Switchgear defi nition <strong>Voltage</strong> transformer<br />

AMTED300014EN.indd<br />

Transformation ratio (Kn)<br />

Kn = Upr<br />

Usr<br />

<strong>Voltage</strong> ratio error<br />

N1<br />

= for a VT<br />

N2<br />

This is the error that the transformer introduces into the voltage<br />

measurement.<br />

(Kn Usr – Upr) • 100<br />

<strong>Voltage</strong> error % =<br />

Upr<br />

Kn = transformation ratio<br />

Phase error or phase-shift error<br />

This is the phase difference between the primary voltage Upr and<br />

the secondary voltage Usr. It is expressed in minutes of angle.<br />

The thermal power limit or rated continuous power<br />

This is the apparent power that the transformer can supply in steady state<br />

at its rated secondary voltage without exceeding the temperature rise limits<br />

set by the standards.<br />