CENTRIFUGAL FAN FAN<br />
CLASS <strong>IV</strong><br />
CATALOG CA ALOG SUPPLEMENT<br />
• Motor Information<br />
• Engineering Information<br />
• Air/Sound Performance<br />
• Dimensional Data<br />
GREENHECK<br />
®<br />
July 1998
2<br />
R<br />
Table of Contents<br />
Engineering Data<br />
Motor selection . . . . . . . . . . . . . . . . . . . . . . . . . . . 3<br />
Maximum and Minimum motor frame<br />
sizes, arr. 4 & 8 . . . . . . . . . . . . . . . . . . . . . . . . . 3<br />
V Belt Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3<br />
Motor starting torque. . . . . . . . . . . . . . . . . . . . . . . 4<br />
Wheel moments of inertia . . . . . . . . . . . . . . . . . . . 4<br />
High temperature RPM derating factors . . . . . . . . 4<br />
High temperature operating limits . . . . . . . . . . . . . 4<br />
Effects of air density-High Inlet Suction . . . . . . . . 4<br />
Effects of air density-Temp. & Elevation . . . . . . . . 5<br />
Effect of installation on performance. . . . . . . . . . . 6<br />
Sound Performance Testing. . . . . . . . . . . . . . . 7 - 8<br />
Sample <strong>Fan</strong> Selection. . . . . . . . . . . . . . . . . . . 9 - 10<br />
Air and Sound Performance Data<br />
Tabulated air performance, fan curves and<br />
sound power ratings<br />
Belt Drive, BISW. . . . . . . . . . . . . . . . . . . . . . 11 - 25<br />
Direct Drive, BISWD . . . . . . . . . . . . . . . . . . . 26 - 33<br />
Dimensional Data<br />
Sizes 18-73, arr. 1 . . . . . . . . . . . . . . . . . . . . . . . . 34<br />
Sizes 30-49, arr. 4 . . . . . . . . . . . . . . . . . . . . . . . . 35<br />
Sizes 30-73, arr. 8 . . . . . . . . . . . . . . . . . . . . . . . . 35<br />
<strong>Greenheck</strong> certifies that the Model BISW fans shown<br />
herein are licensed to bear the AMCA Seal. The ratings<br />
shown are based on tests and procedures performed<br />
in accordance with AMCA Publication 211 and<br />
Publication 311 and comply with the requirements of<br />
the AMCA Certified Ratings Program. The certified<br />
ratings for Model BISW are shown on pages 11 to 25.<br />
GREENHECK<br />
®
Motor Selection<br />
<strong>Greenheck</strong> centrifugal fans can be supplied with any motor that is commercially available and is appropriate for the fan size and<br />
performance required. The tables show motor frame sizes corresponding to readily available 230/460 Volt 3-phase 60 Hz motors. Consult<br />
factory for motor frame sizes on motors with larger horsepowers, 50 Hz, or different voltages. See the maximum and minimum motor frame<br />
size chart on the bottom of the page if motor is for arrangement 4 or 8 fans.<br />
Notes:<br />
1. Belt drive fan motors are 1770 RPM unless the FRPM exceeds 2700, in which case 3600 RPM motors are selected.<br />
2. 870, 1170, 1770 motors are used on direct drive Arr. 4 and 8 fans.<br />
3. Open frame motors have a 1.15 service factor. TE motors have a 1.0 service factor.<br />
4. Energy Efficient motors meet EPACT Requirements Table 1210<br />
870 RPM MOTORS<br />
Single Speed<br />
Standard Exp Energy<br />
Efficient Resist. Efficient<br />
HP Open TE Open TE<br />
15 286T 286T CF 286T 286T<br />
20 324T 324T CF 324T 324T<br />
25 326T 326T CF 326T 326T<br />
30 364T 364T CF 364T 364T<br />
40 365T 365T CF 365T 365T<br />
50 404T 404T CF 404T 404T<br />
60 405T 405T CF 405T 405T<br />
75 444T 444T CF 444T 444T<br />
100 445T 445T CF 445T 445T<br />
1770 RPM MOTORS<br />
Single Speed<br />
Energy Exp Premium<br />
Efficient Resist. Efficient<br />
HP Open TE Open TE<br />
15 254T 254T 254T 254T 254T<br />
20 256T 256T 256T 256T 256T<br />
25 284T 284T 284T 284T 284T<br />
30 286T 286T 286T 286T 286T<br />
40 324T 324T 324T 324T 324T<br />
50 326T 326T 326T 326T 326T<br />
60 364T 364T 364T 364T 364T<br />
75 365T 365T 365T 365T 365T<br />
100 404T 405T 405T 404T 405T<br />
125 405T 444T 444T 405T 444T<br />
150 444T 445T 445T 444T 445T<br />
Maximum and Minimum Motor Frame<br />
Sizes<br />
Arrangement 4 and 8 fans have specific motor size<br />
limitations. The chart below should be used to verify the<br />
motor selected will physically fit on the fan.<br />
<strong>Fan</strong><br />
Size<br />
Mtr.<br />
RPM<br />
Arr. 4 Arr. 8<br />
Min. Max. Min. Max.<br />
30 1770 284T 326T 284T 326T<br />
33 1770 286T 365T 286T 365T<br />
36 1770 326T 405T 326T 405T<br />
40 1770 404T 445T 404T 445T<br />
44 1170 364T 445T 364T 445T<br />
49 1170 404T 445T 404T 445T<br />
54 1170 - - 444T 449T<br />
60 870 - - 445T 449T<br />
60 1170 - - 444T 449T<br />
66 870 - - 445T 449T<br />
73 870 - - 449T 449T<br />
Engineering Data<br />
1170 RPM MOTORS<br />
Single Speed<br />
Energy Exp Premium<br />
Efficient Resist. Efficient<br />
HP Open TE Open TE<br />
15 284T 284T 284T 284T 284T<br />
20 286T 286T 286T 286T 286T<br />
25 324T 324T 324T 324T 324T<br />
30 326T 326T 326T 326T 326T<br />
40 364T 364T 364T 364T 364T<br />
50 365T 365T 365T 365T 365T<br />
60 404T 404T 404T 404T 404T<br />
75 405T 405T 405T 405T 405T<br />
100 444T 444T 444T 444T 444T<br />
125 445T 445T 445T 445T 445T<br />
3500 RPM MOTORS<br />
Single Speed<br />
Energy Exp Premium<br />
Efficient Resist. Efficient<br />
HP Open TE Open TE<br />
15 215T 254T 254T 215T 254T<br />
20 254T 256T 256T 254T 256T<br />
25 256T 284TS 284TS 256T 284TS<br />
30 284TS 286TS 286TS 284TS 286TS<br />
40 286TS 324TS 324TS 386TS 324TS<br />
50 324TS 326TS 326TS 324TS 326TS<br />
60 326TS 364TS 364TS 326TS 364TS<br />
75 364TS 365TS 365TS 364TS 365TS<br />
