Presentation Prefabricated metal-enclosed<br />
switchgear<br />
AMTED300014EN.indd<br />
Example 1:<br />
Here is a GIS solution with in (D) what is said to be “Base section<br />
with cable connection area” (AREVA WI). There is no connection<br />
compartment, and the only HV compartments are gas filled.<br />
Then, there is no accessible compartment to be considered for LSC<br />
classification.<br />
LSC is not relevant in that case, and service continuity during normal<br />
operation and maintenance is expected to be total.<br />
Example 2:<br />
Here is a GIS solution (<strong>Schneider</strong> <strong>Electric</strong> CGset) with an air insulated<br />
connection (and possibly VT) compartment.<br />
This compartment is accessible (with tools).<br />
The other HV compartments are not accessible.<br />
Access to the connection compartment is possible with the busbar(s) live,<br />
meaning all other functional units can be kept operating.<br />
The LSC classification applies, and such solution is LSC2.<br />
Example 3:<br />
Here is a GIS solution (<strong>Schneider</strong> <strong>Electric</strong> GMset) with an air insulated<br />
connection (and possibly VT) compartment. This compartment is<br />
accessible and interlocked with the earthing function.<br />
The circuit breaker can be extracted (tool access compartment), even if<br />
that is not considered as normal operation nor normal maintenance.<br />
Access to one functional unit within a switchboard does not require any<br />
other functional unit to be switched off. Such solution is LSC2A.<br />
Example 4:<br />
A mixed technology (<strong>Schneider</strong> <strong>Electric</strong> GenieEvo) with an air insulated<br />
connection compartment, and an air insulated main switching device<br />
which can be extracted with the busbar live, thanks to the disconnector.<br />
Single line diagram is similar to example 2.<br />
If both the connection compartment and the circuit breaker compartment<br />
are accessible, and access to any of them means the cables are first<br />
switched off and earthed. Category is LSC2A.<br />
11