27.03.2013 Views

Water Specification [DOC] - City of Barrie

Water Specification [DOC] - City of Barrie

Water Specification [DOC] - City of Barrie

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

i<br />

February, 2005<br />

DISCLAIMER<br />

The <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> has supplied these <strong>Specification</strong>s, Standard Drawings and Materials Lists with the<br />

express understanding that it shall not be liable in any manner whatsoever to any person, corporation<br />

or organization for damages, injuries or costs resulting from the use <strong>of</strong> the information supplied.<br />

The information contained herein is not to be reproduced, sold or given in any manner without the<br />

prior consent <strong>of</strong> the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>.<br />

The <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> reserves the right to amend, alter or to accept revisions to these <strong>Specification</strong>s at<br />

any time without further notice.<br />

It is everybody’s responsibility to check with the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> for new revisions.<br />

Last Revision Date: February, 2005


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

ii<br />

February, 2005<br />

SECTION “A” - INTRODUCTION<br />

TABLE OF CONTENTS<br />

1.0 Introduction..............................................................................................................................A-<br />

1<br />

2.0 Definitions................................................................................................................................A-<br />

1<br />

SECTION “B” - DESIGN CRITERIA<br />

1.0 Design Criteria General...........................................................................................................B-1<br />

2.0 Flow Calculations ....................................................................................................................B-2<br />

3.0 <strong>Water</strong>main................................................................................................................................B-3<br />

4.0 Hydrants ...................................................................................................................................B-4<br />

5.0 Restraining <strong>Water</strong>main............................................................................................................B-4<br />

6.0 Fittings......................................................................................................................................B-4<br />

7.0 <strong>Water</strong>main Offsets ...................................................................................................................B-4<br />

8.0 <strong>Water</strong>main Bedding.................................................................................................................B-5<br />

9.0 Services ....................................................................................................................................B-5<br />

10.0 Service Saddles........................................................................................................................B-5<br />

11.0 Tappings...................................................................................................................................B-5<br />

12.0 Valves.......................................................................................................................................B-5<br />

13.0 Maximum Joint Deflection Full-Length Ductile Iron Pipe<br />

Mechanical Joint Pipe (Charts) ...............................................................................................B-6<br />

14.0 PVC <strong>Water</strong>main.......................................................................................................................B-8<br />

SECTION “C” - SUBMISSION OF PLANS AND APPROVALS<br />

1.0 Plans .........................................................................................................................................C-1<br />

2.0 Approvals.................................................................................................................................C-1<br />

3.0 MOE Approvals.......................................................................................................................C-3<br />

SECTION “D” - INSPECTION<br />

1.0 Inspection General................................................................................................................. D-1<br />

2.0 Contractor’s Supervision....................................................................................................... D-2


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

iii<br />

February, 2005<br />

SECTION “E” - BY-LAWS AND AGREEMENTS<br />

1.0 Liability Insurance ...................................................................................................................E-1<br />

SECTION “F” - INSTALLATION AND CONSTRUCTION<br />

1.0 Installation and Construction...................................................................................................F-1<br />

2.0 Materials...................................................................................................................................F-1<br />

3.0 <strong>Water</strong>main and Appurtenances ...............................................................................................F-1<br />

4.0 Tracer Wire ..............................................................................................................................F-2<br />

5.0 Hydrants ...................................................................................................................................F-2<br />

6.0 Services ....................................................................................................................................F-3<br />

7.0 Restraining ...............................................................................................................................F-3<br />

8.0 Fittings......................................................................................................................................F-3<br />

9.0 Fill Areas..................................................................................................................................F-3<br />

10.0 Bedding ....................................................................................................................................F-3<br />

11.0 Protection <strong>of</strong> Existing Utilities................................................................................................F-4<br />

12.0 Locates .....................................................................................................................................F-4<br />

13.0 Testing......................................................................................................................................F-4<br />

14.0 Initial Tie-In .............................................................................................................................F-5<br />

15.0 Swabbing/Charging the <strong>Water</strong>main........................................................................................F-6<br />

16.0 Pressure Testing.......................................................................................................................F-6<br />

17.0 Chlorinating .............................................................................................................................F-7<br />

18.0 Flushing....................................................................................................................................F-7<br />

19.0 Sampling ..................................................................................................................................F-8<br />

20.0 Continuity Test.........................................................................................................................F-8<br />

21.0 Tie-Ins ......................................................................................................................................F-8<br />

SECTION “G” - RESIDENTIAL DOMESTIC WATER SERVICES<br />

1.0 Design.......................................................................................................................................G-<br />

1<br />

2.0 Installation................................................................................................................................G-<br />

1<br />

3.0 Residential Service <strong>Specification</strong>s ..........................................................................................G-<br />

2<br />

4.0 Residential Service Inspections...............................................................................................G-<br />

3<br />

5.0 Procedure for Pressure Testing Residential <strong>Water</strong> Services..................................................G-<br />

3<br />

6.0 <strong>Water</strong> Service Repair Procedure .............................................................................................G-<br />

4<br />

7.0 Domestic <strong>Water</strong> Meters...........................................................................................................G-<br />

4<br />

8.0 Care <strong>of</strong> <strong>Water</strong> Meters ..............................................................................................................G-<br />

5


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

iv<br />

February, 2005<br />

9.0 Location <strong>of</strong> <strong>Water</strong> Meters in Residences<br />

G-5<br />

10.0 Remote Wire Installation/Inspection ......................................................................................G-<br />

5<br />

11.0 Failure to Register Properly.....................................................................................................G-<br />

5<br />

12.0 Testing......................................................................................................................................G-<br />

5<br />

13.0 Dispute Test <strong>of</strong> <strong>Water</strong> Meters .................................................................................................G-<br />

5<br />

14.0 Discontinue the Supply............................................................................................................G-<br />

5<br />

15.0 Draining the Plumbing.............................................................................................................G-<br />

6<br />

16.0 Not for Resale ..........................................................................................................................G-<br />

6<br />

SECTION “H” – GENERAL SERVICES<br />

1.0 General Requirements ........................................................................................................... H-1<br />

2.0 Drawing Requirements.......................................................................................................... H-2<br />

3.0 <strong>Specification</strong>s for General Services Domestic and Fire Services........................................ H-3<br />

4.0 General Service <strong>Water</strong> Meters .............................................................................................. H-4<br />

5.0 Fire Services........................................................................................................................... H-6<br />

6.0 Testing Procedure .................................................................................................................. H-6<br />

7.0 Swabbing/Charging the <strong>Water</strong>main...................................................................................... H-7<br />

8.0 Pressure Testing..................................................................................................................... H-7<br />

9.0 Chlorinating ........................................................................................................................... H-9<br />

10.0 Flushing.................................................................................................................................. H-9<br />

11.0 Sampling ................................................................................................................................ H-9<br />

12.0 Continuity Testing ................................................................................................................. H-9<br />

SECTION “I” - FREEHOLD/CONDOMINIUM TOWNHOUSE PROJECTS DEVELOPED<br />

UNDER SITE PLAN<br />

1.0 Site Plan....................................................................................................................................I-1<br />

2.0 Design Criteria.........................................................................................................................I-1<br />

3.0 Installation and Construction <strong>of</strong> Freehold Projects on <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Right Of Way<br />

<strong>Water</strong>main..........................................................................................................................I-1<br />

<strong>Water</strong> Services...................................................................................................................I-2<br />

<strong>Water</strong> Meters .....................................................................................................................I-2<br />

4.0 Condominium - Private<br />

<strong>Water</strong>main..........................................................................................................................I-2<br />

<strong>Water</strong> Services...................................................................................................................I-2<br />

<strong>Water</strong> Meters .....................................................................................................................I-2<br />

SECTION “J” -CITY OF BARRIE CHARGES


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

v<br />

February, 2005<br />

1.0 <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Charges.............................................................................................................J-1<br />

SECTION “K” - MATERIAL DATA SHEETS<br />

1.0 <strong>Water</strong>main................................................................................................................................K-<br />

1<br />

2.0 <strong>Water</strong> Services .........................................................................................................................K-<br />

1<br />

3.0 <strong>Water</strong>main Fittings & Couplings ............................................................................................K-<br />

1<br />

4.0 <strong>Water</strong>main Valves ...................................................................................................................K-<br />

2<br />

5.0 Hydrants ...................................................................................................................................K-<br />

3<br />

6.0 Valve Boxes.............................................................................................................................K-<br />

3<br />

7.0 Valve Stem Extension .............................................................................................................K-<br />

4<br />

8.0 Restraining Glands...................................................................................................................K-<br />

4<br />

9.0 Metallic Caution Tape .............................................................................................................K-<br />

5<br />

10.0 Tracer Wire ..............................................................................................................................K-<br />

5


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Table <strong>of</strong> Contents<br />

vi<br />

February, 2005<br />

11.0 Tie-Rods...................................................................................................................................K-<br />

6<br />

<strong>Water</strong> Service Materials:<br />

12.0 Service Boxes...........................................................................................................................K-<br />

6<br />

13.0 Service Box Rods ....................................................................................................................K-<br />

6<br />

14.0 Service Saddles........................................................................................................................K-<br />

6<br />

15.0 Spacers .....................................................................................................................................K-<br />

7<br />

16.0 Metering ...................................................................................................................................K-<br />

7<br />

17.0 Main Stop.................................................................................................................................K-<br />

9<br />

18.0 Curb Stop ............................................................................................................................. .K-10<br />

19.0 Couplings ............................................................................................................................. .K-10<br />

20.0 Angle Meter Stops ............................................................................................................... .K-11


A-1<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “A” - Introduction<br />

February, 2005<br />

1.0 INTRODUCTION<br />

The purpose <strong>of</strong> the following specification is to provide a guideline for the design, materials<br />

and installation <strong>of</strong> water systems connected to the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> <strong>Water</strong> Distribution System.<br />

This information will be made available to Consulting Engineers, Subdividers, Contractors<br />

or any individual wanting to make any connection to the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> <strong>Water</strong> Distribution<br />

System.<br />

This specification is applicable to installation <strong>of</strong> services and watermains up to and including<br />

400mm in diameter. Installations <strong>of</strong> watermains larger than 400mm in diameter or for any<br />

special installation shall be reviewed on an individual basis by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

Engineering Department.<br />

The information found in this specification is to be used in conjunction with the terms <strong>of</strong> the<br />

Subdivider’s Agreement and/or Site Plan Agreement issued by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

Engineering Department.<br />

This information will be a supplement to any additional or updated specification, approved<br />

by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>.<br />

2.0 DEFINITIONS<br />

In this specification the following definitions shall apply:<br />

The word "<strong>City</strong>" shall mean the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>.<br />

The word "Contractor" shall mean the firm <strong>of</strong> Contractors, the company or individual<br />

acting as the Contractor and having entered into a contract with the Developer/Owner to<br />

install the watermains, services and/or appurtenances.<br />

The words "Developer(s)/Owner(s)" shall mean the person(s) appearing on the last revised<br />

assessment role <strong>of</strong> the Corporation <strong>of</strong> the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> to be the Owner(s) <strong>of</strong> the land.<br />

The words "<strong>City</strong> Representative" shall mean any person assigned to a project by the <strong>City</strong> to<br />

carry out work on their behalf. The name <strong>of</strong> the Representative shall be specified prior to the<br />

start <strong>of</strong> construction on any project.<br />

The word "Consultant" shall mean pr<strong>of</strong>essional engineers authorized to practice in Ontario<br />

and shall be responsible for the preparation <strong>of</strong> drawings and specifications for the proposed<br />

extension to the water distribution system to the satisfaction <strong>of</strong> the <strong>City</strong>'s Engineering<br />

Department. The Consultant shall act on behalf <strong>of</strong> the Developer/Owner.<br />

The word "Lateral" shall mean every water pipe installed from the watermain to serve one<br />

lot.


A-2<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “A” - Introduction<br />

February, 2005<br />

“AWWA” shall mean the American <strong>Water</strong> Works Association.<br />

“OPSD” shall mean the Ontario Provincial Standard Drawings.<br />

“ODWS” shall mean the Ontario Drinking <strong>Water</strong> Standards<br />

The words “General Service(s)” shall mean Industrial, Commercial, Institutional, and<br />

Multi-Residential


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

B-1<br />

February, 2005<br />

1.0 DESIGN CRITERIA GENERAL<br />

1.1 The Developer/Owner shall employ a Pr<strong>of</strong>essional Engineer, authorized to practice in<br />

Ontario, to design the watermain in conjunction with all sewers, roads, elevations and other<br />

services, in order that all services will be properly co-ordinated.<br />

1.2 The proposed development must be serviced from the municipal water distribution system.<br />

1.3 In order to provide proper and reliable water distribution systems within the development,<br />

reasonable looping <strong>of</strong> these systems shall be provided to the satisfaction <strong>of</strong> the <strong>City</strong>'s<br />

Representative.<br />

1.4 Should the Developer/Owner propose to "phase" the servicing <strong>of</strong> this development, the <strong>City</strong><br />

reserves the right to comment and/or alter the proposal, in order to service the development<br />

in a logical order.<br />

1.5 The Developer/Owner shall submit detailed engineering drawings for the water distribution<br />

design.<br />

1.6 The Developer/Owner and his Consultant shall propose the size <strong>of</strong> the watermain to<br />

accommodate the development. <strong>Water</strong>main size shall be determined by fire flow plus<br />

maximum day use. Fire flows shall meet the following criteria: Flows to be calculated using<br />

formula on page B-2.<br />

a) Residential Single Family Streets: minimum 57 l/sec (750 gpm) @ 138 kpa residual<br />

(20 psi); preferred 76 l/sec (1,000 gpm) @ 138 kpa residual (20 psi).<br />

b) Institutional/Convenience Commercial: minimum 91 l/sec (1,200 gpm) @ 138 kpa<br />

residual (20 psi); preferred 114 l/sec (1,500 gpm) @ 138 kpa residual (20 psi).<br />

c) Industrial/Commercial Subdivisions: minimum 136 l/sec (1,800 gpm) @ 138 kpa<br />

residual (20 psi); preferred 152 l/sec (2,000 gpm) @ 138 kpa residual (20 psi).<br />

d) Downtown Commercial: minimum 136 l/sec (1,800 gpm) @ 138 kpa residual (20<br />

psi); preferred 189 l/sec (2,500 gpm) @ 138 kpa residual (20 psi).