CF - Consult Factory. Motors are Build-Ups<br />
V Belt Drives<br />
Constant Speed Drives<br />
Advantages of constant speed drives include low vibration<br />
levels, ease of assembly and low cost. <strong>Fan</strong> speed changes can<br />
be accomplished in most cases simply by changing the motor<br />
pulley.<br />
Constant speed drives are recommended over variable speed<br />
drives for applications that require motors 15 HP and larger and<br />
when FRPMs are in excess of 2700.<br />
Variable Speed Drives<br />
Not recommended for use on class <strong>IV</strong> fans. Variable speed drives<br />
allow the fan speed to be changed by adjusting the pitch<br />
diameter of the motor pulley. The power to the fan must be off<br />
and locked out and the belts must be removed before manually<br />
adjusting the variable pitch pulley.<br />
GREENHECK<br />
®<br />
3
High Temperature Operating Limits<br />
4<br />
Temperature Material Arrangement Includes Options<br />
-20 to 200°F Steel, Alum., SS 1,4 & 8 None<br />
201 to 500°F<br />
501 to 750°F<br />
Steel, Stainless Steel<br />
Aluminum limited<br />
to 250°F<br />
Steel, Stainless Steel<br />
Motor Starting Torque<br />
1 & 8<br />
1 & 8<br />
- Heat Slinger<br />
- High Temp.<br />
Paint<br />
- Heat Slinger<br />
- High Temp.<br />
grease<br />
- High Temp.<br />
Paint<br />
When selecting a motor for a centrifugal fan, the motor must be<br />
capable not only of driving the fan at operating speed, but also<br />
must be capable of accelerating the fan wheel, shaft and drive<br />
to the operating speed.<br />
The fan performance tables and curves in this catalog show the<br />
brake horsepower required to operate the fan once it is brought<br />
to speed. For applications requiring a large air volume at a low<br />
static pressure, the BHP required at the fan’s operating RPM<br />
may not be sufficient to initially start the fan. If the time required<br />
to bring the fan to speed is excessive, the motor winding<br />
insulation can be damaged due to excessive temperature rise<br />
and the life of the motor seriously affected.<br />
For a belt drive centrifugal fan the required motor starting<br />
torque capability can be expressed by the following formula:<br />
WR 2<br />
M = WR 2<br />
F x<br />
( MRPM)<br />
FRPM 2<br />
x (1.1)<br />
WR 2<br />
M = The moment of inertia that the<br />
motor must be capable of<br />
turning at the motor shaft, LB-Ft. 2<br />
WR 2<br />
F = The moment of inertia of the<br />
fan wheel, LB-Ft. 2<br />
FRPM = <strong>Fan</strong> RPM<br />
MRPM = Motor RPM<br />
For a direct drive fan, WR 2<br />
M must exceed WR 2<br />
F<br />
Effect of Air Density - High Suction at <strong>Fan</strong> Inlet<br />
<strong>Fan</strong> RPM Limitations<br />
The maximum allowable wheel RPM shown on the fan<br />
performance pages are for fans of standard steel operating at<br />
70°F. Since the strength of the fan wheel, shaft and bearings<br />
decrease with an increase in temperature, maximum allowable<br />
speeds must be reduced by the correction factors shown below.<br />
RPM Correction Factors For High Temperatures<br />
Temperature<br />
Wheel Material<br />
(Degrees F) Aluminum Steel 316 SS<br />
70 1.00 1.00 1.00<br />
200 1.00 .97 .92<br />
250 .95 .96 .89<br />
300 .95 .87<br />
400 .93 .83<br />
500 .90 .80<br />
600 .85 .77<br />
700 .80 .75<br />
800 .72<br />
Moments of Inertia (Lb-Ft 2 )<br />
Moments of inertia are shown for steel<br />
wheels with 100% wheel width. Aluminum<br />
wheels are approximately 40% of the value<br />
shown.<br />
STEEL BACKWARD INCLINED<br />
CENTRIFUGAL WHEELS<br />
<strong>Fan</strong> Size<br />
<strong>Class</strong> <strong>IV</strong><br />
Single Width<br />
18 17<br />
20 24<br />
22 40<br />
24 66<br />
27 94<br />
30 143<br />
33 210<br />
36 377<br />
40 581<br />
44 869<br />
49 1350<br />
54 2025<br />
60 3893<br />
66 5511<br />
73 7942<br />
The density used for fan selection is that which is measured at the fan inlet. When the inlet total pressure exceeds 10" in suction, the<br />
density at the fan inlet should be corrected by the following values. These values should be multiplied to the fan static pressure and<br />
the result used for the proper fan selection. With suction pressures less than 10 in., this correction is typically ignored.<br />
Inlet P t<br />
Suction<br />
D.C.F.<br />
-10" 1.03<br />
-14" 1.04<br />
-18" 1.05<br />
-22" 1.06<br />
EXAMPLE<br />
10 in. Ps x 1.03 = 10.3 in. Corrected Ps.<br />
Use 10.3 in. Ps to select fan in performance pages.<br />
GREENHECK<br />
®
Effect of Air Density - Temperature and Elevation<br />
Ratings in the fan performance tables and curves of this catalog are based on standard air (clean, dry air with a density of .075 pounds<br />
per cubic foot, barometric pressure at sea level of 29.92 inches of mercury, temperature of 70°F.). Selecting a fan to operate at<br />
conditions other than standard air requires an adjustment to both static pressure and brake horsepower.<br />
A cubic foot of air has a constant volume regardless of temperature or elevation. However, air density changes with non-standard<br />
temperature or elevation. Therefore, when selecting a fan to operate at a non-standard air density using standard air density tables and<br />
curves, corrections must be made to parameters affected by air density. These parameters are static pressure and brake horsepower.<br />
For example, a size 30<br />
