20 BISW<br />
Performance Data<br />
Wheel Diameter = 20 in.<br />
Outlet Area = 2.30 ft 2<br />
Tip Speed = 5.24 x RPM<br />
Maximum BHP = (RPM/1035) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 3147<br />
<strong>IV</strong> 3794<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
6700 2913 2620 14.6 2715 16.0 2811 17.5 2909 19.1 3002 20.8 3092 22.4 3179 24.1 3264 25.8<br />
7230 3143 2671 15.9 2766 17.4 2857 18.9 2944 20.4 3034 22.1 3123 23.8 3210 25.5 3295 27.3 3376 29.1 3533 32.7<br />
7760 3373 2726 17.2 2817 18.8 2908 20.4 2994 22.0 3078 23.6 3158 25.2 3242 27.0 3326 28.8 3408 30.7 3564 34.5<br />
8290 3604 2786 18.6 2874 20.3 2959 21.9 3046 23.6 3129 25.3 3209 27.0 3287 28.8 3362 30.5 3439 32.3 3595 36.3<br />
8820 3834 2847 20.2 2935 21.9 3019 23.6 3099 25.3 3180 27.1 3260 28.9 3337 30.7 3412 32.5 3485 34.4 3625 38.1<br />
9350 4065 2911 21.8 2996 23.6 3079 25.4 3160 27.2 3237 29.0 3312 30.8 3389 32.7 3463 34.6 3536 36.6 3675 40.4<br />
9880 4295 2979 23.5 3061 25.4 3141 27.2 3220 29.1 3297 31.0 3372 32.9 3443 34.9 3515 36.8 3587 38.8 3726 42.9<br />
10410 4526 3047 25.4 3128 27.3 3206 29.2 3282 31.2 3358 33.2 3432 35.1 3504 37.2 3573 39.2 3640 41.2<br />
10940 4756 3116 27.4 3196 29.4 3274 31.4 3349 33.4 3421 35.4 3493 37.5 3564 39.5 3633 41.6 3701 43.8<br />
11470 4986 3193 29.5 3266 31.5 3342 33.6 3416 35.7 3488 37.8 3557 39.9 3626 42.1 3694 44.2 3761 46.4<br />
12000 5217 3274 31.8 3343 33.9 3411 36.0 3485 38.2 3555 40.3 3624 42.5 3691 44.7 3756 46.9<br />
12530 5447 3356 34.2 3423 36.4 3488 38.5 3554 40.7 3624 43.0 3692 45.3 3758 47.5<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
2200 100 96 95 98 101 96 95 91 81 102<br />
80 95 94 96 99 92 90 85 78 99<br />
60 94 92 94 97 91 88 85 81 97<br />
50 95 93 95 97 91 89 85 82 97<br />
40 98 96 96 95 90 88 86 83 97<br />
3147 100 104 105 105 109 106 104 102 94 111<br />
80 103 104 104 108 103 99 96 90 109<br />
60 102 103 102 105 101 98 94 90 106<br />
50 104 103 103 105 101 98 95 91 107<br />
40 107 107 105 104 100 97 95 92 106<br />
3794 100 107 110 110 112 111 108 106 100 116<br />
80 106 109 109 111 109 104 101 95 113<br />
60 105 108 107 109 106 103 99 96 111<br />
50 107 109 108 109 106 103 100 96 111<br />
40 110 112 111 108 105 102 99 97 111<br />
% WOV = (CFM x 100) / (RPM x 4.74)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
2200 100 106 103 102 105 99 98 95 85 106<br />
80 105 99 99 101 96 93 89 80 102<br />
60 103 95 96 98 94 90 85 80 99<br />
50 103 96 95 95 92 89 84 79 97<br />
40 106 98 96 95 91 87 84 80 97<br />
3147 100 114 112 109 113 109 107 105 98 115<br />
80 114 109 105 109 106 103 99 92 111<br />
60 112 106 103 105 103 100 96 90 108<br />
50 112 106 103 103 101 98 94 90 106<br />
40 116 109 105 103 101 97 94 90 106<br />
3794 100 117 117 114 116 114 111 110 104 119<br />
80 117 114 110 112 111 108 104 98 115<br />
60 115 111 108 109 108 105 101 96 112<br />
50 115 112 108 107 106 103 100 95 111<br />
40 119 115 110 107 106 102 99 95 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
12<br />
3147<br />
GREENHECK<br />
®