B-2<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

2.0 FLOW CALCULATIONS<br />

2.1 Typical Hydrant Flow Calculations:<br />

Calculate Flow at 20 P.S.I. Residual Pressure<br />

QA = QT ha<br />

ht<br />

QA = Flow at 20 P.S.I.<br />

QT = Flow at Test<br />

ha = Pressure Drop Available<br />

ht = Pressure Drop at Test<br />

Example: Static - 56 PSIG; Residual - 40 PSIG; Flow - 976 GPM<br />

56 - 20<br />

QA = 976 = 1464 GPM<br />

56 - 40<br />

2.2 Oversizing <strong>of</strong> watermains would be considered as any watermain larger than 200 mm in<br />

diameter. The <strong>City</strong> would entertain compensating the Developer the difference in the cost <strong>of</strong><br />

materials between a 200 mm diameter watermain and an oversized watermain. Each project<br />

would require <strong>City</strong> approval on an individual basis. Should this approval be granted, the<br />

developer would be entitled to compensation at the time the service main is approved and<br />

connected to the <strong>City</strong> system.<br />

2.3 Oversizing will not be considered should the design for fire flows and maximum daily<br />

demand within a particular development dictate the use <strong>of</strong> a watermain in excess <strong>of</strong> 200 mm<br />

in diameter.<br />

2.4 Should the Ministry <strong>of</strong> the Environment conclude the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> does not have sufficient<br />

water reserve capacity to adequately service the site; the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> draft plan comments<br />

shall become null and void until the capacity issue can be resolved to the satisfaction <strong>of</strong> the<br />

Ministry <strong>of</strong> the Environment.<br />

2.5 The <strong>City</strong> Representative shall review the preliminary drawings, make comments and discuss<br />

any changes required with the Developer/Owner and/or his Consultant.<br />

2.6 Engineering drawings submitted shall include water distribution designs, and driveway<br />

locations (see page C-1). It will be the Developer/Owner’s responsibility to co-ordinate all<br />

utility plants (including; gas, hydro electric, TV cable and telephone cable) so that conflicts<br />

(including driveways) do not occur in the field, on boundary roads or on proposed internal<br />

streets. It will be the sole responsibility <strong>of</strong> the Developer/Owner for all relocations and costs<br />

incurred, as deemed appropriate by the <strong>City</strong>.<br />

2.7 The Developer/Owner shall have survey markers and/or property bars defining the boundary<br />

<strong>of</strong> each lot, easement and road allowance.


B-3<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

2.8 The Developer/Owner shall obtain all necessary permits and consents associated with the<br />

excavation and the installation <strong>of</strong> water distribution systems on existing <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> road<br />

allowances.<br />

3.0 WATERMAIN<br />

3.1 The <strong>City</strong> will permit the use <strong>of</strong> Polyvinyl Chloride PVC (Class 150) or Ductile Iron<br />

(Class 52) watermains up to and including 400 mm diameter pipe size. PVC watermain<br />

must be used when a soils report indicates aggressive soils. The <strong>City</strong> Representative<br />

reserves the right to impose the type <strong>of</strong> watermain material.<br />

3.2 All PVC watermain shall be colour coded blue. <strong>Water</strong>mains shall be installed with a<br />

minimum cover <strong>of</strong> 1.7 metres over the mains in urbanized areas, and 2.2 metres in rural<br />

areas.<br />

3.3 <strong>Water</strong>mains shall be located on the opposite side <strong>of</strong> the road from the proposed hydro<br />

distribution and opposite to the sidewalk. If sidewalks are installed on each side <strong>of</strong> the<br />

roadway, then the watermain shall be located on the north and west side <strong>of</strong> the street<br />

opposite the hydro distribution.<br />

3.4 All watermains in a cul-de-sac shall conform to BSD-55 showing typical cul-de-sac<br />

watermain design, as directed by the <strong>City</strong> Representative.<br />

3.5 Hydrants shall be installed on all dead end watermains. At the discretion <strong>of</strong> the <strong>City</strong>’s<br />

Representative, a blow-<strong>of</strong>f may be utilized instead <strong>of</strong> the hydrant.<br />

3.6 The minimum size <strong>of</strong> a watermain shall be 150 mm in diameter.<br />

3.7 The minimum horizontal separation between the watermain and the sanitary/storm sewer is<br />

to be 2.5 metre sunless otherwise indicated on standard drawings.<br />

3.8 A minimum <strong>of</strong> 0.5 metre vertical clearance between the watermain and all utilities must be<br />

kept, while still maintaining a minimum depth <strong>of</strong> cover at all times.<br />

3.9 All fill areas, where the Developer/Owner’s water system is to be placed, shall be filled to<br />

sub-grade prior to installation. Fill areas shall be compacted to a minimum <strong>of</strong> 95% Standard<br />

Proctor Density prior to the installation <strong>of</strong> the watermain.<br />

3.10 In non-standard locations, such as easements, parks, townhouses/condominium<br />

developments and reconstruction projects, metallic warning tape shall be used over all<br />

watermain. The metallic warning tape shall be terminated at hydrants. The metallic warning<br />

tape shall be laid in the trench 0.3 metres (12”) to 0.5 metres (19”) directly above the PVC<br />

watermain.


B-4<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

4.0 HYDRANTS<br />

4.1 Hydrant flange elevations shall be set at a grade that will give a flange elevation <strong>of</strong> 50 mm to<br />

100 mm above final grade.<br />

4.2 Hydrants shall maintain a minimum <strong>of</strong> 1.5 metres clearance from the edge <strong>of</strong> driveways,<br />

roadways, utilities or other above grade obstacles.<br />

5.0 RESTRAINING WATERMAIN<br />

Restrained watermain shall be used where any utility is located in excess <strong>of</strong> 5.5 metres below<br />

finished grade and future excavation may expose the watermain. Restraint on Ductile Iron<br />

watermain shall be obtained by using tie rods with bell clamps, complete with a welded ring<br />

by the manufacturer, on the spigot end <strong>of</strong> the ductile iron pipe. All steel rods shall be<br />

stainless steel. Restraint for PVC watermain shall be obtained by using restraining glands.<br />

Refer to BSD-47 showing a typical restrained watermain.<br />

6.0 FITTINGS<br />

Mechanical joint Ductile Iron fittings shall be used on Ductile Iron watermain. Mechanical<br />

joint fittings or PVC push-on fittings that meet AWWA <strong>Specification</strong> C-907 and CSA<br />

B137.2 shall be used where applicable, on 150 mm to 400 mm in diameter PVC watermains.<br />

Should Ductile Iron mechanical joint fittings be employed, the Contractor shall install<br />

sacrificial caps on every bolt. PVC joints using mechanical joint fittings are to be square cut,<br />

not bevelled.<br />

7.0 WATERMAIN OFFSETS<br />

7.1 Typical watermain <strong>of</strong>fset from property line shall be in accordance with the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

Road Allowance <strong>Specification</strong>s (see BSD-01 through BSD-7B and BSD-43). Anyone<br />

making a connection to the existing watermain distribution system must make an application<br />

to the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> for Municipal Consent. No construction shall begin without receiving<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Municipal Consent.<br />

7.2 The standard <strong>of</strong>fset <strong>of</strong> all watermains must be maintained on any curved line. Pipe<br />

deflection should be used wherever possible to minimize the use <strong>of</strong> bends. Wherever it is<br />

necessary to deflect from a straight line, either in the vertical or horizontal plane, the amount<br />

<strong>of</strong> deflection shall not exceed that required for satisfactory making up <strong>of</strong> the joint, as directed<br />

by the manufacturer. If, in the opinion <strong>of</strong> the <strong>City</strong> Representative the deflection is excessive,<br />

he will order the pipe removed and reinstalled with the use <strong>of</strong> bends and proper thrust<br />

restraint, in order to provide for acceptable deflection. Refer to the table and chart on pages<br />

B-6 through B-8.


B-5<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

8.0 WATERMAIN BEDDING<br />

<strong>Water</strong>main shall be constructed with beddings as per OPSD 802.010 (granular ‘A’<br />

embedment material) for flexible pipes and OPSD 802.030 or 802.031 class ‘B’ (granular<br />

‘A’ bedding material, granular ‘A’ or select native cover material) for rigid pipe unless<br />

otherwise approved by the Director <strong>of</strong> Engineering, or alternative embedment material.<br />

Alternative embedment material shall be sand meeting gradation requirements <strong>of</strong> OPS<br />

1004.05.05 compacted to 95% Standard Proctor Density. Geotechnical certification <strong>of</strong><br />

alternative material and compaction must be provided every 150 metres. The compaction<br />

testing must include the entire envelope (haunches, bedding and top <strong>of</strong> pipe).<br />

9.0 SERVICES<br />

Residential - Refer to Section G<br />

General Service - Refer to Section H<br />

10.0 SERVICE SADDLES<br />

Service saddles must be used on all PVC watermain and on ductile iron watermain where<br />

tapping size is 38 mm or 50 mm.<br />

11.0 TAPPINGS<br />

11.1 Ductile Iron watermain services larger than 25 mm require a tapping saddle and sleeve and<br />

shall be located at the 3 o’clock and 9 o’clock position.<br />

11.2 On PVC watermain, tapping <strong>of</strong> 19 mm to 25 mm shall be at the 10 o’clock or 2 o’clock<br />

position. The tap must not be closer than 600 mm from the ends <strong>of</strong> the pipe. Avoid tapping<br />

into discoloured areas <strong>of</strong> the pipe and do not tap a curved pipe. All tappings on PVC<br />

watermain require saddles.<br />

11.3 Tappings <strong>of</strong> 38 mm to 50 mm shall be at the 3 o’clock or 9 o’clock position. Only approved<br />

PVC tapping machines are to be used on PVC watermain by competent personnel and a<br />

protective blanket must be used if tapping under pressure. Extra precaution should be taken<br />

during installation in cold weather.


B-6<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

12.0 VALVES<br />

12.1 All valves are to be resilient seat gate valves, complete with valve box, on watermains up to<br />

and including 400 mm. Valves may be mechanical joint or push-on.<br />

12.2 Valves shall be installed with a maximum separation <strong>of</strong> 305 metres in all areas, or with a<br />

maximum <strong>of</strong> 60 services between valves.<br />

12.3 Valves shall be located at intersections so as to be in the boulevard behind the curb radius.<br />

12.4 Valves in excess <strong>of</strong> 1.7 metres in depth shall require a valve stem extension.<br />

12.5 Three (3) valves shall be located at tee intersections. Where no services connect to the main<br />

between valve locations, one (1) valve may be eliminated upon <strong>City</strong> approval.<br />

12.6 Four (4) valves shall be located at cross intersections.<br />

12.7 Pressure reducing valves may be required in certain areas within the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> limits.<br />

Pressure reducing valves are not to be used as standard installations, but as special<br />

installations, at the discretion <strong>of</strong> the <strong>City</strong>'s Representative. The setting <strong>of</strong> valves shall be<br />

determined by the <strong>City</strong> Representative. All pressure reducing valves shall be installed in an<br />

approved pre-cast chamber.<br />

13.0 MAXIMUM JOINT DEFLECTION FULL-LENGTH<br />

DUCTILE IRON PIPE -- MECHANICAL JOINT PIPE<br />

Pipeline Curve Geometry<br />

O = deflection angle<br />

S = joint deflection <strong>of</strong>fset<br />

L = laying <strong>of</strong> length<br />

R = radius <strong>of</strong> curve<br />

R = L<br />

2 tan 0/2


B-7<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

NOMINAL<br />

PIPE SIZE<br />

INCHES<br />

DEFLECT<br />

ANGLE - 0<br />

DEGREES<br />

MAXIMUM OFFSET--S*<br />

in (m)<br />

L* = 18 ft<br />

(5.5 m)<br />

L* = 20 ft<br />

(6.1m)<br />

APPROX. RADIUS OF<br />

CURVE--R* PRODUCED<br />

BY SUCCESSION OF<br />

JOINTS.<br />

ft (m)<br />

L* = 18 ft<br />

(5.5 m)<br />

L* = 20 ft<br />

(6.1 m)<br />

4 (100 mm) 8-18 31 (0.79) 35 (0.89) 125 (38) 140 (43)<br />

6 (150 mm) 7-07 27 (0.69) 30 (0.76) 145 (44) 160 (49)<br />

8 (200 mm) 5-21 20 (0.51) 20 (0.56) 195 (59) 220 (67)<br />

10 (250 mm) 5-21 20 (0.51) 20 (0.56) 195 (59) 220 (67)<br />

12 (300 mm) 5-21 20 (0.51) 20 (0.56) 195 (59) 220 (67)<br />

16 (400 mm) 3-35 13.5 (0.34) 15 (0.38) 285 (87) 320 (98)<br />

18 (450 mm) 3-00 11 (0.28) 12 (0.30) 340 (104) 380 (116)<br />

20 (500 mm) 3-00 11 (0.28) 12 (0.30) 340 (104) 380 (116)<br />

Section C600 AWWA Standards<br />

NOMINAL<br />

PIPE SIZE<br />

INCHES<br />

MAXIMUM JOINT DEFLECTION* FULL-LENGTH<br />

DUCTILE IRON PIPE -- PUSH-ON TYPE JOINT PIPE<br />

DEFLECT<br />

ANGLE - 0<br />

DEGREES<br />

MAXIMUM OFFSET--S*<br />

in (m)<br />

L* = 18 ft<br />

(5.5 m)<br />

L* = 20 ft<br />

(6.1 m)<br />

APPROX. RADIUS OF<br />

CURVE--R* PRODUCED<br />

BY SUCCESSION OF<br />

JOINTS<br />

ft (m)<br />

L* = 18 ft<br />

(5.5 m)<br />

L* = 20 ft<br />

(6.1 m)<br />

4 (100 mm) 5 19 (0.48) 21 (0.53) 205 (62) 230 (70)<br />

6 (150 mm) 5 19 (0.48) 21 (0.53) 205 (62) 230 (70)<br />

8 (200 mm) 5 19 (0.48) 21 (0.53) 205 (62) 230 (70)<br />

10 (250mm) 5 19 (0.48) 21 (0.53) 205 (62) 230 (70)<br />

12 (300 mm) 5 19 (0.48) 21 (0.53) 205 (62) 230 (70)<br />

16 (400 mm) 3* 11 (0.28) 12 (0.30) 340 (104) 380 (116)<br />

18 (450 mm) 3* 11 (02.8) 12 (0.30) 340 (104) 380 (116)<br />

20 (500 mm) 3* 11 (0.28) 12 (0.30) 340 (140) 380 (116)<br />

* For 16 inch and larger push-on joints, maximum deflection angle may be larger than shown<br />

above. Consult the manufacturer. Section C600 AWWA Standards.