BISW centrifugal fan is<br />
to deliver 17,750 CFM at<br />
10.0 in. static pressure.<br />
Elevation is 3000 feet,<br />
temperature is 150°F.<br />
The 10.0 in. static<br />
pressure refers to the<br />
0<br />
50<br />
0.87<br />
0.96<br />
0.90<br />
1.00<br />
0.94<br />
1.04<br />
0.97<br />
1.08<br />
1.01<br />
1.11<br />
1.05<br />
1.15<br />
1.08<br />
1.20<br />
1.13<br />
1.24<br />
1.17<br />
1.30<br />
1.22<br />
1.34<br />
1.26<br />
1.40<br />
1.31<br />
1.45<br />
1.37<br />
1.51<br />
1.43<br />
1.57<br />
1.48<br />
1.63<br />
1.54<br />
1.70<br />
static pressure at the<br />
operating air density, in<br />
this case at 3000 feet,<br />
70<br />
100<br />
1.00<br />
1.06<br />
1.04<br />
1.10<br />
1.08<br />
1.14<br />
1.12<br />
1.18<br />
1.16<br />
1.22<br />
1.22<br />
1.27<br />
1.25<br />
1.32<br />
1.30<br />
1.37<br />
1.35<br />
1.42<br />
1.40<br />
1.48<br />
1.45<br />
1.54<br />
1.51<br />
1.60<br />
1.57<br />
1.66<br />
1.64<br />
1.74<br />
1.70<br />
1.80<br />
1.77<br />
1.88<br />
150°F. Intuitively, we 150 1.15 1.19 1.24 1.30 1.33 1.38 1.44 1.49 1.55 1.61 1.67 1.74 1.81 1.89 1.96 2.04<br />
realize that at higher<br />
than standard<br />
200 1.25 1.29 1.34 1.40 1.44 1.50 1.56 1.61 1.68 1.75 1.81 1.89 1.96 2.05 2.13 2.21<br />
elevations and<br />
250 1.34 1.39 1.44 1.50 1.55 1.61 1.67 1.74 1.80 1.88 1.95 2.02 2.10 2.20 2.28 2.37<br />
temperatures, air<br />
density will be lower<br />
than standard.<br />
300<br />
350<br />
1.43<br />
1.53<br />
1.49<br />
1.58<br />
1.54<br />
1.64<br />
1.60<br />
1.71<br />
1.66<br />
1.77<br />
1.72<br />
1.84<br />
1.79<br />
1.91<br />
1.86<br />
1.98<br />
1.93<br />
2.06<br />
2.01<br />
2.14<br />
2.08<br />
2.22<br />
2.16<br />
2.31<br />
2.25<br />
2.40<br />
2.35<br />
2.51<br />
2.43<br />
2.60<br />
2.53<br />
2.71<br />
Therefore, we must<br />
determine what static<br />
pressure at standard air<br />
400<br />
500<br />
1.62<br />
1.81<br />
1.68<br />
1.88<br />
1.75<br />
1.95<br />
1.81<br />
2.02<br />
1.88<br />
2.10<br />
1.94<br />
2.18<br />
2.03<br />
2.26<br />
2.09<br />
2.35<br />
2.19<br />
2.44<br />
2.27<br />
2.54<br />
2.37<br />
2.63<br />
2.45<br />
2.73<br />
2.54<br />
2.84<br />
2.66<br />
2.97<br />
2.75<br />
3.08<br />
2.87<br />
3.20<br />
density will equate to 600 2.00 2.07 2.15 2.23 2.31 2.40 2.50 2.59 2.69 2.84 2.91 3.02 3.14 3.28 3.40 3.54<br />
10.0 in. static pressure<br />
at our operating density.<br />
Since standard air<br />
700<br />
800<br />
2.19<br />
2.38<br />
2.27<br />
2.48<br />
2.35<br />
2.57<br />
2.44<br />
2.67<br />
2.53<br />
2.76<br />
2.63<br />
2.86<br />
2.73<br />
2.98<br />
2.83<br />
3.09<br />
2.94<br />
3.21<br />
3.07<br />
3.33<br />
3.17<br />
3.45<br />
3.31<br />
3.59<br />
3.44<br />
3.74<br />
3.59<br />
3.90<br />
3.72<br />
4.05<br />
3.88<br />
4.21<br />
density is greater than<br />
operating air density in<br />
this case, we would<br />
expect the corrected<br />
900<br />
1000<br />
2.56<br />
2.76<br />
2.66<br />
2.87<br />
2.76<br />
2.989<br />
2.87<br />
3.09<br />
2.97<br />
3.20<br />
3.07<br />
3.31<br />
3.20<br />
3.45<br />
3.33<br />
3.59<br />
3.46<br />
3.73<br />
3.58<br />
3.86<br />
3.71<br />
4.00<br />
3.87<br />
4.17<br />
4.02<br />
4.33<br />
4.20<br />
4.53<br />
4.35<br />
4.69<br />
4.53<br />
4.89<br />
static pressure to be greater than the operating static pressure.<br />
The accompanying table gives air density correction factors for non-standard temperatures and elevations.<br />
The example below shows the relationship of fan performance at sea level and at 3000 ft. elevation and 150°F.<br />
EXAMPLE<br />
Air<br />
Temp.<br />
°F<br />
The following example shows how to properly select the fan described above:<br />
1. Since the air volume delivered by the fan is not affected<br />
by density, airflow remains 17,750 CFM.<br />
2. Determine correction factor from chart for an elevation of<br />
3000 feet and air temperature of 150°F. The correction<br />
factor is 1.30.<br />
3. Multiply the specified operating static pressure by the<br />
correction factor to determine the standard air density<br />
equivalent static pressure (Corrected static pressure =<br />
10.0 in. x 1.30 = 13.0 in. Ps).<br />
4. Refer to the fan performance table for a 30 BISW.<br />
At 17,750 CFM and 13.0 in. Ps: <strong>Fan</strong> RPM = 2012,<br />
BHP = 49.8.<br />
5. 2012 <strong>Fan</strong> RPM is required to produce the desired<br />
performance.<br />
6. Since the horsepower selected refers to standard air<br />
density, this must be corrected to reflect actual BHP at<br />
the lighter operating air. Operating BHP = standard BHP<br />
÷ 1.30, or 49.8 ÷ 1.30 = 38.3 BHP.<br />
If a fan is selected to operate at high temperatures, the<br />
motor must be of sufficient horsepower to handle the<br />
increased load at any lower operating temperature where<br />
the air is more dense. Assume the air entering the 30 BISW<br />
fan at start-up is 0°F. For 0°F and 3000 feet elevation the air<br />
density correction factor is 0.97. BHP at 0°F = 49.8 ÷ 0.97 =<br />
51.3, therefore, a 75 HP motor is required.<br />
AIR DENSITY CORRECTION FACTORS<br />
Elevation (Feet Above Sea Level)<br />
0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000 11000 12000 13000 14000 15000<br />
Ps<br />
25<br />
20<br />
15<br />
10<br />
5<br />
49.8 BHP<br />
10.0 in. Ps<br />
Sea Level, 70 - Static Pressure<br />
Sea Level, 70 - BHP<br />
