ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S
ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S
ConceptpowerTM – Slim 10-40kVA - Atek Teknik A/S
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
TECHNICAL<br />
SPECIFICATIONS<br />
Conceptpower TM <strong>Slim</strong>-Line<br />
<strong>10</strong>-15-20-30-<strong>40kVA</strong><br />
Uninterruptible Power Supply (UPS)<br />
n+1 redundant, three-phase<br />
On-Line, Double-Conversion, VFI<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 1<br />
Printed in Switzerland <strong>–</strong> Modifications reserved
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
TECHNICAL SPECIFICATIONS<br />
<strong>10</strong>, 15, 20, 30 and 40 kVA (three phase input and output)<br />
GENERAL DATA<br />
Output Rated Power kVA <strong>10</strong> 15 20 30 40<br />
Output Power Factor 0.8<br />
Topology On-Line, Double Conversion, VFI<br />
Technology Second Generation, Tansformerless<br />
For redundancy and/or capacity:<br />
Parallel Configuration (optional)<br />
Double Conversion AC-AC efficiency with batt.fully<br />
charged<br />
- Standard up to <strong>10</strong> modules<br />
- Without limitation on request<br />
<strong>10</strong>0%/75%/50%25% Linear Load (cos =0.8ind) % 94.5/94.5/93/91 94.5/94.5/93/91 94.5/94.5/93/91 95/95/93.5/92 95/95/93.5/92<br />
<strong>10</strong>0%/75%/50%/25% Linear Load (Resistive cos =1) % 94/94/92/90 94/94/92/90 94/94/92/90 94/94/92.5/91 94/94/92.5/91<br />
<strong>10</strong>0%/75%/50%/25% Non-linear Load (EN 62040-1-<br />
1:2003)<br />
% 93/93/91/90 93/93/91/90 93/93/91/90 93/93/92/91 93/93/92/91<br />
Eco-mode efficiency (load on by-pass) at <strong>10</strong>0% load % 98 98 98 98 98<br />
Heat Dissipation With <strong>10</strong>0% Load (cos =0.8ind) W 400 600 800 1200 1600<br />
Heat Dissipation With <strong>10</strong>0% Load (Resistive cos =1) W 480 720 960 1450 1920<br />
Heat Dissipation With <strong>10</strong>0% Non-linear Load<br />
(EN 62040-1-1:2003)<br />
Airflow (25° - 30°C) with Non-linear load<br />
(EN 62040-1-1:2003)<br />
W 560 840 1120 1680 2240<br />
m 3 /h 1<strong>10</strong> 150 200 300 400<br />
Audible Noise with <strong>10</strong>0%/50% Load dBA 55/49 57/49 57/49 59/51 63/53<br />
Ambient Temperature for UPS °C 0 <strong>–</strong> 40<br />
Ambient Temperature for Batteries (recommended) °C 20 <strong>–</strong> 25<br />
Storage Temperature °C -25 - +70<br />
Battery Storage Time at Ambient Temperature Max. 6 months<br />
Cooling Fan-assisted<br />
Relative Air-humidity Max. 95% (non-condensing)<br />
Standards<br />
- Safety EN 62040-1-1:2003, EN 60950-1:2001/A11:2004<br />
- Electromagnetic Compatibility<br />
EN 50091-2:1995, EN6<strong>10</strong>00-3-2:2000, EN6<strong>10</strong>0-3-3:1995/A1:2001, EN6<strong>10</strong>00-<br />
6-2:2001, EN6<strong>10</strong>00-6-4:2001<br />
- Performance EN62040-3:2001<br />
Transportation Palette Provided with UPS<br />
Accessibility Front and right side access for service and maintenance<br />
Positioning Min. <strong>10</strong>cm rear space (required for fan)<br />
Input and Output Power Cabling From front and bottom<br />
Dry Port (Volt-free contacts) For remote signalling and automatic computer shutdown<br />
Smart Port (RS 232) For monitoring and integration in network management<br />
Input Terminals<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 2<br />
Printed in Switzerland <strong>–</strong> Modifications reserved<br />
EMERGENCY OFF (Normally closed)<br />
GEN-ON (Normally open)<br />
BATTERY TEMPERATURE SENSOR
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
RECTIFIER DATA<br />
Input Voltage V 3x380/220V+N, 3x400V/230V+N, 3x415/240V+N<br />
For Loads:
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
POWER MANAGEMENT DISPLAY (PMD)<br />
The user-friendly PMD consists of three parts the MIMIC DIAGRAM, CONTROL KEYS and LCD that provides<br />
the necessary monitoring information about the UPS.<br />
MIMIC DIAGRAM<br />
The mimic diagram serves to give the general status of the UPS. The LED-indicators show the power flow<br />
