<strong>SAFT</strong> AMERICA INC.<br />

Component Maintenance Manual<br />

1159SCAV519-1<br />

if the duration of the second discharge is less than 1 hr. At<br />

C1 (less than 122 min. At 0.5C1), or if the voltage of some<br />

cells is less than 1 V D.C. within 1 hour of discharge (122<br />

min. At 0.5C1 ), the battery should undergo a more complete<br />

overhaul. Perform the complementary checks [see para.<br />

(b)].<br />

(b) Complementary checks<br />

The capacity supplied by the battery is :<br />

53 A • number of minutes before 21 V D.C. / 60 = Number of<br />

Ampere-hours (Ah), or divide by 122 if using 0.5C1<br />

If the capacity is not greater than 53 Ah, or if the voltage of each cell<br />

rises too quickly during charging, drops, or is excessively low at the<br />

end of charge, some cells may have been insufficiently balanced, the<br />

volume of added water is insufficient, or the cell separators are<br />

damaged.<br />

Repeat the balancing operations more accurately by discharging at<br />

10 A.<br />

Meanwhile, regularly measure and note the voltage of each cell,<br />

observing the sequence of measurement. Locate and shunt the cells<br />

whose voltage drops below 1 to 0.9 V D.C. using a 1-ohm (10 W)<br />

resistor.<br />

Stop discharging at the latest when the voltage reaches 10 V across<br />

the battery terminals. Keep the shunts in place as described in<br />

paragraph (2) (b).<br />

Repeat the remaining operations: slow-rate charging [see para. A. (2)<br />

(b)], checking the levels [see para. (3) (b)] and a new test discharge<br />

[see para (a)].<br />

Regularly check the voltage of each cell during the first and last hour<br />

of charging.<br />

At the end of this test, discard the following cells whose operation is<br />

defective:<br />

cells not reaching 1.2 V D.C. after 5 min. Charging,<br />

24-34-01<br />

PAGE 111<br />

AUG 30/96