3000 ft., 150 - Static Pressure<br />
3000 ft., 150 - BHP<br />
17,750<br />
CFM<br />
38.3 BHP<br />
13.0 in. Ps<br />
0<br />
10<br />
0 5 10 15 20 25 30 35 40<br />
CFM x 1000<br />
60<br />
50<br />
40<br />
30<br />
20<br />
BHP<br />
GREENHECK<br />
®<br />
5
Effect Of Installation On Performance<br />
6<br />
Ratings presented in the performance tables and curves of this<br />
catalog were derived from tests made in accordance with AMCA<br />
Standard 210 – “Laboratory Methods of Testing <strong>Fan</strong>s for<br />
Ratings.” The AMCA test procedure utilizes an open inlet and a<br />
straight outlet duct to assure maximum static regain.<br />
Any installation with inlet or discharge configurations that deviate<br />
from this standard may result in reduced fan performance.<br />
Restricted or unstable flow at the fan inlet can cause pre-rotation<br />
of incoming air or uneven loading of the fan wheel yielding large<br />
system losses and increased sound levels. Free discharge or<br />
turbulent flow in the discharge ductwork will also result in<br />
system effect losses.<br />
Static pressure losses due to inlet and discharge conditions can<br />
be expressed in terms of system effect factors. The static<br />
pressure for selection of the fans equals the system static<br />
pressure plus the system effect factor.<br />
Some common inlet and discharge conditions which affect fan<br />
performance are:<br />
NON-DUCTED INLET CLEARANCE<br />
Installation of a fan with an open inlet too close to a wall or<br />
bulkhead will cause reduced fan performance. It is desirable to<br />
have one fan wheel diameter if possible and a minimum of three<br />
fourths of a wheel diameter between the fan inlet and the wall.<br />
System effect curve #3 depicts the pressure loss for one-half<br />
wheel diameter clearance.<br />
FREE DISCHARGE<br />
Free or abrupt discharge into a plenum results in a reduction in<br />
fan performance. The effect of static regain in discharge is not<br />
realized. System effect curve #2 depicts the pressure loss for<br />
free or abrupt discharge.<br />
INLET DUCT TURNS<br />
Turning<br />
Vanes<br />
1 <strong>Fan</strong><br />
Wheel<br />
Dia.<br />
1 <strong>Fan</strong><br />
Wheel<br />
Dia.<br />
GOOD POOR<br />
Installation of a duct turn or elbow too close to the fan inlet<br />
reduces fan performance because the air is loaded unevenly into<br />
the fan wheel. To achieve full fan performance there should be at<br />
least one fan wheel diameter between the turn or elbow and the<br />
fan inlet. Curve #1 shows the system effect factor when less than<br />
one diameter is provided. Note: Use of an inlet box in lieu of a<br />
turn or elbow significantly reduces system effect.<br />
INLET SPIN<br />
Inlet spin is a frequent cause of reduced fan performance. The<br />
change in fan performance is a function of the intensity of spin<br />
and not easily defined. The best solution is proper duct design<br />
and airflow patterns.<br />
DISCHARGE DUCT TURNS<br />
Duct turns located near the fan discharge should always be in<br />
the direction of the fan rotation.<br />
<strong>Fan</strong> performance is reduced when duct turns are made<br />
immediately off the fan discharge. To achieve cataloged fan<br />
performance there should be at least three equivalent duct<br />
diameters of straight ductwork between the fan discharge and<br />
any duct turns. Curve #4 shows the system effect factor for two<br />
diameters of straight ductwork and curve #2 for one diameter.<br />
SYSTEM EFFECT FACTOR CURVES<br />
STATIC PRESSURE LOSS<br />
1.2<br />
1.0<br />
0.8<br />
0.6<br />
0.4<br />
0.2<br />
0.0<br />
Rotation<br />
Rotation<br />
POOR<br />
Rotation<br />
POOR<br />
Turning<br />
Vanes<br />
Length of Straight Duct<br />
GOOD<br />
CURVE 1<br />
Rotation<br />
GOOD<br />
CURVE 2<br />
CURVE 3<br />
CURVE 4<br />
0 5 10 15 20 25 30 35 40 45<br />
FPM X 100<br />
OUTLET VELOCITY<br />
Additional information on system effect factors can be found in<br />
AMCA Publication 201 – “<strong>Fan</strong>s and Systems” and ASHRAE<br />
Handbooks.<br />
GREENHECK<br />
®
Sound Performance Data<br />
AMCA Licensed Ratings<br />
Sound tests of Model BISW were conducted in <strong>Greenheck</strong>'s AMCA Registered sound laboratory in accordance with AMCA Standard 300.<br />
Inlet and outlet sound ratings comply with AMCA Publication 311, qualifying these models to bear the AMCA seal for sound and air<br />
performance. The sound power levels published here can be compared directly with those of other similarly rated fans, or used as a<br />
baseline to determine sound levels in occupied spaces.<br />
The sound data in this brochure is the result of extensive testing, which included both inlet and outlet sound tests on single width<br />
centrifugal fans. Typically, fan manufacturers publish only inlet sound for single width fans. The assumption they make is that outlet sound is<br />
identical to inlet sound. Sound data based on this assumption is simply not accurate enough for today's sound sensitive installations. This<br />
assumption also ignores duct end corrections for outlet sound.<br />
Test Methods<br />
AMCA Standard 300 clearly defines methods used to test fans in a reverberant sound test room. The reverberant room is specifically<br />
designed to allow sound waves to be dispersed evenly throughout the room. The walls have a hard surface that reflects sound and are<br />