status and in the event of mains failure or load transfer from inverter to bypass and vice-versa the<br />
corresponding LED-indicators will change colour from green (normal) to red (warning). The LED’s LINE 1<br />
(rectifier) and LINE 2 (bypass) indicate the availability of the mains power supply. The LED’s INVERTER and<br />
BYPASS if green indicate which of the two are supplying power to the critical load. When the LED-indicator<br />
BATTERY is lit it means that the battery due to mains failure is supplying the load. The LED-indicator ALARM is<br />
a visual indication of any internal or external alarm condition. At the same time the audible alarm will be<br />
activated.<br />
PUSHBUTTONS<br />
The pushbuttons serve to manage the UPS by performing commands. The 2xON/OFF pushbuttons serve to<br />
start-up or shutdown the UPS if pressed simultaneously. The pushbuttons UP and DOWN allow working<br />
through the PMD-menu. The RESET pushbutton serves to cancel the audible alarm in the event of a<br />
disturbance. If the alarm condition was only transient the LED-indicator ALARM would also extinguish otherwise<br />
it will remain on (red).<br />
DISPLAY<br />
The 2 x 20 character LCD simplifies the communication with the UPS. The menu driven LCD enables the<br />
access to the EVENT REGISTER, or to monitor the input and output U, I, f, P, Autonomy Time and other<br />
Measurement’s, to perform commands like start-up and shut-down of INVERTER or load transfer from<br />
INVERTER to BYPASS and vice-versa and finally it serves for the DIAGNOSIS (SERVICE MODE) for<br />
adjustments and testing (for more details see the USER MANUAL of <strong>ConceptpowerTM</strong> ).<br />
Power Management Display (PMD) of Conceptpower TM<br />
OPTIONALS<br />
Extended Battery Autonomies In matching battery frames CBAT-30C,CBAT-30GU and<br />
CBAT-M<br />
Optional Battery Charger For longer autonomies<br />
Remote Signalling Panel (RSP) For UPS-Status indication<br />
Parallel Configuration A number of units may be paralleled<br />
for redundancy or capacity upgrade<br />
Wavemon Software For automatic shut-down and monitoring<br />
SNMP <strong>–</strong> Card/Adapter For network management and remote monitoring<br />
Input or Output Isolation Transformer For special voltages or for galvanic isolation<br />
Customized UPS- and Battery Frames On request (for OEM-Projects only)<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 4<br />
Printed in Switzerland <strong>–</strong> Modifications reserved
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
MECHANICAL CHARACTERISTICS <strong>Slim</strong> Line<br />
MODEL kVA <strong>10</strong> 15 20 30 40<br />
Dimensions (WxHxD) mm 550 x 1400 x 750 550 x 1800 x 750<br />
Protection Degree IP 20<br />
Ventilation Fan assisted<br />
Colour RAL 9002<br />
Foot Print m 2 0.41<br />
Maximum Output Power of one <strong>Slim</strong> Line UPS 30 kVA 40 kVA<br />
Dimensions of Concept Power <strong>Slim</strong>-Line (Depth 750mm) for <strong>10</strong>-30kVA<br />
<strong>Slim</strong>-Line Frame: CUPS-30S<br />
550 mm<br />
550 mm<br />
1400 mm<br />
Battery Frame CBAT-30CS<br />
580 mm<br />
1400mm<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 5<br />
Power<br />
(kVA)<br />
Power<br />
(kVA)<br />
Autonomy<br />
(min.)<br />
Maximum<br />
Autonomy<br />
(min.)<br />
Printed in Switzerland <strong>–</strong> Modifications reserved<br />
Battery<br />
Type<br />
Maximum<br />
Battery<br />
Frame<br />
Type<br />
Frame<br />
Type<br />
UPS +<br />
Battery<br />
Weight<br />
(kg)<br />
<strong>10</strong> 132 90x24Ah CBAT-30C 1140<br />
15 78 90x24Ah CBAT-30C 1140<br />
20 53 90x24Ah CBAT-30C 1140<br />
30 32 90x24Ah CBAT-30C 1140<br />
Weight<br />
(kg)<br />
<strong>10</strong> 0 ____ CUPS-30S 180<br />
<strong>10</strong> <strong>10</strong> 40 x 7Ah CUPS-30S 280<br />
<strong>10</strong> 16 (2x30) x 7Ah CUPS-30S 330<br />
<strong>10</strong> 24 (2x40) x 7Ah CUPS-30S 380<br />
