br />

Power Management Display (PMD) of Conceptpower TM<br />

OPTIONALS<br />

Extended Battery Autonomies In matching battery frames CBAT-30C,CBAT-30GU and<br />

CBAT-M<br />

Optional Battery Charger For longer autonomies<br />

Remote Signalling Panel (RSP) For UPS-Status indication<br />

Parallel Configuration A number of units may be paralleled<br />

for redundancy or capacity upgrade<br />

Wavemon Software For automatic shut-down and monitoring<br />

SNMP <strong>–</strong> Card/Adapter For network management and remote monitoring<br />

Input or Output Isolation Transformer For special voltages or for galvanic isolation<br />

Customized UPS- and Battery Frames On request (for OEM-Projects only)<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 4<br />

Printed in Switzerland <strong>–</strong> Modifications reserved


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

MECHANICAL CHARACTERISTICS <strong>Slim</strong> Line<br />

MODEL kVA <strong>10</strong> 15 20 30 40<br />

Dimensions (WxHxD) mm 550 x 1400 x 750 550 x 1800 x 750<br />

Protection Degree IP 20<br />

Ventilation Fan assisted<br />

Colour RAL 9002<br />

Foot Print m 2 0.41<br />

Maximum Output Power of one <strong>Slim</strong> Line UPS 30 kVA 40 kVA<br />

Dimensions of Concept Power <strong>Slim</strong>-Line (Depth 750mm) for <strong>10</strong>-30kVA<br />

<strong>Slim</strong>-Line Frame: CUPS-30S<br />

550 mm<br />

550 mm<br />

1400 mm<br />

Battery Frame CBAT-30CS<br />

580 mm<br />

1400mm<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 5<br />

Power<br />

(kVA)<br />

Power<br />

(kVA)<br />

Autonomy<br />

(min.)<br />

Maximum<br />

Autonomy<br />

(min.)<br />

Printed in Switzerland <strong>–</strong> Modifications reserved<br />

Battery<br />

Type<br />

Maximum<br />

Battery<br />

Frame<br />

Type<br />

Frame<br />

Type<br />

UPS +<br />

Battery<br />

Weight<br />

(kg)<br />

<strong>10</strong> 132 90x24Ah CBAT-30C 1140<br />

15 78 90x24Ah CBAT-30C 1140<br />

20 53 90x24Ah CBAT-30C 1140<br />

30 32 90x24Ah CBAT-30C 1140<br />

Weight<br />

(kg)<br />

<strong>10</strong> 0 ____ CUPS-30S 180<br />

<strong>10</strong> <strong>10</strong> 40 x 7Ah CUPS-30S 280<br />

<strong>10</strong> 16 (2x30) x 7Ah CUPS-30S 330<br />

<strong>10</strong> 24 (2x40) x 7Ah CUPS-30S 380<br />

<strong>10</strong> 40 (3x40) x 7Ah CUPS-30S<br />

15 0 ____<br />

CUPS-30S<br />

480<br />

185<br />

15 <strong>10</strong> (2x30) x 7Ah CUPS-30S 335<br />

15 14 (2x40) x 7Ah CUPS-30S 385<br />

15 24 (3x40) x 7Ah CUPS-30S 485<br />

20 0 ____ CUPS-30S 185<br />

20 <strong>10</strong> (2x40) x 7Ah CUPS-30S 385<br />

20 16 (3x40) x 7Ah CUPS-30S 485<br />

30 0 ____ CUPS-30S 190<br />

30 <strong>10</strong> (3x40) x 7Ah CUPS-30S 490<br />

In the Battery Frame CBAT-30CS and up to<br />

90 x 24Ah / 28Ah may be fitted.<br />

The maximum achievable autonomy with one<br />

additional Battery Frame CBAT-30CS are:


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

Dimensions of Concept Power <strong>Slim</strong>-Line (Depth 750mm) for <strong>40kVA</strong><br />