positioned to prevent resonances which could result in quiet areas within the room.<br />
Sound power cannot be directly measured. The test method is based on a Reference Sound Source (RSS) substitution for determining fan<br />
sound power. The RSS is a laboratory calibrated device which has a known sound power output level. The test fan is installed as shown<br />
below. The RSS is energized and the sound pressure levels in the reverberant room are recorded. The fan is then operated without the RSS<br />
and the fan sound pressure levels are recorded for various points of operation. Since the sound power levels of the RSS are known, the<br />
substitution method is used to determine the sound power levels of the fan. This method is illustrated in the following example.<br />
Octave Band 1 2 3 4 5 6 7 8<br />
Center Frequency (Hz) 63 125 250 500 1000 2000 4000 8000<br />
Calibrated RSS Sound Power (Lwr) 82 81 81 81 81 81 79 78<br />
Measured RSS Sound Pressure (Lpq) 70 74 75 76 75 74 69 61<br />
Difference (Lwr-Lpq) 12 7 6 5 6 7 10 17<br />
Measured <strong>Fan</strong> Sound Pressure (Lpm) 68 72 69 69 68 62 57 46<br />
Substitution (Lwr-Lpq, from above) +12 +7 +6 +5 +6 +7 +10 +17<br />
<strong>Fan</strong> Sound Power (Lw) 80 79 75 74 74 69 67 63<br />
Test Setups<br />
The illustrations at right show where the sound levels were measured<br />
with respect to the fan. Inlet sound was tested as in Figure 2 of<br />
Standard 300 and outlet sound was tested as in Figure 3. Inlet and<br />
outlet sound were determined in the same inlet and outlet<br />
configurations as the air tests. (Installation Type B - free inlet, ducted<br />
outlet.)<br />
Calculating <strong>Fan</strong> Sound Power<br />
Interpreting Sound Data<br />
Sound power levels in this brochure are presented as dB (re 10 -12<br />
watts) in each of the eight full octave bands with center frequencies<br />
from 63 Hz to 8000 Hz. They are also presented as a single A-weighted<br />
sound power level, LwA. Charts are provided covering the full range of<br />
fan speeds and percent wide open volume (%WOV) for each fan size.<br />
Outlet sound power data is based on a ducted outlet and therefore<br />
includes duct end reflection corrections.<br />
Airflow<br />
<strong>Fan</strong><br />
Reference<br />
Sound<br />
Source<br />
Microphone<br />
Path<br />
Reverberant<br />
Room<br />
AMCA Standard 300 - Figure 2: <strong>Fan</strong> Inlet Sound Testing<br />
Installation Type B: Free Inlet, Ducted Outlet<br />
<strong>Fan</strong> Airflow<br />
Reference<br />
Sound<br />
Source<br />
Microphone<br />
Path<br />
Reverberant<br />
Room<br />
AMCA Standard 300 - Figure 3: <strong>Fan</strong> Outlet Sound Testing<br />
Installation Type B: Free Inlet, Ducted Outlet<br />
(Ratings include the effects of duct end correction)<br />
Units in<br />
dB<br />
GREENHECK<br />
®<br />
7
Outlet Sound - Duct End Corrections<br />
This correction accounts for sound that is reflected back<br />
into the duct where there is an abrupt termination of the<br />
duct.<br />
AMCA Standard 300 requires that outlet sound power for<br />
fans with ducted outlets include Duct End Corrections.<br />
These corrections account for any sound power that may be<br />
present in the duct but is not measured in the reverberant<br />
room, because it is reflected back into the duct at the<br />
discharge.<br />
Duct end corrections are included in all outlet sound power<br />
ratings.<br />
Tolerance and Application<br />
The certification process in AMCA Standard 311 call for a precertification test to verify original test results. Check tests are also required<br />
every 3 years for each model licensed. Test data must agree with the published sound power within the following tolerance levels:<br />
These tolerance levels are a good indication of the variance that could occur from one fan or test setup to another. Once installed,<br />
however, there are many other factors that can affect the sound power generated by a fan.<br />
The lower frequencies (below 125 Hz) are greatly affected by vibration. <strong>Fan</strong> wheel balance, motor balance, drive alignment, etc., all affect<br />
the vibration level of the fan and can increase sound power in the 1st and 2nd octaves. When ducts are not properly isolated from the fan,<br />
these vibrations can be transmitted into the ducts, which can generate additional low frequency sound.<br />
Sound power generated by a fan can also be influenced by system effects. System effects are pressure losses caused by inlet or outlet<br />
restrictions, or other conditions causing non-uniform airflow at the inlet or discharge of a fan (see AMCA publication 201). Examples<br />
include inlet or outlet elbows too close to a fan, restricted inlets, and fan accessories. While system effects can prevent fans from<br />
reaching their designed air performance, they can also result in increased sound power levels. Typically, system effects cause pressure<br />
fluctuations which influence the lower frequencies. Poor inlet conditions can also greatly increase sound levels at the blade passage<br />
frequency (BPF). The blade passage frequency refers to how often a blade or wheel fin passes a stationary location of the housing and<br />
can be calculated using the following equation:<br />
Sound is becoming increasingly critical for most fan installations. <strong>Greenheck</strong> employs extensive research and testing to provide sound<br />