B-8<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “B” - Design Criteria<br />

February, 2005<br />

14.0 PVC WATERMAIN<br />

14.1 Pipe Deflection<br />

On a radius, lengths should be assembled in a straight line and then curved in the trench. All<br />

curvatures result from the bending <strong>of</strong> the pipe lengths. Deflection <strong>of</strong> the joint is very slight,<br />

up to one degree. The Contractor shall follow, at all times, manufacturer specifications for<br />

pipe deflection.<br />

Offset per 20 ft (6.1 metres) Length Pipe Size<br />

4" (100 mm) - 24" (610 mm)<br />

6" (150 mm) - 17" (430 mm)<br />

8" (200 mm) - 12" (305 mm)<br />

10" (250 mm) - 11" (280 mm)<br />

12" (305 mm) - 9" (230 mm)<br />

16” (400 mm) - 6” (150 mm)


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

C-1<br />

February, 2005<br />

Section “C” - Submission <strong>of</strong> Plans and Approvals<br />

1.0 PLANS<br />

1.1 The Developer/Owner or his Consultant shall submit a proposed design for any extension <strong>of</strong><br />

the water distribution system to the <strong>City</strong>'s Engineering Department for approval.<br />

1.2 The preliminary submission shall consist <strong>of</strong> paper copies:<br />

Two (2) copies <strong>of</strong> the "Overall General Plan" (scales 1:500 to 1:2000)<br />

Two (2) copies <strong>of</strong> the "Plan and Pr<strong>of</strong>ile Drawings" (scale 1:500 or 1:250 horizontal and 1:50<br />

vertical)<br />

One (1) copy <strong>of</strong> the "Proposed Registered Plan"<br />

This preliminary plan shall show the size and type <strong>of</strong> watermain, the location <strong>of</strong> mains,<br />

valves, hydrants, services, bends, tees, and crosses in relation to all other utilities. The<br />

submission also shall include the location <strong>of</strong> proposed and existing elevation. These plans<br />

shall be on “D” standard size sheets <strong>of</strong> paper. This preliminary submission shall be reviewed<br />

by the <strong>City</strong>'s Engineering Department and one (1) copy shall be given back to the<br />

Developer/Owner showing all the changes that are required.<br />

1.3 The final submission shall consist <strong>of</strong> one (1) set <strong>of</strong> paper and one (1) set <strong>of</strong> mylar copies <strong>of</strong><br />

the following:<br />

"Overall General Plan" (scale 1:500 to 1:2000)<br />

"Plan and Pr<strong>of</strong>ile Drawings" (scale 1:500 or 1:250 horizontal and 1:50 vertical)<br />

"Ministry <strong>of</strong> the Environment Application for Approval <strong>of</strong> <strong>Water</strong> Works" and<br />

supporting documents.<br />

One (1) set <strong>of</strong> "mylars <strong>of</strong> Overall General Plan" and "mylars <strong>of</strong> Plan and Pr<strong>of</strong>ile<br />

Drawings" on D standard sheets, complete with the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> signature <strong>of</strong> approval for<br />

roads, watermain, sanitary and storm sewer locations.<br />

1.4 Digital data must be AutoCAD compatible with the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> and must be tied to the<br />

horizontal Cosine Network NAD83.<br />

2.0 APPROVALS<br />

2.1 The <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> will not release consent for the issue <strong>of</strong> building permits prior to the<br />

watermains and services being installed, approved and connected to the existing municipal<br />

water distribution system.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

C-2<br />

February, 2005<br />

Section “C” - Submission <strong>of</strong> Plans and Approvals<br />

2.2 Approval for construction shall be given if:<br />

1. The <strong>City</strong> has approved all drawings and materials;<br />

2. The <strong>City</strong> has received a complete set <strong>of</strong> mylars;<br />

3. The <strong>City</strong> has received a copy <strong>of</strong> the Ministry <strong>of</strong> the Environment Certificate <strong>of</strong><br />

Approval, and number;<br />

4. The Subdivider's Agreements have been signed;<br />

5. All Letters <strong>of</strong> Credit have been placed;<br />

6. All cash contributions have been made between the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> and the<br />

Developer(s)/Owner(s);<br />

7. All drawings pertaining to roads, sanitary, and storm sewer locations have been<br />

signed by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>;<br />

8. All Municipal Consents have been approved by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>;<br />

9. The <strong>City</strong> has received 48 hours notice prior to construction; and<br />

10. The required liability insurance has been taken out. Refer to Section E.<br />

2.3 Should the Subdivider’s Agreement not be signed, the Developer/Owner will be permitted to<br />

start work on their own lands once the following conditions are met:<br />

1. MOE Certificate <strong>of</strong> Approval obtained;<br />

2. The Engineering Fee is paid to the <strong>City</strong>;<br />

3. Insurance requirements are in place; and<br />

4. The housekeeping deposit is paid.<br />

No connection to existing municipal services or work on <strong>City</strong> property will be permitted<br />

until after registration <strong>of</strong> the Plan <strong>of</strong> Subdivision.<br />

2.4 All field or design changes affecting servicing drawings shall be forwarded to the <strong>City</strong><br />

Representative for comment prior to any further work proceeding.<br />

2.5 No tie-ins to the existing municipal water distribution system will be allowed until the<br />

Subdivider’s Agreement has been signed by all parties.<br />

2.6 Upon completion <strong>of</strong> the testing procedure, the Consultant shall deposit with the <strong>City</strong>, within<br />

30 days, mylar drawings showing "as-constructed" details <strong>of</strong> all watermains, fittings, water<br />

services and hydrant locations complete with constructed elevations. These drawings shall<br />

be drawn on “D” standard size sheets <strong>of</strong> mylar, with scales <strong>of</strong> 1:500 or 1:250 for "Plan and<br />

Pr<strong>of</strong>ile Drawings" and 1:500 to 1:2000 for "Overall General Plans".<br />

2.7 Failure to provide mylars and valve location drawings will result in the <strong>City</strong> taking the<br />

responsibility to produce "as-constructed" mylars. All associated costs shall be at the<br />

expense <strong>of</strong> the Developer/Owner.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

C-3<br />

February, 2005<br />

Section “C” - Submission <strong>of</strong> Plans and Approvals<br />

3.0 MOE APPROVALS<br />

The Applications for MOE Approval and Certificate <strong>of</strong> Approval must follow the most<br />

recent Guide for Applying for Approval <strong>of</strong> Municipal and Private <strong>Water</strong> and Sewage Works.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “D” - Inspection<br />

D-1<br />

February, 2005<br />

1.0 INSPECTION<br />

1.1 The <strong>City</strong> requires an inspection <strong>of</strong> all distribution systems installed.<br />

1.2. The Contractor shall notify the <strong>City</strong> Engineering Department 48 hours before commencing<br />

any work.<br />

1.3 The <strong>City</strong> does not provide full time inspection but a <strong>City</strong> Representative will be on site as<br />

long as required, to ensure proper installation, materials, and construction is adhered to as<br />

outlined in this document.<br />

1.4 The <strong>City</strong> Representative shall be introduced to the Contractor at the pre-construction<br />

meeting.<br />

1.5 The <strong>City</strong> Representative shall not be considered as a substitute for supervision by the Owner<br />

or his Contractor.<br />

1.6 The <strong>City</strong> Representative is not responsible for ensuring that the trench meets the criteria set<br />

out by the Occupational Health and Safety Act. Safety shall be adhered to at all times.<br />

1.7 The Developer/Owner shall pay the <strong>City</strong> for the services <strong>of</strong> the <strong>City</strong> Representative at<br />

regular rates Monday through Friday, 8:30 a.m. to 4:30 p.m.. Overtime rates shall apply for<br />

all other times, including statutory holidays and <strong>City</strong> holidays. When a contractor is going to<br />

work outside <strong>of</strong> normal working hours he should notify the <strong>City</strong>’s Engineering Department a<br />

minimum <strong>of</strong> 48 hours before work is to commence.<br />

1.8 The Contractor should follow all instructions given by a <strong>City</strong> Representative <strong>of</strong> the <strong>City</strong><br />

relating to the quality or type <strong>of</strong> material, installation or construction practices.<br />

1.9 The Developer/Owner agrees to have a surveyor verify the final installation grades,<br />

elevations and the trench locations for the watermain, main valves, hydrant valves and top<br />

flange elevations <strong>of</strong> the hydrants. The surveyor shall provide the <strong>City</strong> Representative with a<br />

daily written verification.<br />

1.10 The <strong>City</strong> Representative has the right to suspend the work immediately if the work practices<br />

being employed, the materials being used or the proposed layout is insufficient. This will be<br />

in the form <strong>of</strong> verbal notification, followed by a written notification. Work shall not<br />

recommence until the written notification has been rescinded by the <strong>City</strong> Representative.<br />

1.11 The <strong>City</strong> Representative, in consultation with the Consulting Engineer and the Design Staff,<br />

reserves the right to order field revisions at the expense <strong>of</strong> the Developer/Owner.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “D” - Inspection<br />

D-2<br />

February, 2005<br />

2.0 CONTRACTOR'S SUPERVISION<br />

The Contractor shall have a Supervisor/Foreman in charge at all times. This person shall be<br />

responsible for notices, communication or installation instructions and safety precautions.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “E” - By-Laws and Agreements<br />

E-1<br />

February, 2005<br />

1.0 LIABILITY INSURANCE<br />

1.1 The Contractor shall provide, maintain and pay for insurance and all required assessments to<br />

protect himself and the <strong>City</strong> from claims under the Workers' Compensation Act and from<br />

any other claims for damages arising from personal injury, including death, and for claims<br />

for property damage that may arise from his operation under this contract.<br />

1.2 The Developer/Owner shall save harmless, the <strong>City</strong>, its agents and employees from and<br />

against all claims, demands, losses, costs, damages, actions, suits and proceedings arising out<br />

<strong>of</strong> or attributable to any act or omission in connection with the development and servicing <strong>of</strong><br />

this plan <strong>of</strong> subdivision, and without limiting the generality <strong>of</strong> the foregoing, including<br />

inspections <strong>of</strong> the services arising out <strong>of</strong>, or attributable to the development.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-1<br />

February, 2005<br />

1.0 INSTALLATION AND CONSTRUCTION<br />

1.1 Prior to the installation <strong>of</strong> the watermain and appurtenances, the Contractor shall notify the<br />

<strong>City</strong>’s Representative 48 hours in advance.<br />

1.2 The Consultant/Contractor shall obtain all necessary permits and consents associated with<br />

the excavation and installation <strong>of</strong> water distribution systems on existing <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> road<br />

allowances. The Developer/Owner shall have survey markers and/or property bars defining<br />

the boundary <strong>of</strong> each lot, easement and road allowance.<br />

1.3 All construction shall conform to the <strong>City</strong>'s Standard <strong>Specification</strong>s and Drawings. During<br />

construction all watermain installations shall be in accordance with ANSI/AWWA Standard<br />

C651-99 - Disinfecting <strong>Water</strong>mains.<br />

2.0 MATERIALS<br />

2.1 The Contractor shall supply all materials for the watermain and appurtenances necessary for<br />

the complete watermain assembly.<br />

2.2 A complete list <strong>of</strong> materials, which will be used to install the water distribution system, shall<br />

be sent to the <strong>City</strong> Representative for approval before construction commences.<br />

2.3 The Contractor shall inspect all materials before installation and reject any pieces showing<br />

breaks, cracks or other defects. Before the watermain is lowered into the ground it shall be<br />

brushed out to ensure that there is no dirt or foreign material in the watermain or<br />

appurtenances.<br />

3.0 WATERMAIN AND APPURTENANCES<br />

3.1 Sacrificial caps shall be used on all mechanical joint fittings on every bolt. The Contractor<br />

shall provide for sufficient bolt lengths to accommodate the caps.<br />

Refer to the Material Data Sheet (Cathodic Protection) located on page K-4.<br />

3.2 Concrete thrust blocking shall be installed at all tees, vertical and horizontal bends, hydrants,<br />

ends <strong>of</strong> watermains and connections 100 mm and larger, as per OPSD 1103.010 and OPSD<br />

1103.020. PVC ‘tee’ pressure fittings require additional thrust blocking on either side <strong>of</strong> the<br />

tee legs. In cases where concrete thrust blocking is inappropriate, restraining glands may be<br />

used at the discretion <strong>of</strong> the <strong>City</strong>’s Representative.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-2<br />

February, 2005<br />

3.3 All watermain tees, horizontal bends and branch valves in fill areas shall be restrained with<br />

tie rods, 19 mm stainless steel, in addition to concrete thrust blocking.<br />

3.4 The Contractor shall install the pipe and appurtenances to the line and grades noted on the<br />

construction drawings, with a minimum depth cover <strong>of</strong> 1.7 metres in residential areas and 2.2<br />

metres in rural areas. The Contractor is responsible to notify the <strong>City</strong>’s Representative<br />

immediately <strong>of</strong> any discrepancies to line or grade.<br />

3.5 Bonding wedges, as supplied by the manufacturer are NOT to be installed on ductile iron<br />

pipe.<br />

3.6 All couplings must be installed with the proper restraining glands.<br />

4.0 TRACER WIRE<br />

4.1 All non-metallic and metallic reinforced watermains shall be installed with a #12 TWU<br />

stranded copper tracer wire along the spring line <strong>of</strong> the watermain. The tracer wire shall be<br />

wrapped around each joint <strong>of</strong> the watermain and brought to the surface at each hydrant and<br />

connected to flange bolt. A continuous length <strong>of</strong> wire must be used. If the wire must be<br />

joined, the appropriate wire connectors shall be used and wrapped with self-amalgamating<br />

tape to prevent corrosion. If no hydrants are available then some means <strong>of</strong> connecting to<br />

wire must be established.<br />

4.2 When non-metallic mains are connected to metallic mains, a tracer wire must be installed<br />

and bonded (cade weld) to metallic main.<br />

4.3 To ensure there is no damage to the tracer wire during or after construction, the <strong>City</strong>’s<br />

Representative shall do a continuity test on the wire during testing procedures. Should the<br />

<strong>City</strong>’s Representative find a problem with continuity or installation <strong>of</strong> the tracer wire, the<br />

Contractor/Developer shall be responsible for the repair, at no cost to the <strong>City</strong>.<br />