<strong>Slim</strong>-Line Frame: CUPS-40S<br />

550 mm<br />

550 mm<br />

1800<br />

Battery Frame CBAT-M<br />

580 mm<br />

1800<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 6<br />

Power<br />

(kVA)<br />

Power<br />

(kVA)<br />

Autonomy<br />

(min.)<br />

Printed in Switzerland <strong>–</strong> Modifications reserved<br />

Maximum<br />

Autonomy<br />

(min.)<br />

Battery<br />

Type<br />

Maxim<br />

um<br />

Battery<br />

40 25 (2x50)x<br />

24Ah<br />

40 42 (3x50)x<br />

24Ah<br />

Frame<br />

Type<br />

CBAT-<br />

M<br />

2x<br />

CBAT-M<br />

Frame<br />

Type<br />

UPS +<br />

Battery<br />

Weight<br />

(kg)<br />

1350<br />

1990<br />

Weight<br />

(kg)<br />

40 0 ____ CUPS-40S 260<br />

40 8 (3x50) x 7Ah CUPS-40S 640<br />

40 12 (4x50) x 7Ah CUPS-40S 770<br />

In the Battery Frame CBAT-M up to<br />

<strong>10</strong>0 x 24Ah / 28Ah may be fitted.<br />

The maximum achievable autonomy with one<br />

additional Battery Frame CBAT-M are:


Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />

Block Diagram <strong>Slim</strong>-Line<br />

Cable E<br />

Fuse E<br />

STANDARD VERSION (SINGLE INPUT FEED)<br />

Fuse A<br />

Cable A<br />

F4<br />

<strong>Slim</strong> Frame<br />

F1 F2<br />

UPS System 1<br />

Rectifier<br />

Inverter<br />

Static Switch<br />

F3<br />

MAINS (3x380V/220V,<br />

3x400/230V,3x415/240<br />

Mainten. Bypass<br />

Load<br />

Cable Sections and Fuse Ratings recommended by European standards.<br />

Alternatively, local standards to be respected<br />

STANDARD VERSION (SINGLE FEED INPUT)<br />

Cable D<br />

Power (kVA) Fuse A (Agl/CB) Cable A (IEC 60950-1:2001) Cable D (IEC 60950-1:2001) Fuse E +/N/- Cable E +/N/-<br />

<strong>10</strong> 3x20 5x2.5 5x2.5 3x32A 3x4<br />

15 3x25 5x4 5x4 3x63A 3x<strong>10</strong><br />

20 3x40 5x6 5x6 3x63A 3x<strong>10</strong><br />

30 3x63 5x<strong>10</strong> 5x<strong>10</strong> 3x80A 3x16<br />

40 3x80 5x25 5x25 3x<strong>10</strong>0A 3x25<br />

VERSION ON REQUEST (DUAL FEED INPUT)<br />

Cable E<br />

Fuse E<br />

Power Fuse B Cable B<br />

Fuse C<br />

Cable C<br />

Cable D Fuse E Cable E<br />

(kVA) (Agl/CB) (IEC 60950-1:2001) (Agl/CB) (IEC 60950-1:2001) (IEC 60950-1:2001) +/N/- +/N/-<br />

<strong>10</strong> 3x20 5x2.5 3x20 4x2.5 5x2.5 3x32A 3x4<br />

15 3x25 5x4 3x25 4x4 5x4 3x63A 3x<strong>10</strong><br />

20 3x40 5x6 3x40 4x6 5x6 3x63A 3x<strong>10</strong><br />

30 3x63 5x<strong>10</strong> 3x63 4x<strong>10</strong> 5x<strong>10</strong> 3x80A 3x16<br />

40 3x80 5x25 3x80 4x25 5x25 3x<strong>10</strong>0A 3x25<br />

The Conceptpower <strong>Slim</strong>-Line UPS’s may be paralleled for power capacity upgrade or redundancy. The standard<br />

conceptpower TM <strong>Slim</strong> UPS is not provided with the parallel option.<br />

UPS 1 UPS 2 UPS n<br />

Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 7<br />

Printed in Switzerland <strong>–</strong> Modifications reserved<br />

VERSION ON REQUEST (DUAL INPUT FEED)<br />

Fuse B Fuse C<br />

Cable B<br />

F4<br />

<strong>Slim</strong> Frame<br />

F1 F2<br />

UPS System 1<br />

Rectifier<br />

Inverter<br />

Static Switch<br />

F3<br />

Mainten. Bypass<br />

Load<br />

Cable C<br />

Cable D<br />

MAINS (3x380V/220V,<br />

3x400/230V,3x415/240V

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!