data that is as thorough and accurate as possible. However, sound pressure levels in occupied spaces are affected by the acoustical<br />
qualities of the space, distance from source to receiver, etc. Therefore, published sound power data can be used only as a baseline for<br />
determining the resulting sound pressure levels an occupant hears. While <strong>Greenheck</strong> provides products which meet published sound<br />
power levels, no manufacturer can be responsible for poor installations or system designs beyond their control. For further information on<br />
installation practices, see AMCA publication 201, “<strong>Fan</strong>s and Systems.”<br />
Sound Power<br />
Sound power data is charted for the full range of RPM and percent wide open volume (% WOV) for belt drive and RPM and static<br />
pressure for direct drive in each unit size.<br />
The % WOV is a convenient way to indicate the operating point (pressure and CFM) for a given fan RPM. To calculate the % WOV for a<br />
given fan size, use the equation given on the performance page.<br />
8<br />
Size<br />
63 Hz<br />
Single Width <strong>Fan</strong>s<br />
125 Hz 250 Hz<br />
18 9 5 2<br />
20 9 4 1<br />
22 8 4 1<br />
24 7 3<br />
27 6 3<br />
30 6 2<br />
33 5 2<br />
36 5 2<br />
40 4 1<br />
44 4 1<br />
49 3<br />
54 3<br />
60 2<br />
66 2<br />
73 2<br />
BPF (Hz) = <strong>Fan</strong> RPM x Number of Blades (All <strong>Greenheck</strong> wheels have 9 blades)<br />
60<br />
% WOV =<br />
CFM x 100<br />
RPM x K<br />
Duct End Corrections (dB)<br />
Octave Band 1 2 3 4 5 6 7 8<br />
Center Frequency (Hz) 63 125 250 500 1000 2000 4000 8000<br />
Tolerance +6 +3 +3 +3 +3 +3 +3 +3<br />
Use the following procedure to calculate sound data for a specific <strong>Fan</strong> RPM and % WOV:<br />
1. Determine the eight sound power levels for the specified % WOV using the higher <strong>Fan</strong> RPM shown.<br />
2. Determine the eight sound power levels for the specified % WOV using the lower <strong>Fan</strong> RPM shown.<br />
3. Interpolate between the higher and lower sound power levels using the specified RPM.<br />
GREENHECK<br />
®
Belt Drive <strong>Fan</strong> Selection Procedure<br />
An important point to remember when manually selecting a centrifugal fan is that more than one fan is available to meet the<br />
desired performance (CFM and Ps). Selection criteria such as unit size, efficiency, speed, outlet velocity, horsepower, or<br />
construction material may also dictate which fan to select.<br />
Abelt drive performance page exists for each wheel diameter (18 - 73 inches) which includes fan curves and tabular<br />
performance for both air and sound. See page 36 for complete model number code.<br />
Belt Drive <strong>Fan</strong> Selection Example<br />
Enter the performance table with the desired CFM and Ps. Obtain the fan RPM, brake horsepower (BHP) and class<br />
requirements. Verify the required motor HP by using the performance graph.<br />
For this example, select 44300 CFM at 15 inches static pressure. From the table we get a fan RPM of 1444, requiring<br />
134 BHP with class <strong>IV</strong> construction. Go to the graph and verify the operating point, motor HP and the fan class. Our<br />
example confirms that we will be using a class <strong>IV</strong> fan with a 150 HP motor.<br />
44 BISW<br />
Performance Data<br />
Wheel Diameter = 44 1/2 in.<br />
Outlet Area = 11.39 ft 2<br />
Tip Speed = 11.65 x RPM<br />
Maximum BHP = (RPM/276) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1392<br />
<strong>IV</strong> 1675<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
37700 3309 1198 77.3 1236 84.1 1274 90.9 1311 97.9 1346 105 1389 113 1429 121 1468 130 1505 138<br />
39900 3503 1219 82.9 1259 90.0 1297 97.2 1332 105 1367 112 1401 119 1438 127 1477 136 1514 144<br />
42100 3696 1244 89.1 1281 96.3 1318 104 1355 111 1389 119 1422 127 1455 134 1487 142 1523 151<br />
44300 3889 1270 95.6 1306 103 1341 111 1376 119 1411 126 1444 134 1476 142 1508 150 1538 159<br />
46500 4082 1295 102 1331 110 1366 118 1399 126 1433 134 1466 142 1497 151 1529 159 1559 168<br />
48700 4275 1322 110 1357 118 1391 126 1424 134 1456 143 1488 151 1520 160 1551 168 1580 177<br />
50900 4468 1348 117 1383 126 1417 134 1449 143 1481 151 1512 160 1542 169 1573 178 1603 187<br />
53100 4661 1376 125 1410 134 1443 143 1475 152 1507 161 1537 169 1567 178 1595 188 1624 197<br />
55300 4855 1405 133 1437 142 1470 152 1501 161 1532 170 1562 179 1592 189 1620 198 1648 207<br />
57500 5048 1435 141 1466 151 1496 161 1528 170 1558 180 1588 190 1617 199 1645 209<br />
59700 5241 1465 150 1496 160 1525 170 1555 180 1585 190 1614 200 1643 210<br />
61900 5434 1498 160 1525 170 1555 180 1584 191 1612 201 1641 211<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10-12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1000 100 106 111 104 98 96 95 88 82 103<br />
80 101 109 99 94 92 89 83 79 99<br />
60 99 106 96 90 90 87 85 82 96<br />
50 101 107 96 89 89 87 85 83 96<br />
40 109 109 100 92 90 88 86 83 99<br />
1392 100 112 117 117 108 104 103 98 92 112<br />
80 107 114 114 103 100 98 93 88 109<br />
60 104 111 110 100 97 96 93 90 106<br />
50 106 112 111 99 96 95 93 91 106<br />
40 115 117 114 103 98 96 94 92 109<br />
1675 100 115 121 120 114 109 107 104 97 117<br />
80 110 117 117 110 105 103 99 94 113<br />
60 107 114 114 107 102 100 98 95 110<br />
50 110 116 114 106 101 99 98 96 110<br />
40 118 121 117 110 103 101 99 96 113<br />
20<br />
RPM BHP<br />
1586 162<br />