4.4 In non-standard locations, such as easements, parks, townhouse/condominium developments<br />

and reconstruction projects, metallic warning tape shall be used over all watermains. The<br />

metallic warning tape shall be laid in the trench 0.3 metres (12”) to 0.5 metres (19”) directly<br />

above the watermain.<br />

5.0 HYDRANTS<br />

5.1 All hydrants are to be connected to the watermain using a 150 mm ductile iron mechanical<br />

joint anchor tee complete with adjustable flange and resilient seat gate valve or PVC push-on<br />

tee, complete with restraining rods and clamps, from tee to the valve. The detail <strong>of</strong> the<br />

hydrant installation shall be according to BSD-50. Hydrant flange elevation should be set at<br />

a grade that will give a final flange elevation <strong>of</strong> 50 mm to 100 mm above final grade.<br />

5.2 Hydrants shall maintain an absolute minimum <strong>of</strong> a 1.5 metre clearance from the edge <strong>of</strong> all<br />

driveways, utilities or any other above grade obstacles.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-3<br />

February, 2005<br />

5.3 Maximum hydrant spacing is 152 metres in residential areas and 92 metres in General<br />

Service areas.<br />

5.4 Painting <strong>of</strong> hydrants will be completed by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> - refer to Section J.<br />

6.0 SERVICES<br />

Refer to Section G for Residential Services<br />

Refer to Section H for General Service Services<br />

7.0 RESTRAINING<br />

In all areas where the watermain is to be laid in fill areas or where other utilities will be<br />

located 5.5 metres or more below the finished grade or where, during installation <strong>of</strong> other<br />

utilities, will expose the watermain, the watermain shall be restrained in addition to thrust<br />

blocking. Restraint shall be achieved by using tie rods with bell clamps complete with a<br />

welded ring on the spigot end <strong>of</strong> the ductile iron pipe. All tie-rods shall be stainless steel.<br />

Refer to BSD-47.<br />

8.0 FITTINGS<br />

Mechanical joint fittings shall be used on Ductile Iron watermain. PVC push-on fittings or<br />

mechanical joint fittings that meet C-907 and CSA B137.2 shall be used on PVC watermain.<br />

9.0 FILL AREAS<br />

No watermain shall be laid in fill until the density reports have been submitted to, and<br />

approved by the <strong>City</strong>’s Representative. No watermain shall be laid in fill areas until such<br />

areas have been filled to sub-grade and compacted to 95% Standard Proctor Density. The<br />

<strong>City</strong>’s Representative shall receive a copy <strong>of</strong> the compaction reports.<br />

10.0 BEDDING<br />

10.1 <strong>Water</strong>main shall be constructed with beddings as per OPSD 802.010 (granular ‘A’<br />

embedment material) for flexible pipes and OPSD 802.030 or 802.031 Class ‘B’ (granular<br />

‘A’ bedding material, granular ‘A’ or select native cover material) for rigid pipe unless<br />

otherwise approved by the Director <strong>of</strong> Engineering, or alternative embedment material.<br />

Alternative embedment material shall be sand meeting gradation requirements <strong>of</strong> OPS<br />

1004.05.05 compacted to 95% Standard Proctor Density. Geotechnical certification <strong>of</strong><br />

alternative material must be provided every 150 metres. The compaction testing must<br />

include the entire envelope (haunches, bedding and top <strong>of</strong> pipe).


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-4<br />

February, 2005<br />

10.2 Cover is to be placed 0.3 metres minimum above the top <strong>of</strong> watermain grades and<br />

compacted to minimum <strong>of</strong> 95% Standard Proctor Density. Tests should be taken along the<br />

centre line <strong>of</strong> watermain at maximum intervals <strong>of</strong> 150 metres.<br />

10.3 In cases where native material is deemed unsuitable by the <strong>City</strong>’s Representative, backfill<br />

will be imported granular and shall be at the sole discretion <strong>of</strong> the <strong>City</strong>’s Representative.<br />

10.4 In areas where the <strong>City</strong>’s Representative allows a watermain to be installed with less than a<br />

minimum cover, the Contractor is to supply and install Styr<strong>of</strong>oam SM insulation or Urecon<br />

insulation as directed by the <strong>City</strong>’s Representative to protect watermains, hydrant leads and<br />

appurtenances.<br />

11.0 PROTECTION OF EXISTING UTILITIES<br />

11.1 It shall be the Contractor's responsibility to protect and support existing<br />

underground/overhead utilities, which may be encountered during the progress <strong>of</strong> the work.<br />

11.2 Any existing utilities, which have to be relocated, shall be at the Contractor's expense with<br />

no cost to the <strong>City</strong>.<br />

11.3 Utility poles, which require support, shall be held with the appropriate equipment as supplied<br />

by the Contractor, at his expense. The attachment <strong>of</strong> this equipment shall be made by the<br />

Utility Company. The Contractor must have a qualified person on-site at all times to operate<br />

any vehicle, used to support utility poles.<br />

12.0 LOCATES<br />

12.1 The Contractor must arrange for locates <strong>of</strong> all utilities by contacting the appropriate<br />

operating authority prior to any excavation on road allowance.<br />

12.2 The <strong>City</strong> will locate watermain and services on private property upon request. However, this<br />

will be at no liability to the <strong>City</strong>, and the locate will not be guaranteed.<br />

13.0 TESTING<br />

Testing <strong>of</strong> the system shall conform to the following sequence: initial tie-in, remove<br />

swabs/charge the watermain, pressure test, chlorinate the system, flush the system, take a<br />

water sample for bacteriological analysis, tracer wire continuity and complete final tie-ins.<br />

No tie-ins to the existing water distribution system shall be allowed until the Subdivision<br />

Agreement has been signed by all parties, all financial obligations have been fulfilled and all<br />

testing and sampling has been completed to the satisfaction <strong>of</strong> the <strong>City</strong>. When all the above<br />

conditions are met, the new system shall be connected to the existing system.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-5<br />

February, 2005<br />

14.0 INITIAL TIE-IN<br />

14.1 At the discretion <strong>of</strong> the <strong>City</strong>’s Representative, a Contractor may be permitted one initial tiein<br />

to the existing watermain by installing a new resilient seat gate valve. The Contractor<br />

shall supply all materials, excavation, labour, equipment and restoration. The <strong>City</strong>’s<br />

Representative shall be present to inspect the tie-in by the Contractor. Should there be an<br />

existing valve in place for tie-in purposes, the Contractor may utilize this valve with the<br />

understanding that should this valve fail, for any reason during the testing procedure, it shall<br />

be the Contractor's responsibility to replace the valve, including all labour, material and<br />

excavation. The <strong>City</strong>’s Representative shall determine the location <strong>of</strong> the tie-in. All<br />

required tappings, on existing charged watermains must be performed by the <strong>City</strong>. If a<br />

tapping sleeve and valve is required for the initial tie-in, they must be supplied and installed<br />

by the Contractor. A <strong>City</strong> Representative must be present during the installation.<br />

14.2 There shall be a daily charge for operation <strong>of</strong> a valve for filling the watermain.<br />

14.3 Failure to comply with this regulation will result in a charge, outlined in By-law 99-290<br />

located in Section E.<br />

14.4 Should the <strong>City</strong>’s Representative deem that circumstances do not allow an initial tie-in; then<br />

the Contractor shall use a by-pass complete with a check valve and shut<strong>of</strong>f. The location <strong>of</strong><br />

the by-pass shall be at the discretion <strong>of</strong> the <strong>City</strong>’s Representative.<br />

14.5 A <strong>City</strong> Representative must complete all tappings <strong>of</strong>f any existing charged watermain. The<br />

Contractor shall provide all materials, excavation, necessary safety devices, backfill and<br />

restoration to permit the <strong>City</strong>’s Representative to complete the tapping. The Contractor shall<br />

be responsible for all <strong>City</strong> costs associated with tapping watermains.<br />

14.6 The Contractor shall remove all temporary services from the watermain when the services<br />

are no longer needed and replace them with brass plugs.<br />

14.7 The Contractor shall not operate any existing valves, existing blow-<strong>of</strong>fs, existing hydrants or<br />

remove any anti-tampering devices for any reason.<br />

14.8 If an existing hydrant is used for by-pass purposes, there shall be a daily charge for installing<br />

and removing a gate valve, as supplied by the <strong>City</strong>. Only gate valves supplied by the <strong>City</strong><br />

shall be used. It shall be the Contractor's responsibility to supply a check valve immediately<br />

downstream <strong>of</strong> the <strong>City</strong>-installed gate valve.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-6<br />

February, 2005<br />

15.0 SWABBING/CHARGING THE WATERMAIN<br />

15.1 Swabs shall be supplied by the <strong>City</strong>’s Representative on the site. The swabs shall be<br />

numbered and the <strong>City</strong>’s Representative is required to witness the installation <strong>of</strong> swabs by<br />

the Contractor. A swabbing schedule shall be prepared by the Developer’s Consultant and<br />

approved by the <strong>City</strong>’s Representative. The swabbing schedule shall indicate where the<br />

swabs are to be installed and removed.<br />

15.2 Swabs up to and including 250 mm may be taken out <strong>of</strong> hydrants, if available. If hydrants<br />

are not located in suitable areas then risers shall be installed by the Contractor, at his<br />

expense, to facilitate the removal <strong>of</strong> swabs. All risers shall be properly restrained and<br />

installed above ground. All swabs over 250 mm must be taken out <strong>of</strong> risers. Refer to<br />

BSD-45.<br />

15.3 The <strong>City</strong>’s Representative shall remove the swabs. However, the Contractor shall be<br />

required to provide assistance, at his expense. The Contractor must supply a means <strong>of</strong><br />

swabbing the system as determined by the <strong>City</strong>’s Representative. It will be the responsibility<br />

<strong>of</strong> the Contractor, during swabbing, to supply a water course for the water to escape without<br />

causing damage/erosion to the existing grade <strong>of</strong> the property or adjacent properties.<br />

15.4 Any damage caused by swabbing the watermain must be restored to its original state or<br />

better, by the Contractor. The <strong>City</strong> shall not be responsible for any damage or repairs during<br />

swabbing.<br />

15.5 All swabs shall be accounted for and removed from the system prior to pressure testing the<br />

system. Any swabs that are not accounted for must be located and removed, including<br />

material, labour, equipment and excavation, with no cost to the <strong>City</strong>.<br />

16.0 PRESSURE TESTING<br />

16.1 The Contractor shall strive to install a system that has zero leakage and zero pressure drop<br />

when tested. Pressure testing <strong>of</strong> all new water systems will be completed by the <strong>City</strong>’s<br />

Representative.<br />

16.2 The pressure test will be for a two hour period at 150 psi zero leakage and zero pressure<br />

drop. If the pressure test meets this criterion, the system as a whole, shall be accepted.<br />

16.3 If the above criterion is not met, the system will be divided into sections no greater than<br />

305m in length. Each section will be tested individually and will be required to meet the<br />

allowable leakage and test pressure criteria, as outlined in the AWWA <strong>Specification</strong><br />

C-600-99; Section 4 "Hydrostatic Testing" and Section 4.1 "Pressure and Leakage Test".


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-7<br />

February, 2005<br />

16.4 All Contractor-installed main valves and hydrant valves are to be opened by the Contractor<br />

and checked by the <strong>City</strong>’s Representative, to ensure that all valves are open prior to any<br />

pressure test.<br />

16.5 The Contractor is responsible for the supply <strong>of</strong> a suitable pressure test location to allow <strong>City</strong><br />

Personnel to complete a pressure test. This test point will be a 19 mm service, complete with<br />

a main stop and curb stop and box. The service tail shall be above grade for easy access.<br />

16.6 The Contractor shall supply all materials, excavations, labour and equipment necessary for<br />

the pressure test, at no expense to the <strong>City</strong>.<br />

16.7 From November 01 to April 01, the contractor shall supply a heated enclosure, at their<br />

expense, to protect the pressure pump and to facilitate the test.<br />

16.8 Failure <strong>of</strong> the initial pressure test by the <strong>City</strong>’s Representative shall result in all further<br />

pressure tests being charged to the Contractor.<br />

17.0 CHLORINATING<br />

17.1 Upon approval <strong>of</strong> the pressure test, the <strong>City</strong>’s Representative shall proceed to chlorinate the<br />

new system, using a Contractor-supplied 19 mm temporary service. The service shall have a<br />

tail brought above grade a minimum <strong>of</strong> 1 metre to allow access for the chlorine pump. This<br />

service should be at the tie-in point on the newly-installed watermain. The point <strong>of</strong><br />

chlorination must be located in such a way that the new system is chlorinated using a flow <strong>of</strong><br />

water from the existing system to distribute the chlorine.<br />

17.2 The Contractor shall "NOT" operate any main valves, hydrant blow-<strong>of</strong>fs, by-passes or any<br />

other appurtenances within the new system during the period <strong>of</strong> chlorination.<br />

17.3 The system shall be chlorinated with an initial concentration <strong>of</strong> 50 mg/L available chlorine<br />

and allowed to remain in the new system for a minimum <strong>of</strong> 24 hours. The <strong>City</strong>’s<br />

Representative shall flush the system after the chlorine has been in the system for a<br />

minimum <strong>of</strong> 24 hours.<br />

18.0 FLUSHING<br />

18.1 The Contractor must supply a means <strong>of</strong> flushing the system, as determined by the <strong>City</strong>’s<br />

Representative. Only the <strong>City</strong>’s Representative shall operate valves for flushing the system.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “F” - Installation and Construction<br />

F-8<br />

February, 2005<br />

18.2 It is the responsibility <strong>of</strong> the Contractor, during charging, swabbing, chlorination and<br />

flushing <strong>of</strong> the system, to supply a means for the water to escape without causing<br />

damage/erosion to the existing grade <strong>of</strong> the property or any adjacent property. The <strong>City</strong>’s<br />

Representative shall not flush the system if it is felt that proper precautions have not been<br />

taken by the Contractor to do so. Any damage caused by flushing during chlorinating or<br />

charging <strong>of</strong> the watermain must be restored to the original state or better by the Contractor,<br />

at his expense. The <strong>City</strong> shall not be responsible for any damage or repair caused by<br />

flushing the watermain.<br />

18.3 Special attention should be given to any areas that are close to streams, ponds or ditches that<br />

may be contaminated by run<strong>of</strong>f water from flushing chlorine from the watermain. It is the<br />

responsibility <strong>of</strong> the Contractor to provide a means <strong>of</strong> safely removing the chlorinated water<br />

in these areas.<br />

18.4 The Contractor shall supply all materials, labour, and excavation necessary for flushing the<br />

new system.<br />

19.0 SAMPLING<br />

The <strong>City</strong> Representative (certified <strong>Water</strong> Distribution Operator) shall take water samples, for<br />

analysis, from all newly installed watermains after the system has been flushed. The new<br />

system shall become part <strong>of</strong> the existing water system upon potability confirmation from the<br />

