Standards IEC – ANSI/IEEE comparison<br />
AMTED300014EN.indd<br />
b For routine tests, auxiliary circuits are checked at 1500 V x 1 min in ANSI<br />
(C37.20.3) instead of 2 kV x 1 min for IEC.<br />
b ANSI switches according to C37.20.4 shall perform load-breaking tests<br />
before any of the optional rating tests (fault making for integral switch-fuse,<br />
cable charging switching current, unloaded transformer switching current).<br />
b Dielectric test as condition check after power tests or mechanical<br />
endurance tests is specified at 80% of the rated power frequency withstand<br />
voltage by IEC (common clauses), and only at 75% by ANSI (C37.20.4).<br />
b<br />
Fuse to checked current to ground during power tests of switches<br />
is specified differently in IEC and ANSI (100 mm long and 0.1mm diameter<br />
for IEC, 3 A rating or 2 inches long and #38AWG for ANSI).<br />
81