1595 169<br />
1603 176<br />
1618 184<br />
1639 194<br />
% WOV = (CFM x 100) / (RPM x 51.4)<br />
- Wheel Diameter<br />
OUTLET SOUND POWER, Lwo<br />
- Outlet Area; used to calculate<br />
Outlet Velocity (OV)<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1000 100 113 115 107 103 100 98 92 85 107<br />
80 110 112 102 99 96 92 87 81 102<br />
60 105 110 100 96 92 89 85 81 100<br />
50 106 109 99 95 91 88 85 82 99<br />
40 107 108 98 94 90 87 85 82 98<br />
1392 100 119 121 119 112 109 107 102 96 116<br />
80 116 118 115 108 104 101 96 91 112<br />
60 111 115 114 105 101 98 94 90 109<br />
50 112 115 113 104 100 96 94 90 108<br />
40 113 115 112 103 99 95 93 90 107<br />
1675 100 123 125 123 118 114 111 108 102 121<br />
80 119 122 119 114 109 106 102 96 116<br />
60 114 118 117 111 106 103 99 95 114<br />
50 115 118 116 111 105 101 98 95 113<br />
40 116 118 115 110 104 100 98 95 112<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
20<br />
1392<br />
GREENHECK<br />
®<br />
Enter the <strong>Fan</strong> Sound Table<br />
with the <strong>Fan</strong> RPM from the<br />
performance table and the<br />
% WOV from the equation.<br />
Obtain the eight octave<br />
ratings for inlet (Lwi) and<br />
Outlet (Lwo) Sound Power.<br />
EXAMPLE<br />
For this example, the %WOV<br />
value is 60 and the eight<br />
octave ratings are to be<br />
interpolated between the two<br />
sets of RPM values. See page<br />
8 for details.<br />
NOTE: The % WOV for your<br />
desired performance can be<br />
found using the equation at<br />
the top of the Sound Power<br />
Table.<br />
If the RPM and %WOV can<br />
not be found in the chart, the<br />
eight octave ratings can then<br />
be found using interpolation.<br />
Additional Information<br />
on Performance Page<br />
CFM<br />
OV=<br />
OA<br />
- Equation for tip speed<br />
- Max. BHP for fan at<br />
specified RPM<br />
- Most efficient selections<br />
shown with bolded<br />
values<br />
- Wheel class used to<br />
meet performance<br />
- Max. class wheel RPM<br />
GREENHECK<br />
®<br />
9
Direct Drive <strong>Fan</strong> Selection Procedure<br />
10<br />
Most direct drive applications will have multiple fan size and RPM selections which will satisfy the design requirements.<br />
Selections can be narrowed further by RPM or horsepower restrictions, sound criteria or space restrictions.<br />
The direct drive performance graphs contain fan wheel sizes ranging from 30 to 73 inch diameters and RPMs ranging<br />
from 870 to 1770. All fan sizes and RPMs have fan performance curves in 5 percent increments from a full width wheel<br />
down to a 50% wheel width. Both static pressure vs. CFM (shown as solid lines) and brake horsepower vs. CFM (dashed<br />
lines) are depicted.<br />
Inlet and outlet sound power is shown for all fan sizes and RPMs. Tables of sound power for direct drive fans are found starting<br />
on page 32. Sound power for each selection can be determined by matching fan RPM with the system static pressure.<br />
See page 36 for complete model number code.<br />
Direct Drive <strong>Fan</strong> Selection Example<br />
Enter the performance graph with the desired CFM and Ps. Obtain the percentage wheel width and brake horsepower<br />
requirements.<br />
For this example, select 40,000 CFM at 6 inches static pressure which is shown as 'A'. The static vs CFM curve (solid<br />
line) that satisfies this point of operation has a wheel width of 85%. To determine the brake horsepower, find the<br />
intersection of the brake horsepower vs. CFM curve (dashed line) for a 85% wheel at 40000 CFM (point 'B'). Read the<br />
brake horsepower value from the right side of the table. For this selection, the brake horsepower is approximately 66. A<br />
75 horsepower motor or larger is required. See pages 3 and 4 to find motor frame sizes and check minimum<br />
and maximum motor frame size for Arr. 4 and 8.<br />
44 BISWD<br />
44 BISWD<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1392<br />
<strong>IV</strong> 1675<br />
Wheel Diameter 44 1/2 in.<br />
Outlet Area 11.39 ft. 2<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1170 2 107 113 108 101 99 97 91 85 106 1170 2 115 117 111 106 102 100 95 88 110<br />
4 106 112 107 100 97 95 89 84 105 4 114 116 110 105 101 98 93 87 108<br />
6 104 112 106 98 96 93 88 83 103 6 113 115 108 103 99 96 91 85 107<br />
8 102 110 104 96 94 92 88 84 102 8 110 113 107 101 98 94 90 85 105<br />
10 102 109 102 94 93 91 88 86 100 10 108 112 106 100 96 92 89 85 104<br />
B<br />
x<br />
x<br />
A<br />
Sound Power [dB Ref 10 -12 watts]<br />
Determining Inlet and<br />
Outlet Sound<br />
Enter the fan sound table with<br />
the <strong>Fan</strong> RPM and static<br />
pressure. For this example,<br />
the eight octave ratings are<br />
circled in the table below.<br />
Tables for direct drive sound<br />
power levels are found<br />
starting on page 32.<br />
Note: If the static pressure is<br />
not indicated in the chart, the<br />
eight octave ratings can be<br />
interpolated.<br />
Additional Information<br />
on Performance Graph<br />
-Wheel Diameter<br />
-Outlet Area; used to calculate<br />
Outlet Velocity (OV)<br />
CFM<br />
OV=<br />
OA<br />
-Wheel class used to meet<br />
performance<br />
-Max. class wheel RPM<br />
GREENHECK<br />
®
18 BISW<br />
Performance Data<br />
Wheel Diameter = 18 1/4 in.<br />
Outlet Area = 1.92 ft 2<br />
Tip Speed = 4.78 x RPM<br />
Maximum BHP = (RPM/1206) 3<br />