<strong>City</strong> Representative.<br />

If the sample does not pass, additional swabbing, chlorinating and flushing will be required<br />

until a successful potability result has been obtained. All costs shall be at the Contractor's<br />

expense.<br />

20.0 CONTINUITY TEST<br />

The <strong>City</strong>’s Representative shall do a continuity test on the watermain or tracer wire during<br />

the test procedures. Should the <strong>City</strong>’s Representative find a problem with continuity or<br />

installation <strong>of</strong> the tracer wire, the Contractor will not be allowed a final tie-in to the system.<br />

The Contractor/Developer shall be responsible for the repair, at no cost to the <strong>City</strong>.<br />

21.0 TIE-INS<br />

Upon receipt <strong>of</strong> Ministry <strong>of</strong> the Environment approvals by the <strong>City</strong> and all testing has been<br />

completed to the satisfaction <strong>of</strong> the <strong>City</strong>’s Representative, the remaining tie-ins may be<br />

scheduled. At the discretion <strong>of</strong> the <strong>City</strong>’s Representative, the Contractor may be permitted<br />

to do the tie-in. A <strong>City</strong> Representative must be present when the Contractor performs the tiein.<br />

When the Contractor is not granted permission to do the tie-in, the Contractor shall<br />

provide all the materials, excavation, labour, equipment, necessary safety devices and<br />

restoration for the <strong>City</strong> Representatives to complete the actual tie-in. The Contractor shall<br />

provide assistance as required by the <strong>City</strong>’s Representatives.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-1<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

1.0 DESIGN<br />

1.1 Each residential building lot will be permitted one service. The service pipe must be laid at<br />

right angles to the watermain and in a straight line from the watermain to the meter. The<br />

standard service lateral will be normally located so as to pass through a point near the centre<br />

<strong>of</strong> the building lot frontage.<br />

1.2 The only exception to the aforesaid would be in a multi-family residential development,<br />

when ownership <strong>of</strong> the property is maintained by one person or corporation. (Refer to<br />

BSD-25)<br />

1.3 On crescents or cul-de-sacs the service lateral may be laid at other than right angles to the<br />

watermain, but in a straight line from the watermain to the meter.<br />

1.4 Service boxes shall be located on the property line in residential areas (Refer to BSD-25). A<br />

36” stainless steel service box rod must be installed.<br />

1.5 <strong>Water</strong> services are not to be installed in driveways.<br />

2.0 INSTALLATION<br />

2.1 A <strong>City</strong> Representative must complete all tappings <strong>of</strong>f an existing charged watermain. The<br />

Contractor shall provide all materials, excavation, necessary safety devices, backfill and<br />

restoration to permit the <strong>City</strong>’s Representative to complete the tapping. The Contractor shall<br />

be responsible for all <strong>City</strong> costs associated with tapping watermains.<br />

2.2 All 19 mm and 25 mm services shall be tapped at the 10 o’clock or 2 o’clock position. The<br />

copper service shall be installed with a goose neck at the watermain. The height <strong>of</strong> the goose<br />

neck should be kept to a minimum. Refer to Drawing BSD-48. Services 38 mm and 50 mm<br />

require a saddle and shall be at the 3 o’clock and 9 o’clock position. Refer to BSD-49. All<br />

services <strong>of</strong>f PVC watermains require a service saddle.<br />

2.3 The Contractor shall install a marker <strong>of</strong> 50 mm x 100 mm lumber, 2.5 metres in length, at<br />

each curb stop at the time <strong>of</strong> installation. The marker should project 1.3 metres above<br />

ground and be identified by painting the top 300 mm with “blue” paint. These markers must<br />

be removed at the time <strong>of</strong> acceptance <strong>of</strong> the watermain.<br />

2.4 The <strong>City</strong> requires three working days notice from receipt <strong>of</strong> payment, made at building<br />

permit stage, to complete a tapping.<br />

2.5 All residential service fittings shall be compression copper connections.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-2<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

3.0 RESIDENTIAL SERVICE SPECIFICATIONS<br />

3.1 Copper service pipe shall be a continuous run <strong>of</strong> Type "K" (W.H.) 3rd party s<strong>of</strong>t copper,<br />

minimum 19 mm in diameter.<br />

3.2 Copper services shall enter through the building wall or under the footings.<br />

3.3 On a service <strong>of</strong> 50 mm and smaller, a main stop shall be installed at the watermain.<br />

3.4 <strong>Water</strong> services terminated in a crawl space or any other inaccessible areas will not be<br />

accepted.<br />

3.5 Any services larger than 50 mm shall be installed in accordance with procedures outlined in<br />

Section F - Installation and Construction.<br />

3.6 Curb boxes shall be sized for the service. The service box shall be installed in a<br />

perpendicular manner, properly adjusted to final grade. A 36” stainless steel service box rod<br />

must be installed.<br />

3.7 Curb stops shall be placed on the street property line.<br />

3.8 Curb stops shall be ball style with compression connection.<br />

3.9 Couplings shall be copper compression.<br />

3.10 There shall be no couplings under the foundation or floor <strong>of</strong> the building or inside the<br />

building. Only one (1) coupling is permitted between the curb stop and the angle meter<br />

valve for services under 50 mm.<br />

3.11 No couplings will be permitted between the watermain and the curb stop for services under<br />

50 mm.<br />

3.12 An angle meter ball valve, complete with compression connection, is to be installed on all<br />

residential water services, at the point the service enters the building and prior to the water<br />

meter.<br />

3.13 Angle meter valves shall be no less than 300 mm and no more than 450 mm above the<br />

finished grade.<br />

3.14 Trench depth shall be a minimum <strong>of</strong> 1.7 metres deep from final grade. Where the 19 mm<br />

service cannot maintain 1.7 metres due to the elevations <strong>of</strong> utilities, the contractor shall<br />

install 4.0 metres <strong>of</strong> 100 mm PVC SDR28 liner, a minimum <strong>of</strong> 0.5 metres below the utility.<br />

This will allow for the installation/removal <strong>of</strong> the water service.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-3<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

3.15 Services 19 mm to 52 mm in diameter shall be embedded in sand, conforming to OPS<br />

1004.05.05, and 100 mm above and below the service pipe.<br />

3.16 The Contractor will be responsible for any costs associated with the relocating <strong>of</strong> service(s)<br />

that do not comply with the <strong>City</strong>'s specifications.<br />

4.0 RESIDENTIAL SERVICE INSPECTIONS<br />

4.1 The Contractor shall schedule service inspections forty eight hours in advance.<br />

4.2 All applicable inspection fees, meter fees and/or tapping fees must be paid prior to<br />

scheduling <strong>of</strong> inspections. Refer to the fee schedule located in Section J.<br />

4.3 Should the <strong>City</strong>’s Representative be required to return to the site for an extra inspection (due<br />

to curb box damage, curb box not accessible, coupling not exposed, approved angle meter<br />

valve not installed, leakage or the remote wire test fails), the Contractor shall reschedule<br />

another inspection and shall be invoiced a service charge.<br />

4.4 Copper pipe must be extended inside the building to the meter location and the angle meter<br />

valve must be installed. All services must be completely accessible at all times.<br />

4.5 It is the responsibility <strong>of</strong> the Contractor to provide the appropriate protection to prevent<br />

damages caused by the flushing procedure.<br />

4.6 During winter conditions, the same procedures shall apply. The Contractor is responsible for<br />

protecting the service from adverse weather conditions, including freezing.<br />

5.0 PROCEDURE FOR PRESSURE TESTING RESIDENTIAL WATER SERVICES<br />

5.1 When a <strong>City</strong> Representative arrives to install a water meter, a pressure test <strong>of</strong> the water<br />

service will be performed at this time.<br />

5.2 The water service will be thoroughly flushed and then a pressure gauge will be installed by<br />

the representative at the angle meter valve location. The curb stop is then operated by the<br />

<strong>City</strong> Representative to pressurize the service and then the stop is turned <strong>of</strong>f.<br />

5.3 The pressure gauge will register system pressure and must be left in position a minimum <strong>of</strong><br />

three minutes after the gauge needle has stabilized. No drop in the registered pressure on the<br />

gauge will be considered an acceptable test.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-4<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

5.4 Tests that have not passed will be flushed by the Representative and re-tested. If the second<br />

test does not pass, the builder will be notified to have the water service excavated and<br />

repaired. The <strong>City</strong> Representative will retest at the builder’s expense.<br />

5.5 The <strong>City</strong> Representative shall record service sketch measurements for locating the curb<br />

stop/box with respect to the watermain, property line and the building.<br />

5.6 Should the Contractor use the water service prior to meter installation, a back flow device<br />

shall be installed.<br />

6.0 WATER SERVICE REPAIR PROCEDURE<br />

6.1 When a water service is identified as leaking, the <strong>City</strong>’s Representative will establish an<br />

approximate location <strong>of</strong> the leak. The location <strong>of</strong> the leak will determine who is responsible<br />

for the remedial action.<br />

a) The property owner is responsible for repairs to all leaks located on private property.<br />

If the leak, in the <strong>City</strong>’s Representative's opinion, requires immediate attention, the<br />

<strong>City</strong> will undertake the necessary repairs or replacements. The property owner will<br />

be invoiced for the costs involved. The property owner may be able to recover the<br />

repair costs from the builder.<br />

b) ASSUMED SUBDIVISION<br />

The <strong>City</strong> will repair all leaks located on assumed road allowances using procedures<br />

deemed appropriate by the <strong>City</strong>’s Representative, at the <strong>City</strong>'s expense.<br />

UNASSUMED SUBDIVISION<br />

The <strong>City</strong>’s Representative will contact the Developer to explain the situation and<br />

confirm a repair date.<br />

If the scheduled date is unacceptable in the <strong>City</strong>’s Representative's opinion OR if the<br />

Developer refuses to acknowledge responsibility OR if in the <strong>City</strong>’s Representative's<br />

opinion the leak requires immediate attention, the <strong>City</strong> will undertake the necessary<br />

repairs or replacements. The Developer will be invoiced for the costs involved.<br />

Should the invoice not be paid, the <strong>City</strong> will proceed to recover the costs by drawing<br />

on the Letter <strong>of</strong> Credit for this development.<br />

7.0 DOMESTIC WATER METERS<br />

For meters up to and including 50 mm, the Developer/Owner shall provide a capital<br />

contribution to the <strong>City</strong> for the applicable meter, service inspection costs and installation <strong>of</strong><br />

the water meter. This meter shall be provided and installed by the <strong>City</strong> prior to occupancy <strong>of</strong><br />

the premises. All meters above 50 mm shall be supplied and installed by the<br />

Developer/Owner. The meter will be the property <strong>of</strong> the <strong>City</strong> at the time <strong>of</strong> occupancy.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-5<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

8.0 CARE OF WATER METERS<br />

All domestic meters shall be maintained and repaired by the <strong>City</strong>. Meters damaged due to<br />

neglect or by freezing, shall be repaired or replaced at the expense <strong>of</strong> the Developer/Owner.<br />

9.0 LOCATION OF WATER METERS IN RESIDENCES<br />

9.1 <strong>Water</strong> meters located in a crawl space or other inaccessible areas will not be accepted.<br />

9.2 The Developer/Owner shall keep the water meters accessible, clean, dry, and protected from<br />

freezing.<br />

10.0 REMOTE WIRE INSTALLATION/INSPECTION<br />

The Developer/Owner shall be responsible to install wire for the remote meter. The meter<br />

wire shall be installed from the water meter location to within 0.3 metres <strong>of</strong> the electric<br />

meter base outside <strong>of</strong> the building. A 300 mm (12”) coil <strong>of</strong> wire must be left at the angle<br />

meter valve and outside <strong>of</strong> the building at the meter base. (Refer to Section K for approved<br />

meter wire). The remote meter wire must be installed a minimum <strong>of</strong> 200 mm (8”) from any<br />

electrical wiring and inside the building, not underground. The remote wire will be tested<br />

for continuity at the time <strong>of</strong> the service inspection and pressure test. Should the remote<br />

meter wire test fail, the water service will not be connected until the remote meter wire is<br />

repaired. It will be the responsibility <strong>of</strong> the Developer/Owner to repair the remote meter<br />

wire to the satisfaction <strong>of</strong> the <strong>City</strong>’s Representative. Four-conductor wire will not be<br />

accepted.<br />

11.0 FAILURE TO REGISTER PROPERLY<br />

Where the <strong>City</strong> has established that a water meter has failed to register accurately, the <strong>City</strong><br />

shall estimate the quantity <strong>of</strong> water consumed. The recorded consumption prior to such<br />

failure will be the basis <strong>of</strong> estimating quantities consumed during the failure.<br />

12.0 TESTING<br />

The <strong>City</strong> reserves the right to test the water meter at any time.<br />

13.0 DISPUTE TEST OF WATER METERS<br />

Upon written request by the Consumer, the <strong>City</strong> may test any water meter at the expense <strong>of</strong><br />

the Consumer. If the meter is found to be inaccurate, the <strong>City</strong> shall adjust the water bills<br />

accordingly.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

G-6<br />

February, 2005<br />

Section “G” - Residential Domestic <strong>Water</strong> Service<br />

14.0 DISCONTINUE THE SUPPLY<br />

The <strong>City</strong> may interrupt the supply <strong>of</strong> water to any premises that has overdue and unpaid<br />

accounts. The <strong>City</strong> shall restore the supply <strong>of</strong> water upon payment to the <strong>City</strong> <strong>of</strong> such<br />

overdue amounts plus any applicable service charge.<br />

15.0 DRAINING THE PLUMBING<br />

Where the Owner has requested the water supply to be shut <strong>of</strong>f at the curb stop, the <strong>City</strong> will<br />

not be responsible for draining the water meter and plumbing apparatus to prevent freezing<br />

or other damage.<br />

16.0 NOT FOR RESALE<br />

<strong>Water</strong> supplied by the <strong>City</strong> shall not be resold nor shall water servicing be extended without<br />

the written permission <strong>of</strong> the <strong>City</strong>.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-1<br />

