Presentation Prefabricated metal-enclosed<br />

switchgear<br />

AMTED300014EN.indd<br />

Example 1:<br />

Here is a GIS solution with in (D) what is said to be “Base section<br />

with cable connection area” (AREVA WI). There is no connection<br />

compartment, and the only HV compartments are gas filled.<br />

Then, there is no accessible compartment to be considered for LSC<br />

classification.<br />

LSC is not relevant in that case, and service continuity during normal<br />

operation and maintenance is expected to be total.<br />

Example 2:<br />

Here is a GIS solution (<strong>Schneider</strong> <strong>Electric</strong> CGset) with an air insulated<br />

connection (and possibly VT) compartment.<br />

This compartment is accessible (with tools).<br />

The other HV compartments are not accessible.<br />

Access to the connection compartment is possible with the busbar(s) live,<br />

meaning all other functional units can be kept operating.<br />

The LSC classification applies, and such solution is LSC2.<br />

Example 3:<br />

Here is a GIS solution (<strong>Schneider</strong> <strong>Electric</strong> GMset) with an air insulated<br />

connection (and possibly VT) compartment. This compartment is<br />

accessible and interlocked with the earthing function.<br />

The circuit breaker can be extracted (tool access compartment), even if<br />

that is not considered as normal operation nor normal maintenance.<br />

Access to one functional unit within a switchboard does not require any<br />

other functional unit to be switched off. Such solution is LSC2A.<br />

Example 4:<br />

A mixed technology (<strong>Schneider</strong> <strong>Electric</strong> GenieEvo) with an air insulated<br />

connection compartment, and an air insulated main switching device<br />

which can be extracted with the busbar live, thanks to the disconnector.<br />

Single line diagram is similar to example 2.<br />

If both the connection compartment and the circuit breaker compartment<br />

are accessible, and access to any of them means the cables are first<br />

switched off and earthed. Category is LSC2A.<br />

11