<strong>10</strong> 40 (3x40) x 7Ah CUPS-30S<br />
15 0 ____<br />
CUPS-30S<br />
480<br />
185<br />
15 <strong>10</strong> (2x30) x 7Ah CUPS-30S 335<br />
15 14 (2x40) x 7Ah CUPS-30S 385<br />
15 24 (3x40) x 7Ah CUPS-30S 485<br />
20 0 ____ CUPS-30S 185<br />
20 <strong>10</strong> (2x40) x 7Ah CUPS-30S 385<br />
20 16 (3x40) x 7Ah CUPS-30S 485<br />
30 0 ____ CUPS-30S 190<br />
30 <strong>10</strong> (3x40) x 7Ah CUPS-30S 490<br />
In the Battery Frame CBAT-30CS and up to<br />
90 x 24Ah / 28Ah may be fitted.<br />
The maximum achievable autonomy with one<br />
additional Battery Frame CBAT-30CS are:
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
Dimensions of Concept Power <strong>Slim</strong>-Line (Depth 750mm) for <strong>40kVA</strong><br />
<strong>Slim</strong>-Line Frame: CUPS-40S<br />
550 mm<br />
550 mm<br />
1800<br />
Battery Frame CBAT-M<br />
580 mm<br />
1800<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 6<br />
Power<br />
(kVA)<br />
Power<br />
(kVA)<br />
Autonomy<br />
(min.)<br />
Printed in Switzerland <strong>–</strong> Modifications reserved<br />
Maximum<br />
Autonomy<br />
(min.)<br />
Battery<br />
Type<br />
Maxim<br />
um<br />
Battery<br />
40 25 (2x50)x<br />
24Ah<br />
40 42 (3x50)x<br />
24Ah<br />
Frame<br />
Type<br />
CBAT-<br />
M<br />
2x<br />
CBAT-M<br />
Frame<br />
Type<br />
UPS +<br />
Battery<br />
Weight<br />
(kg)<br />
1350<br />
1990<br />
Weight<br />
(kg)<br />
40 0 ____ CUPS-40S 260<br />
40 8 (3x50) x 7Ah CUPS-40S 640<br />
40 12 (4x50) x 7Ah CUPS-40S 770<br />
In the Battery Frame CBAT-M up to<br />
<strong>10</strong>0 x 24Ah / 28Ah may be fitted.<br />
The maximum achievable autonomy with one<br />
additional Battery Frame CBAT-M are:
Conceptpower TM <strong>–</strong> <strong>Slim</strong> <strong>10</strong>-<strong>40kVA</strong><br />
Block Diagram <strong>Slim</strong>-Line<br />
Cable E<br />
Fuse E<br />
STANDARD VERSION (SINGLE INPUT FEED)<br />
Fuse A<br />
Cable A<br />
F4<br />
<strong>Slim</strong> Frame<br />
F1 F2<br />
UPS System 1<br />
Rectifier<br />
Inverter<br />
Static Switch<br />
F3<br />
MAINS (3x380V/220V,<br />
3x400/230V,3x415/240<br />
Mainten. Bypass<br />
Load<br />
Cable Sections and Fuse Ratings recommended by European standards.<br />
Alternatively, local standards to be respected<br />
STANDARD VERSION (SINGLE FEED INPUT)<br />
Cable D<br />
Power (kVA) Fuse A (Agl/CB) Cable A (IEC 60950-1:2001) Cable D (IEC 60950-1:2001) Fuse E +/N/- Cable E +/N/-<br />
<strong>10</strong> 3x20 5x2.5 5x2.5 3x32A 3x4<br />
15 3x25 5x4 5x4 3x63A 3x<strong>10</strong><br />
20 3x40 5x6 5x6 3x63A 3x<strong>10</strong><br />
30 3x63 5x<strong>10</strong> 5x<strong>10</strong> 3x80A 3x16<br />
40 3x80 5x25 5x25 3x<strong>10</strong>0A 3x25<br />
VERSION ON REQUEST (DUAL FEED INPUT)<br />
Cable E<br />
Fuse E<br />
Power Fuse B Cable B<br />
Fuse C<br />
Cable C<br />
Cable D Fuse E Cable E<br />
(kVA) (Agl/CB) (IEC 60950-1:2001) (Agl/CB) (IEC 60950-1:2001) (IEC 60950-1:2001) +/N/- +/N/-<br />
<strong>10</strong> 3x20 5x2.5 3x20 4x2.5 5x2.5 3x32A 3x4<br />
15 3x25 5x4 3x25 4x4 5x4 3x63A 3x<strong>10</strong><br />
20 3x40 5x6 3x40 4x6 5x6 3x63A 3x<strong>10</strong><br />
30 3x63 5x<strong>10</strong> 3x63 4x<strong>10</strong> 5x<strong>10</strong> 3x80A 3x16<br />
40 3x80 5x25 3x80 4x25 5x25 3x<strong>10</strong>0A 3x25<br />
The Conceptpower <strong>Slim</strong>-Line UPS’s may be paralleled for power capacity upgrade or redundancy. The standard<br />
conceptpower TM <strong>Slim</strong> UPS is not provided with the parallel option.<br />
UPS 1 UPS 2 UPS n<br />
Newave_TDS_CPS_<strong>10</strong>K_40K_GB_220605.DOC Page 7<br />
Printed in Switzerland <strong>–</strong> Modifications reserved<br />
VERSION ON REQUEST (DUAL INPUT FEED)<br />
Fuse B Fuse C<br />
Cable B<br />
F4<br />
<strong>Slim</strong> Frame<br />
F1 F2<br />
UPS System 1<br />
Rectifier<br />
Inverter<br />
Static Switch<br />
F3<br />
Mainten. Bypass<br />
Load<br />
Cable C<br />
Cable D<br />
MAINS (3x380V/220V,<br />
3x400/230V,3x415/240V