February, 2005<br />

1.0 GENERAL REQUIREMENTS<br />

1.1 The Developer/Owner shall retain the services <strong>of</strong> a Pr<strong>of</strong>essional Engineer experienced in the<br />

design and installation <strong>of</strong> water services. The Pr<strong>of</strong>essional Engineer retained shall be<br />

authorized to practice in the Province <strong>of</strong> Ontario and shall be responsible for the preparation<br />

<strong>of</strong> drawings and specifications for the proposed water services to the satisfaction <strong>of</strong> the <strong>City</strong>.<br />

The services <strong>of</strong> the Pr<strong>of</strong>essional Engineer shall continue until the work provided for on the<br />

site is completely developed.<br />

1.2 The Developer/Owner is responsible for the <strong>City</strong>’s service connection charges arising out <strong>of</strong>,<br />

or attributable to the development <strong>of</strong> the site plan including, but not limited to field<br />

inspection, testing and connection <strong>of</strong> the water services. The <strong>City</strong> reserves the right to order<br />

field revisions, as deemed required by the <strong>City</strong>’s Representative, at the expense <strong>of</strong> the<br />

Developer/Owner.<br />

1.3 The Developer/Owner shall save harmless, the <strong>City</strong>, its agents and employees from and<br />

against all claims, demands, losses, costs, damages, actions, suits and proceedings arising out<br />

<strong>of</strong> or attributable to any act or omission in connection with the development and servicing <strong>of</strong><br />

the site and without limiting the generality <strong>of</strong> the foregoing, including inspections <strong>of</strong> the<br />

services arising out <strong>of</strong>, or attributable to the development <strong>of</strong> the site.<br />

1.4 The <strong>City</strong> requires a separate fire and domestic service and permits one domestic and fire<br />

service per lot. Specific conditions may require a reduced pressure principal back flow<br />

preventer on fire services.<br />

1.5 The Developer/Owner shall relocate, support or modify any existing utilities required to<br />

develop the site, at his own expense.<br />

1.6 When a site is subject to a Development Agreement, connections to the municipal system are<br />

not permitted until the agreement has been registered.<br />

1.7 The Developer/Owner shall obtain all necessary permits and consents associated with<br />

excavation and installation <strong>of</strong> water services on existing <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> road allowances and<br />

to discharge any applicable <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Act charges or Local Improvement charges.<br />

1.8 The Developer/Owner shall make a capital contribution towards the extension <strong>of</strong> the water<br />

services to the site and across its frontage if the present servicing is not adequate to<br />

accommodate the development. The amount <strong>of</strong> the capital contribution will be determined<br />

by the <strong>City</strong>.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-2<br />

February, 2005<br />

1.9 The Developer/Owner shall be responsible to co-ordinate the installation <strong>of</strong> all utilities and<br />

driveway entrances so that conflicts do not occur in the field. All driveways indicated on the<br />

drawings must be a minimum distance <strong>of</strong> 1.5 metres from any above ground water facility.<br />

1.10 The Developer/Owner shall supply to the <strong>City</strong> one full set <strong>of</strong> as-built water drawings.<br />

1.11 The water services and fire hydrants within the limits <strong>of</strong> this site plan are privately owned<br />

and shall be maintained by the Developer/Owner.<br />

1.12 <strong>Water</strong> meter to be located within the mechanical room on the ground floor and be totally<br />

accessible at all times.<br />

1.13 All materials used on the site shall conform to the Material Data Sheets located in Section K<br />

<strong>of</strong> this document.<br />

1.14 This service size shall be continuous from watermain to water meter.<br />

1.15 Refer to E-1 re: Service Size Changes or refer to By-law 2001-290, Bill No. 289.<br />

1.16 Any existing service that will be abandoned must be done to the <strong>City</strong>’s satisfaction.<br />

2.0 DRAWING REQUIREMENTS<br />

2.1 The Developer/Owner shall submit to the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>’s Planning and Development<br />

Department a proposed site servicing drawing for approval, indicating the following:<br />

1) The location, material and size <strong>of</strong> any existing domestic and fire services;<br />

2) The location, material and size <strong>of</strong> any existing underground or overhead utilities and<br />

private driveways within 92 metres <strong>of</strong> the site;<br />

3) The location, material and size <strong>of</strong> any existing services to be abandoned;<br />

4) The location, material and size <strong>of</strong> the proposed domestic and fire services;<br />

5) The location <strong>of</strong> the mechanical rooms for approval by the <strong>City</strong>;<br />

6) The size and location <strong>of</strong> water meter(s); and<br />

7) Digital copy <strong>of</strong> site service to be supplied to the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>.<br />

2.2 Site Plan Drawings shall be legible, in metric, at the Scale <strong>of</strong> 1:250 or 1:500 and include a<br />

key plan, north arrow and legend. Digital drawings, in an AutoCAD compatible format, and<br />

tied to the horizontal Cosine Network NAD83, are preferred.<br />

2.3 If the property is located within a Plan <strong>of</strong> Subdivision not yet assumed, a site drawing with<br />

the Subdivision’s Consulting Engineer’s Stamp <strong>of</strong> Approval must be submitted.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-3<br />

February, 2005<br />

3.0 SPECIFICATIONS FOR GENERAL SERVICES, DOMESTIC, AND FIRE<br />

SERVICES<br />

3.1 Written material approval list, for the materials required, shall be submitted to the <strong>City</strong><br />

Representative for approval before commencing with the installation <strong>of</strong> the water services.<br />

3.2 The Developer/Owner shall determine the pipe size for the proposed domestic service. This<br />

service shall be continuous from watermain to water meter. The Developer/Owner shall<br />

provide the corresponding flow calculations for any domestic service larger than 50 mm.<br />

3.3 The Contractor may utilize an existing valve for tie-in purposes if available. It is understood<br />

that should this valve fail, for any reason during the testing procedure, it shall be the<br />

Developer/Owner’s responsibility to replace the valve, including all labour, material and<br />

excavation.<br />

3.4 All water services from 100 mm to 300 mm shall be Ductile Iron or PVC. Should a soils<br />

report indicate aggressive soils are present on the site, PVC water main shall be used. The<br />

service pipe material must be Ductile Iron from the restraining flange to a minimum <strong>of</strong><br />

3 metres outside the foundation. Refer to BSD-61. The internal piping must also meet<br />

the most current Building Code and/or National Fire Protection Act. This service must<br />

have some form <strong>of</strong> Cathodic Protection.<br />

3.5 There shall be a daily charge for operation <strong>of</strong> a valve for filling the service. Refer to<br />

Section J.<br />

3.6 The service pipe(s) shall be laid at right angles to the watermain and in a straight line from<br />

the water main to the property line on the building lot frontage. A valve is not required on<br />

the property line for services larger than 50 mm, due to the use <strong>of</strong> “main” valves on larger<br />

services.<br />

3.7 All main stops, curb stops, meter stops, and shut<strong>of</strong>f valves up to and including 50 mm are to<br />

be ball valves. Valves over 50 mm shall be gate valves.<br />

3.8 Any water service 50 mm and less shall have a curb stop and box on the property line. A<br />

<strong>City</strong> Representative shall complete all tappings <strong>of</strong>f any existing charged watermain. The<br />

Contractor shall provide all materials, excavation, necessary safety devices, backfill and<br />

restoration to permit the <strong>City</strong> Representative to complete the tapping. The contractor shall<br />

be responsible for all <strong>City</strong> costs associated with tapping watermains. Refer to Section “J”.<br />

3.9 All domestic water services 50 mm and less shall be Type K (W.H.) 3rd party s<strong>of</strong>t copper.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-4<br />

February, 2005<br />

3.10 The <strong>City</strong> shall NOT be responsible, or liable, for adverse water quality resulting from the<br />

installation <strong>of</strong> an improperly sized water service.<br />

3.11 No person shall operate valves, hydrants or interfere with a potable water system in any<br />

manner that will cause the water to become non-potable. Failure to comply with this<br />

regulation will result in a charge, outlined in By-Law 99-290 located in Section E.<br />

3.12 The Developer/Owner shall supply all materials, labour and excavation necessary for<br />

charging, swabbing, testing, chlorinating and/or flushing the new service.<br />

3.13 The water service tapping requirements are as follows:<br />

TAPPING SIZE DUCTILE IRON<br />

WATERMAIN<br />

PVC WATERMAIN<br />

19 mm and 25 mm Direct tapping Service saddle required<br />

38 mm and 50 mm Service saddle required Service saddle required<br />

100 mm and larger Tapping sleeve and valve<br />

up to size on size tapping<br />

A cutting-in tee and valve<br />

for larger than size on size<br />

tappings.<br />

Tapping sleeve and valve<br />

up to one trade size smaller<br />

than existing watermain.<br />

A cutting-in tee and valve<br />

for size on size tappings or<br />

larger.<br />

3.14 Should a temporary service be required, a backflow device must be installed.<br />

4.0 GENERAL SERVICE WATER METERS<br />

4.1 Meter size must be the same as service size as per By-law 2002-102 (Bill No. 109).<br />

4.2 The <strong>City</strong> shall supply and install water meters up to and including 50 mm. The<br />

Developer/Owner must make a capital contribution for each meter that is required, along<br />

with inspection fees and other associated fees (e.g. tappings), prior to the meter being<br />

installed. Refer to Section J.<br />

All meters greater than 50 mm shall be supplied and installed by the Developer/Owner and<br />

will become the property <strong>of</strong> the <strong>City</strong> at the time <strong>of</strong> occupancy. Measurements must be in<br />

cubic metres (m 3 ), refer to BSD-58 and Section 4.5.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-5<br />

February, 2005<br />

The <strong>City</strong> has the right to re-size the meter if they determine that the domestic metering has<br />

been improperly calculated.<br />

The <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> does not allow turbine meters nor should butterfly valves be<br />

installed.<br />

4.3 All water meter locations are to be:<br />

1) Reviewed and approved by the <strong>City</strong> Representative;<br />

2) Accessible at all times, and<br />

3) Installed in a horizontal position within the mechanical room. This room is to be<br />

sized to allow meter installations as per BSD-58.<br />

4.4 In General Service Properties only one Bulk meter will be used per property.<br />

4.5 Meter by-passes are mandatory on all water meter installations 38 mm and larger. All water<br />

services shall have a valve installed on each side <strong>of</strong> the water meter. Refer to BSD-58.<br />

4.6 Operation <strong>of</strong> the by-pass valve by other than a <strong>City</strong> Representative will result in the<br />

disruption <strong>of</strong> service and/or charges being levied.<br />

4.7 The correct spacing for setting water meters is as follows:<br />

METER SIZE METER SETTING SIZE<br />

16 mm x 19 mm 250 mm<br />

19 mm 330 mm<br />

25 mm 380 mm<br />

*The above includes allowance for meter couplings or “tail pieces”.<br />

38 mm 330 mm<br />

50 mm 432 mm<br />

75 mm 432 mm<br />

100 mm 508 mm<br />

150 mm 610 mm<br />

*The above is flange face to flange face dimension <strong>of</strong> meter only. The Contractor<br />

is responsible to ensure the above mentioned values are to catalogue specifications.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-6<br />

February, 2005<br />

5.0 FIRE SERVICES<br />

5.1 All fire services shall conform to the Ontario Building Code and National Fire Protection<br />

Act.<br />

5.2 The fire service requirements shall be the responsibility <strong>of</strong> the Developer/Owner.<br />

Information may be obtained from the Insurance Underwriters, the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Building<br />

Services Department and the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fire Department.<br />

5.3 Where fire services are not metered, the Developer/Owner shall pay to the <strong>City</strong> a fixed<br />

annual service charge. Refer to Section J.<br />

5.4 The <strong>City</strong> may test the fire water service system from time to time to determine the loss <strong>of</strong><br />

water through system leakage or other causes. If as a result <strong>of</strong> the testing, the <strong>City</strong> believes<br />

that water has been used from the said system for other than fire protection purposes, the<br />

<strong>City</strong> may require that the fire water service system be metered and the Developer/Owner<br />

shall comply forthwith.<br />

5.5 For Fire Protection charges refer to Section J.<br />

5.6 The Owner shall paint private hydrants “Fire Hydrant Red”.<br />

5.7 If a fire hydrant is installed on the fire service, a valve and box is required on the service<br />

before it enters the building.<br />

5.8 A building shall be within 90 metres <strong>of</strong> a fire hydrant.<br />

5.9 All siamese connections shall be within 45 metres <strong>of</strong> a fire hydrant.<br />

5.10 An anchor tee and valve shall be installed for all fire hydrants and all fire hydrants shall be<br />

located a minimum <strong>of</strong> 0.7 metres from the valve.<br />

5.11 Private fire hydrants or other fire water service outlets shall not be operated except in the<br />

case <strong>of</strong> fire for fire protection purposes, unless special permission <strong>of</strong> the <strong>City</strong> has been<br />

obtained.<br />

5.12 All hydrants shall be maintained as per fire code/insurance requirements.<br />

6.0 TESTING PROCEDURE<br />

6.1 Testing <strong>of</strong> General Service domestic services and fire services shall conform to the<br />

following sequence: initial tie-in, remove the swabs/charge the watermain, pressure test,<br />

chlorinate, flush the system and take a water sample. The service will not be turned on<br />

until a sample is approved.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-7<br />

February, 2005<br />

7.0 SWABBING/CHARGING THE WATERMAIN<br />

7.1 All domestic and fire services larger than 50 mm shall be swabbed. Swabs shall be supplied<br />

by the <strong>City</strong> Representative on the site. The swabs shall be numbered and the <strong>City</strong><br />

Representative is required to witness the installation <strong>of</strong> swabs by the Contractor. If a<br />

multiple system is installed, a swabbing schedule shall be prepared by the <strong>City</strong><br />

Representative and shall be supplied to the Developer/Owner. The swabbing schedule shall<br />

indicate where the swabs are to be installed and removed.<br />

7.2 Swabs up to and including 250 mm may be taken out <strong>of</strong> hydrants. If hydrants are used to<br />

remove swabs, the Contractor shall remove and replace the internal parts <strong>of</strong> the private<br />

hydrant. If hydrants are not located in suitable areas then risers shall be installed by the<br />

Contractor, at his expense, to facilitate the removal <strong>of</strong> swabs. All risers shall be properly<br />

restrained and installed above ground. All swabs over 250 mm must be taken out <strong>of</strong> risers.<br />

Refer to BSD-45.<br />

7.3 The <strong>City</strong> Representative shall remove the swabs. The Contractor shall supply a means <strong>of</strong><br />

swabbing the system and provide assistance, at his expense, as determined by the <strong>City</strong><br />

Representative. It shall be the responsibility <strong>of</strong> the Contractor to supply a water course for<br />

the water to escape, without causing damage/erosion to the existing grade <strong>of</strong> the property or<br />

adjacent properties, during swabbing. Any damage caused by swabbing the watermain shall<br />

be restored to its original state or better, by the Developer/Owner. The <strong>City</strong> shall not be<br />

responsible for any damage or repairs during swabbing.<br />

7.4 All swabs shall be accounted for and removed from the system prior to pressure testing the<br />

system. Any swabs that are not accounted for may require excavation to locate and remove<br />

them. All additional work required to locate and remove misplaced swabs shall be at the<br />

Developer/Owner’s expense.<br />

7.5 Swabbing by hand may be utilized by the Contractor if deemed acceptable by the <strong>City</strong><br />

Representative.<br />

7.6 All risers in a multiple General Service site must be removed by the Contractor prior to the<br />

commencement <strong>of</strong> pressure testing, unless the riser is the only means <strong>of</strong> flushing the<br />

watermain.<br />

8.0 PRESSURE TESTING<br />

8.1 The initial tie-in valve shall NOT be operated by the Contractor under any circumstances.<br />

All Developer/Owner-installed main and hydrant valves are to be opened by the Contractor<br />

and checked by the <strong>City</strong>’s Representative, to ensure that all valves are open prior to any<br />

pressure test. The Contractor shall supply all materials, excavations, labour and equipment<br />

necessary for the pressure test, at no expense to the <strong>City</strong>.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-8<br />

February, 2005<br />

8.2 All domestic and fire services 19 mm and larger, shall be pressure tested by the Contractor<br />

and witnessed by the <strong>City</strong> Representative. The pressure test shall be for a two hour period at<br />

1035 Kpa (150 psi.), zero leakage and zero pressure drop. If the pressure test meets the<br />

above criterion, the system as a whole, shall be accepted. The internal fire service shall be<br />

pressure tested to National Fire Code Standards.<br />

8.3 If the above criterion is not met, the system may be divided into smaller sections. In this<br />

case, each section shall be tested individually and shall be required to meet the allowable<br />

leakage and test pressure criteria, as outlined in the AWWA <strong>Specification</strong> C-600-99; Section<br />

4 “Hydrostatic Testing” and Section 4.1 “Pressure and Leakage Test”.<br />

9.0 CHLORINATING<br />

9.1 The domestic and fire service installations shall be in accordance with ANSI/AWWA<br />

Standard C651-99 - Construction and Disinfection Methods. The domestic service shall<br />

have a 19 mm tail located near the tie-in point <strong>of</strong> the newly installed water service and<br />

brought above grade a minimum <strong>of</strong> 1 metre, to allow access for the chlorine pump. The<br />

point <strong>of</strong> chlorination must provide a sufficient flow <strong>of</strong> water to evenly distribute the chlorine<br />

throughout the entire service. The <strong>City</strong> Representative will determine if the tail location and<br />

distribution <strong>of</strong> chlorine are acceptable. Chlorination shall be performed by the <strong>City</strong><br />

Representative. The chlorination tail must be removed, main stop closed and a brass plug<br />

installed upon successful test results.<br />

9.2 The Contractor shall NOT operate any main valves, hydrant blow-<strong>of</strong>fs, by-passes or any<br />

other appurtenances within the new system during the period <strong>of</strong> chlorination.<br />

9.3 The service shall be chlorinated with an initial concentration <strong>of</strong> 50 mg/L available chlorine<br />

and allowed to remain in the new service for a minimum <strong>of</strong> 24 hours. The <strong>City</strong><br />

Representative shall flush the service after the chlorine has been in place for a minimum <strong>of</strong><br />

24 hours.<br />

10.0 FLUSHING<br />

10.1 The Contractor shall supply a means <strong>of</strong> flushing the service that is acceptable to the <strong>City</strong><br />

Representative. Only the <strong>City</strong> Representative shall operate valves for flushing the service.<br />

10.2 It is the responsibility <strong>of</strong> the Contractor while charging, swabbing, testing, chlorinating<br />

and/or flushing the new service to supply a means for the water to escape without causing<br />

damage/erosion to the existing property or to any adjacent property. The service shall not be<br />

flushed until the <strong>City</strong> Representative determines that the proper precautions have been taken<br />

by the Contractor. The Contractor shall restore any property damage caused by charging,<br />

swabbing, testing, chlorinating and/or flushing the new service to its original state or better at<br />

his own expense. The <strong>City</strong> shall not be responsible for any damage or repair caused by<br />

charging, swabbing, testing, chlorinating and/or flushing the new service.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “H” - General Services<br />

H-9<br />

February, 2005<br />

10.3 Special attention, by the Contractor, should be given to any areas that are close to streams,<br />

ponds or ditches that may be contaminated by run<strong>of</strong>f water from flushing chlorine from the<br />

water service. It shall be the responsibility <strong>of</strong> the Contractor to provide a means <strong>of</strong> safely<br />

removing the chlorinated water in these areas.<br />

11.0 SAMPLING<br />

11.1 The <strong>City</strong> Representative shall take water samples for analysis, when required or requested,<br />

from all newly installed domestic water service after the service has been flushed. The new<br />

service shall be deemed potable upon confirmation from the <strong>City</strong> Representative's approved<br />

water analysis.<br />

11.2 Additional swabbing, chlorinating and flushing, at the Developer/Owner’s expense, shall be<br />

required until a successful potability result has been obtained.<br />

12.0 CONTINUITY TESTING (TRACER WIRE)<br />

12.1 All non-metallic and metallic reinforced watermains shall be installed with a #12 TWU<br />

stranded copper tracer wire along the spring line <strong>of</strong> the watermain. The tracer wire shall be<br />

wrapped around each joint <strong>of</strong> the watermain and brought to the surface at each hydrant and<br />

connected to flange bolt or within building’s mechanical room. A continuous length <strong>of</strong> wire<br />

must be used. If the wire must be joined, the appropriate wire connectors shall be used and<br />

wrapped with self-amalgamating tape to prevent corrosion. If no hydrants are available then<br />

some means <strong>of</strong> connecting to wire must be established.<br />

12.2 To ensure there is no damage to the tracer wire during or after construction, the <strong>City</strong>’s<br />

Representative shall do a continuity test on the wire during testing procedures. Should the<br />

<strong>City</strong>’s Representative find a problem with continuity or installation <strong>of</strong> the tracer wire, the<br />

Contractor/Developer shall be responsible for the repair, at no cost to the <strong>City</strong>.<br />

12.3 In non-standard locations, such as easements, parks, townhouse/condominium developments<br />

and reconstruction projects, metallic warning tape shall be used over all watermains. The<br />

metallic warning tape shall be laid in the trench 0.3 metres (12”) to 0.5 metres (19”) directly<br />

above the watermain.<br />

12.4 When non-metallic mains are connected to metallic mains, a tracer wire must be installed<br />

and bonded (cade weld) to metallic main.


I-1<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong> February, 2005<br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “I” - Freehold/Condominium Townhouse Projects Developed Under Site Plan<br />

1.0 SITE PLAN<br />

The following design criteria and site plan requirements are to be met by Developers on<br />

townhouse developments, both freehold (individually owned) and condominium<br />

(corporation owned) townhouses, located on site plans and in subdivisions. Defined as<br />

follows: 1) Freehold - An individual owns the land and the residential unit it is situated on;<br />

2) Condominium - A corporation owns the land and residential units are privately owned.<br />

The design, installation and testing shall be as noted in Sections B and F, except as follows.<br />

2.0 DESIGN CRITERIA<br />

2.1 The <strong>City</strong>’s Representative shall complete site plan water servicing conditions that are to be<br />

incorporated into a site specific Development Agreement and forward a copy to the Civil<br />

Consultant and the Developer/Owner.<br />

2.2 The Developer/Owner shall supply a drawing, indicating water servicing for the project,<br />

including a Pr<strong>of</strong>essional Engineer’s stamp and signature.<br />

2.3 The water servicing drawings will be reviewed by the <strong>City</strong> and revisions forwarded to the<br />

Developers’ Consultant. The Consultant shall forward the MOE Approval forms and the<br />

MOE fee to the <strong>City</strong> for review, complete with two sets <strong>of</strong> water service drawings.<br />

2.4 The Developer/Owner shall be responsible to post a Letter <strong>of</strong> Credit equal to the value <strong>of</strong> the<br />

work to be completed. The Letter <strong>of</strong> Credit Requirements shall be approved by the <strong>City</strong>’s<br />

Representative and a copy shall be forwarded to the Developer/Owner.<br />

2.5 Upon approval <strong>of</strong> the water servicing drawings, the <strong>City</strong>’s Representative shall sign <strong>of</strong>f the<br />

site plan and building permits.<br />

2.6 A Registered Plan <strong>of</strong> the project shall be required prior to the start <strong>of</strong> construction.<br />

2.7 The Development Agreement must be signed by the Developer/Owner and a Letter <strong>of</strong> Credit<br />

in place prior to the start <strong>of</strong> construction.<br />

2.8 Should demolition permits be required, the Developer/Owner must sign the appropriate<br />

forms and forward to all applicable parties.<br />

3.0 INSTALLATION AND CONSTRUCTION OF FREEHOLD PROJECTS ON CITY<br />

OF BARRIE RIGHT OF WAY<br />

3.1 WATERMAIN<br />

<strong>Water</strong>main is to be supplied and installed by the Developer/Owner. Upon MOE water<br />

sample approval and at the end <strong>of</strong> the one year maintenance period, this watermain will<br />

become part <strong>of</strong> the <strong>City</strong>’s Distribution System and will be maintained by the <strong>City</strong>.<br />

3.2 WATER SERVICES


I-2<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong> February, 2005<br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “I” - Freehold/Condominium Townhouse Projects Developed Under Site Plan<br />

Individual services are required to each unit, from the watermain to the meter. The curb box<br />

shall be on the street line. After the one year maintenance period, the <strong>City</strong> will be<br />

responsible for the watermain and water services installed in the right-<strong>of</strong>-way. On private<br />

property, the homeowner is responsible for their water service. The <strong>City</strong> may make the<br />

repairs on private property, at the homeowner’s request and at the homeowner’s expense.<br />

3.3 WATER METERS<br />

Individual water meters are required to each unit. The Developer/Owner is responsible for<br />

water meter costs. (See page J-1)<br />

4.0 CONDOMINIUM - PRIVATE<br />

4.1 WATERMAIN<br />

The watermain is supplied and installed by the Developer/Owner who is responsible for all<br />

repairs. The <strong>City</strong> will isolate the system at the Developer/Owner’s expense. Valves shall be<br />

placed at the adjacent road allowance to the site.<br />

4.2 WATER SERVICES<br />

Individual services only are allowed. The curb box shall be a minimum <strong>of</strong> 1.5 metres from<br />

the face <strong>of</strong> the building. All repairs shall be completed by the corporation, at their expense.<br />

4.3 WATER METERS<br />

All water meters to be supplied by the <strong>City</strong> <strong>of</strong> <strong>Barrie</strong>.<br />

Individual read meters must be used. Meters must be accessible to the <strong>City</strong>’s Representative.<br />

The Developer/Owner is responsible for all water meter costs.


J-1<br />

<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

Section “J” – <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Charges<br />

February, 2005<br />

1.0 WATERMAIN INSTALLATION CHARGES<br />

BY THE CITY OF BARRIE<br />

1.1 FLAT RATE WATER SERVICE FEES *<br />

SIZE<br />

19 mm, 25 mm, 38 mm, 52 mm, 100 mm, 150 mm, and 200 mm<br />

CUSTOMER COST<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

For larger sizes or hyprescon tappings, estimate to be provided<br />

* Flat rate fee includes the <strong>City</strong>’s review, inspection, water operations and tapping<br />

charges<br />

1.2 WATER METER COSTS<br />

SIZE<br />

16 mm x 19 mm, 19 mm, 25 mm, 38 mm, and 50 mm<br />

CUSTOMER COST<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

1.3 WATER SERVICE INSPECTION (RESIDENTIAL ONLY)<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

1.4 INSTALLATION/REMOVAL OF HYDRANT VALVE FOR TESTING/FILLING<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

1.5 PAINTING HYDRANTS<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

1.6 OPERATION OF MAIN VALVE FOR FILLING WATERMAIN/SERVICE<br />

As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

1.7 FIRE PROTECTION CHARGES<br />

1. Annual charge for each private fire hydrant supplied with water from the municipal<br />

water system. As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.<br />

2. Annual charge for each private connection made to the municipal water distribution<br />

system. As per the current <strong>City</strong> <strong>of</strong> <strong>Barrie</strong> Fees By-law.


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-1<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

1.0 WATERMAIN<br />

Ductile Iron CL52 C151/A21.51;<br />

C104/A21.40<br />

FEATURES MANUFACTURER CATALOGUE #<br />

6 metres in length, Push-on Joint,<br />

cement lined, poly-wrapped in<br />

aggressive soils<br />

PVC Class 150 C900;DR18 Push-on Joint, colour code<br />

“blue”, 6 metres in length<br />

2.0 WATER SERVICES<br />

19 mm<br />

50 mm<br />

3.0 WATERMAIN FITTINGS<br />

ASTM Standard<br />

B88-88<br />

Ductile Iron C110/A21.10<br />

C153/A21.53<br />

Type “k”, 3rd Party (W.H.), s<strong>of</strong>t<br />

copper<br />

Mechanical Joint, Ductile Iron<br />

Body and Glands cement lined<br />

seal coat to AWWA C104/A21.4<br />

Polyvinyl Chloride C907 Push-on Joint CSA B137.2<br />

(100 mm to 200 mm only)<br />

U.S. Pipe; Canada Pipe;<br />

Atlantic States; Clow; Pacific<br />

States; McWane; Griffin Pipe<br />

Ipex; Royal Pipe;<br />

Rehau; Diamond Pipe; Maple,<br />

National Pipe; Duchesne<br />

Wolverine Tube<br />

Cerro Copper <strong>of</strong> Canada Ltd.<br />

Magotteaux (Sigma);<br />

Star<br />

as per manufacturer<br />

as per manufacturer<br />

as per manufacturer<br />

as per manufacturer<br />

Ipex; Harco as per manufacturer


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-2<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

COUPLINGS<br />

D.I. and PVC <strong>Water</strong><br />

Main<br />

Cast Iron (over-sized<br />

main)<br />

4.0 WATERMAIN VALVES<br />

Resilient Seated Gate<br />

Valves<br />

M.J. x M.J.<br />

**Note: M.J. refers to<br />

Mechanical Joint<br />

Resilient Seated Gate<br />

Valves Push On<br />

C110/A21.10<br />

C153/A21.53<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Mechanical Joint, Ductile Iron<br />

Body and Glands cement lined<br />

seal coat to AWWA C104/A21.4;<br />

D.I. bodies, stainless steel nuts<br />

and bolts<br />

C509 52 mm square nut, M.J. x M.J.<br />

(150 mm – 400 mm) open counter<br />

clockwise<br />

Resilient seated gate<br />

Epoxy coating<br />

C509 52 mm square nut, Push-on Joint,<br />

(150 mm – 400 mm), open<br />

counter clockwise<br />

Magotteaux (Sigma);<br />

Star<br />

Robar;<br />

Smith/Blair;<br />

Dresser<br />

Mueller;<br />

Clow;<br />

Avk;<br />

Bibby<br />

Bibby;<br />

Mueller;<br />

Clow;<br />

Avk<br />

as per manufacturer<br />

1406<br />

441<br />

as per manufacturer<br />

A2370-23<br />

F-6100<br />

Series 25/00<br />

as per manufacturer<br />

as per manufacturer<br />

A2370-40<br />

F-6112<br />

Series 25/50


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-3<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

Resilient Seated Valves<br />

Tapping<br />

Pressure Reducing and<br />

Check Valve<br />

Reduced Pressure<br />

Principal Back Flow<br />

Preventer<br />

C509 Flange x M.J. 150 mm to 300<br />

mm, 150 mm to 300 mm, open<br />

counter clockwise, 52 mm square<br />

nut, epoxy coating<br />

C510 Flange x Flange (Note: <strong>City</strong> <strong>of</strong><br />

<strong>Barrie</strong> to supply contractor with<br />

the appropriate pressure gauge<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Mueller;<br />

Clow;<br />

Bibby;<br />

Avk<br />

Clayton Valve 90-01<br />

H-687<br />

F-6114<br />

as per manufacturer<br />

25/30081<br />

C511 Watt’s #909 Series<br />

Air Release Valve N/A I.P. Thread x I.P. Thread<br />

(ball type)<br />

**Note: M.J. refers to Mechanical Joint<br />

Apco<br />

Clayton Valve<br />

Model #65<br />

34AR-332-3/4”


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-4<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

5.0 HYDRANTS<br />

Fire Hydrant C502 1.98 metres (6’6”) barrel length<br />

chrome yellow; post type dry<br />

barrel compression shut<strong>of</strong>f with<br />

ball valve closing with flow; M.J.<br />

elbow, 5” valve ball, 2 CSA<br />

standard hose connection (2½”<br />

nominal), 4” Storz threadless<br />

pumper connection as per NFPA<br />

1963 and AWWA C502,<br />

breakaway flange, self draining.<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Clow;<br />

Canada Valve;<br />

Avk;<br />

Bibby **<br />

** Note: Bibby hydrants may<br />

be installed in private<br />

applications only<br />

** Note: Storz connections<br />

must be supplied manufacturer<br />

specific to the Hydrant<br />

6.0 VALVE BOXES N/A 150 mm Cover Bibby;<br />

Emco/Concord<br />

Guide Plate Bibby;<br />

Emco/Concord<br />

Extension 300 mm Bibby;<br />

Emco/Concord<br />

Extension 450 mm Bibby;<br />

Emco/Concord<br />

Extension 600 mm; Slide style, Bibby;<br />

upper/ lower section<br />

Emco/Concord<br />

D67M Premier<br />

Century<br />

2780<br />

Sentinel **<br />

VB800<br />

4SL-48<br />

VB875<br />

GP<br />

VB700<br />

4SL-12E<br />

VB705<br />

4SL-18E<br />

VB710<br />

4SL-24E


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-5<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

7.0 VALVE STEM<br />

EXTENSION<br />

8.0 RESTRAINING GLANDS<br />

a) Ductile Iron <strong>Water</strong><br />

Main<br />

N/A Required for additional depth<br />

over 1.7 metres; 52 mm top<br />

operating c/w set screw;<br />

*contractor to supply to required<br />

length<br />

N/A Colour Code “black” for Ductile<br />

Iron use<br />

b) PVC <strong>Water</strong>main N/A Uni-bell Standard UNI-B-13-94<br />

ASTM Standard F1674-96<br />

ANSI/AWWA C11/A21.11<br />

where applicable. The split<br />

ring restraint design shall<br />

incorporate a series <strong>of</strong> nondirectional<br />

machined serrations<br />

(not “as cast”) on the inside<br />

diameter to provide positive<br />

restraint, exact fit, 360 degree<br />

contact and support <strong>of</strong> the pipe<br />

wall. * If machined serrations<br />

are directional, additional<br />

safeguards must be built into<br />

casting<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Bibby;<br />

Bibby;<br />

Concord/Daigle;<br />

*Canada Valve;<br />

*Canada Valve<br />

EBAA Iron;<br />

Canron;<br />

Star;<br />

Uniflange;<br />

Sigma<br />

EBAA Iron ( to be Series 1500<br />

used with an U/G bell joint<br />

clamp and two 19 mm tie rods);<br />

Uniflange<br />

Sigma * (see note)<br />

Sigma<br />

Clow<br />

Star<br />

VB950<br />

VB959<br />

D78A<br />

218/758 (Nut)<br />

29/06 (Socket)<br />

Series 1100<br />

as per manufacturer<br />

Stargrip<br />

Series 1400<br />

One-Lok<br />

Series 1500<br />

1300, 1350<br />

as per manufacturer<br />

PV – Lok<br />

One-Lok (PVC)<br />

Series 300, 350<br />

All Grip (Series 3600)<br />

PVC Grip (Series 3500)


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-6<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

Cathodic Protection<br />

(Nuts and Caps)<br />

9.0 METALLIC<br />

CAUTION TAPE<br />

N/A 99.9% high grade Zinc, steel<br />

core, coated with low resistant<br />

depolarizing material: 175 grams<br />

ASTM B-418-73-Type II<br />

N/A Mylar Marking Tape c/w<br />

metallic backing; Lineguard<br />

Type 2 max bury <strong>of</strong> 150 mm.<br />

“Caution <strong>Water</strong> Main” colour<br />

code “orange”<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Protecto Caps (Maple<br />

Agencies);<br />

Duratron<br />

Lineguard Maintenance<br />

Systems;<br />

Health Survey Consultants<br />

10.0 TRACER WIRE N/A #12 TWU Stranded Copper Electrical Suppliers;<br />

Canada Wire;<br />

Phillips;<br />

Pirrelli<br />

Maple Agencies (Noma)<br />

11.0 TIE-RODS<br />

(19 mm)<br />

175P190<br />

DSN0750<br />

as per manufacturer<br />

as per manufacturer<br />

N/A Stainless Steel N/A as per manufacturer


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-7<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

WATER SERVICE MATERIALS<br />

12.0 SERVICE<br />

BOXES<br />

13.0 SERVICE BOX<br />

RODS<br />

14.0 SERVICE SADDLES<br />

D.I. <strong>Water</strong>main<br />

(38 mm to 50 mm)<br />

P.V.C. <strong>Water</strong>main<br />

(19 mm to 50mm)<br />

FEATURES MANUFACTURER CATALOGUE #<br />

N/A Steel Boots only Mueller;<br />

Emco;<br />

Concord Clow;<br />

Bibby/Trojan;<br />

Rossland Supply<br />

N/A 36” Stainless Steel Mueller;<br />

Emco;<br />

Concord Clow;<br />

Bibby<br />

N/A Ductile Iron, Double Strap Smith/Blair;<br />

Ford;<br />

Robar;<br />

Cascade<br />

NN/A Stainless Steel, Double Bolt,<br />

Broad Band<br />

Smith/Blair;<br />

Ford;<br />

Cambridge Brass<br />

(Teck Saddle);<br />

Robar;<br />

Cascade<br />

D1, D3, Size 8<br />

A-714, A-715, A-716<br />

Size 8<br />

as per manufacturer<br />

as per manufacturer<br />

as per manufacturer<br />

313<br />

F202<br />

2408<br />

CSC2<br />

up to 300 mm 372<br />

up to 300 mm FS303DB<br />

up to 400 mm Series 403DB<br />

up to 300 mm 2616DB; up to<br />

400 mm 2626DB<br />

CSC2


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-8<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

Tapping Sleeve<br />

Ductile Iron<br />

N/A Order with Stainless Steel Bolts;<br />

Flange Outlet; Epoxy Coating<br />

PVC Stainless Steel;<br />

Full Surround Gridded Gasket<br />

15.0 SPACERS<br />

Casing End Seals Seal-Virgin SBR & Bands<br />

T-304 Stainless Steel<br />

Casing Spacers Fusion Coated Steel Casing<br />

Insulators<br />

16.0 METERING<br />

<strong>Water</strong> Meter<br />

16 mm – 50 mm<br />

C700- 2.3 m 3 /hr<br />

- 18.0 m 3 /hr<br />

FEATURES MANUFACTURER CATALOGUE #<br />

Ford;<br />

Robar:<br />

Smith/Blair;<br />

Concord/Daigle;<br />

Mueller<br />

Smith/Blair;<br />

Robar;<br />

Ford<br />

Cascade;<br />

PSI<br />

Advance (APS)<br />

Direct Read or Encoder Register Invensys<br />

(Sensus Technologies)<br />

FTSS or FTSC<br />

6906<br />

622<br />

as per manufacturer<br />

H-621<br />

663<br />

6606<br />

Fast Tap<br />

as per manufacturer<br />

as per manufacturer<br />

model SI & SSI<br />

Cascade;<br />

as per manufacturer<br />

PSI<br />

as per manufacturer<br />

Advance (APS) Model SI & SSI<br />

Model ECR, DR


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-9<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

<strong>Water</strong> Meter<br />

75 mm<br />

<strong>Water</strong> Meter<br />

100 mm<br />

AWWA 702<br />

ANSI Class 125<br />

AWWA 702<br />

ANSI Class 125<br />

FEATURES MANUFACTURER CATALOGUE #<br />

5m 3 c/w Touch Pad Compound<br />

Meter<br />

Operating Range 1/2 to 320 GPM<br />

(0.11 to 72.6 m 3 /h)<br />

Accuracy <strong>of</strong> 100% +/- 1.5% <strong>of</strong><br />

actual thruput<br />

Flanged 3" Round<br />

Single Register to Read High and<br />

Low Flows<br />

5m 3 c/w Touch Pad Compound<br />

Meter<br />

Operating Range 3/4 to 500 GPM<br />

(0.15 to 114 m 3 /h)<br />

Accuracy <strong>of</strong> 100% +/- 1.5% <strong>of</strong><br />

Actual Thruput<br />

Flanged 4" Round<br />

Single Register to Read High and<br />

Low Flows<br />

Invensys<br />

(Sensus Technologies)<br />

Invensys<br />

(Sensus Technologies)<br />

3" SRH ECR<br />

4" SRH ECR


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-10<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

<strong>Water</strong> Meter<br />

150 mm<br />

AWWA 702<br />

ANSI Class 125<br />

Meter Wire CSA Type CMG<br />

LL3996<br />

FEATURES MANUFACTURER CATALOGUE #<br />

5m 3 c/w Touch Pad Compound<br />

Meter<br />

Operating Range 1 1/2 to 1000<br />

GPM<br />

(0.35 to 225 m 3 /h)<br />

Accuracy <strong>of</strong> 100% +/- 1.5% <strong>of</strong><br />

Actual Thruput<br />

Flanged 6" Round<br />

Single Register to Read High and<br />

Low Flows<br />

22 Gauge<br />

3 Conductor<br />

Metgrey<br />

Temperature: 60 o C<br />

Flame Rating – FT4<br />

Invensys<br />

(Sensus Technologies)<br />

6" SRH ECR<br />

Splice Kits 3m Scotch Lok UY2 (for meter wire)<br />

17.0 MAIN STOP 19 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

B-25008<br />

301-A3H3<br />

19 mm -FB1000-3Q<br />

4701B-T


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-11<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

FEATURES MANUFACTURER CATALOGUE #<br />

25 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

38 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

52 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

18.0 CURB STOP 19 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford<br />

25 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford<br />

38mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford<br />

B-25008<br />

301-A4H4<br />

25 mm-FB1000-4Q<br />

4701B-T<br />

B-25008<br />

301-A6H6<br />

38 mm -FB1000-6<br />

4701B-T<br />

B-25008<br />

301-A7H7<br />

52 mm -FB1000-7Q<br />

4701B-T<br />

B-25209<br />

202-H3H3<br />

B44-333<br />

B-25209<br />

202-H4H4<br />

B44-444<br />

B-25209<br />

202-H6H6<br />

B44-666


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-12<br />

April, 2008<br />

MATERIAL AWWA/ANSI<br />

(Latest Edition)<br />

FEATURES MANUFACTURER CATALOGUE #<br />

50mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford<br />

19.0 COUPLINGS 19mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

20.0 ANGLE METER<br />

STOPS (Including<br />

Handle)<br />

25mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

38mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

50 mm C800 Mueller;<br />

Cambridge Brass;<br />

Ford;<br />

McDonald Brass<br />

19mm C800<br />

Full Port<br />

Mueller;<br />

Ford;<br />

McDonald Brass;<br />

Cambridge Brass<br />

B-25209<br />

202-H7H7<br />

B44-77<br />

H-15-403<br />

118-H3H3<br />

C44-33<br />

4758T<br />

H-15-403<br />

118-H4H4<br />

C44-44<br />

4758T<br />

H-15-403<br />

118-H6H6<br />

C44-66<br />

4758T<br />

H-15-403<br />

118-H7H7<br />

C44-77<br />

4785T<br />

B24258-B20298<br />

BA43-332W-H34<br />

4602B-22, 4602BT ¾”<br />

210-H3H3-H


<strong>City</strong> <strong>of</strong> <strong>Barrie</strong><br />

<strong>Water</strong> Distribution <strong>Specification</strong><br />

K-13<br />

April, 2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!