Pressure <strong>Class</strong> Limits 3450<br />
<strong>Class</strong> Max. RPM<br />
III 3450<br />
<strong>IV</strong> 4160<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
5700 2968 2886 12.4 2990 13.6 3090 14.9 3196 16.2 3299 17.6 3397 19.0 3493 20.4 3585 21.8 3675 23.2<br />
6150 3203 2943 13.5 3047 14.8 3146 16.1 3242 17.4 3333 18.7 3432 20.1 3528 21.6 3620 23.1 3709 24.6 3881 27.6<br />
6600 3437 3007 14.7 3105 16.0 3204 17.3 3298 18.7 3390 20.1 3478 21.5 3563 22.9 3655 24.4 3744 26.0 3916 29.1<br />
7050 3671 3075 15.9 3171 17.3 3263 18.7 3356 20.1 3447 21.5 3534 23.0 3619 24.5 3702 25.9 3782 27.4 3951 30.7<br />
7500 3906 3143 17.2 3239 18.7 3331 20.1 3419 21.6 3504 23.1 3592 24.6 3676 26.1 3758 27.7 3838 29.2 3991 32.4<br />
7950 4140 3217 18.7 3308 20.2 3399 21.7 3487 23.2 3571 24.8 3652 26.3 3734 27.9 3816 29.5 3895 31.1 4047 34.4<br />
8400 4375 3293 20.2 3382 21.7 3468 23.3 3555 24.9 3639 26.5 3720 28.1 3799 29.8 3874 31.4 3952 33.1 4104 36.5<br />
8850 4609 3370 21.8 3458 23.4 3543 25.1 3626 26.7 3707 28.4 3788 30.0 3866 31.7 3942 33.4 4015 35.2<br />
9300 4843 3449 23.5 3535 25.2 3619 26.9 3701 28.6 3779 30.3 3857 32.0 3934 33.8 4010 35.6 4083 37.4<br />
9750 5078 3539 25.4 3614 27.1 3696 28.9 3777 30.6 3855 32.4 3931 34.2 4004 36.0 4078 37.8<br />
10200 5312 3630 27.4 3704 29.2 3776 30.9 3854 32.8 3931 34.6 4006 36.5 4079 38.3<br />
10650 5546 3722 29.5 3795 31.3 3866 33.2 3934 35.0 4008 36.9 4082 38.8<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
2500 100 96 95 97 102 96 96 93 83 103<br />
80 95 94 95 101 93 91 87 80 100<br />
60 94 92 93 98 91 89 85 81 98<br />
50 96 93 95 98 91 89 86 83 98<br />
40 99 96 96 96 90 89 86 83 97<br />
3450 100 102 105 105 108 106 103 101 94 111<br />
80 101 103 103 107 104 99 96 90 108<br />
60 100 102 101 104 101 97 94 90 106<br />
50 102 103 102 104 101 97 95 91 106<br />
40 105 106 105 103 100 96 94 92 105<br />
4160 100 105 109 110 111 110 108 106 100 115<br />
80 104 108 108 110 109 104 101 95 113<br />
60 104 107 106 108 106 102 99 95 110<br />
50 105 108 107 108 106 102 99 96 111<br />
40 108 111 110 108 105 101 99 96 110<br />
% WOV = (CFM x 100) / (RPM x 3.60)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
2500 100 107 103 101 106 99 99 96 87 106<br />
80 106 99 97 102 97 94 90 82 103<br />
60 104 95 96 98 94 91 86 81 99<br />
50 104 96 96 96 93 89 85 80 98<br />
40 108 98 96 96 92 88 85 80 98<br />
3450 100 113 112 109 111 109 106 105 98 114<br />
80 112 109 105 108 106 102 99 93 110<br />
60 110 106 102 104 103 99 95 90 107<br />
50 110 107 103 102 101 98 94 90 106<br />
40 114 110 104 102 101 97 93 89 106<br />
4160 100 116 116 114 115 114 111 109 104 118<br />
80 116 114 110 111 111 107 104 99 115<br />
60 114 111 108 108 107 105 101 96 112<br />
50 114 112 108 106 105 103 99 95 110<br />
40 118 115 110 107 105 102 98 94 110<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
GREENHECK<br />
®<br />
11
20 BISW<br />
Performance Data<br />
Wheel Diameter = 20 in.<br />
Outlet Area = 2.30 ft 2<br />
Tip Speed = 5.24 x RPM<br />
Maximum BHP = (RPM/1035) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 3147<br />
<strong>IV</strong> 3794<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
6700 2913 2620 14.6 2715 16.0 2811 17.5 2909 19.1 3002 20.8 3092 22.4 3179 24.1 3264 25.8<br />
7230 3143 2671 15.9 2766 17.4 2857 18.9 2944 20.4 3034 22.1 3123 23.8 3210 25.5 3295 27.3 3376 29.1 3533 32.7<br />
7760 3373 2726 17.2 2817 18.8 2908 20.4 2994 22.0 3078 23.6 3158 25.2 3242 27.0 3326 28.8 3408 30.7 3564 34.5<br />
8290 3604 2786 18.6 2874 20.3 2959 21.9 3046 23.6 3129 25.3 3209 27.0 3287 28.8 3362 30.5 3439 32.3 3595 36.3<br />
8820 3834 2847 20.2 2935 21.9 3019 23.6 3099 25.3 3180 27.1 3260 28.9 3337 30.7 3412 32.5 3485 34.4 3625 38.1<br />
9350 4065 2911 21.8 2996 23.6 3079 25.4 3160 27.2 3237 29.0 3312 30.8 3389 32.7 3463 34.6 3536 36.6 3675 40.4<br />
9880 4295 2979 23.5 3061 25.4 3141 27.2 3220 29.1 3297 31.0 3372 32.9 3443 34.9 3515 36.8 3587 38.8 3726 42.9<br />
10410 4526 3047 25.4 3128 27.3 3206 29.2 3282 31.2 3358 33.2 3432 35.1 3504 37.2 3573 39.2 3640 41.2<br />
10940 4756 3116 27.4 3196 29.4 3274 31.4 3349 33.4 3421 35.4 3493 37.5 3564 39.5 3633 41.6 3701 43.8<br />
11470 4986 3193 29.5 3266 31.5 3342 33.6 3416 35.7 3488 37.8 3557 39.9 3626 42.1 3694 44.2 3761 46.4<br />
12000 5217 3274 31.8 3343 33.9 3411 36.0 3485 38.2 3555 40.3 3624 42.5 3691 44.7 3756 46.9<br />
12530 5447 3356 34.2 3423 36.4 3488 38.5 3554 40.7 3624 43.0 3692 45.3 3758 47.5<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
2200 100 96 95 98 101 96 95 91 81 102<br />
80 95 94 96 99 92 90 85 78 99<br />
60 94 92 94 97 91 88 85 81 97<br />
50 95 93 95 97 91 89 85 82 97<br />
40 98 96 96 95 90 88 86 83 97<br />
3147 100 104 105 105 109 106 104 102 94 111<br />
80 103 104 104 108 103 99 96 90 109<br />
60 102 103 102 105 101 98 94 90 106<br />
50 104 103 103 105 101 98 95 91 107<br />
40 107 107 105 104 100 97 95 92 106<br />
3794 100 107 110 110 112 111 108 106 100 116<br />
80 106 109 109 111 109 104 101 95 113<br />
60 105 108 107 109 106 103 99 96 111<br />
50 107 109 108 109 106 103 100 96 111<br />
40 110 112 111 108 105 102 99 97 111<br />
% WOV = (CFM x 100) / (RPM x 4.74)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
2200 100 106 103 102 105 99 98 95 85 106<br />
80 105 99 99 101 96 93 89 80 102<br />
60 103 95 96 98 94 90 85 80 99<br />
50 103 96 95 95 92 89 84 79 97<br />
40 106 98 96 95 91 87 84 80 97<br />
3147 100 114 112 109 113 109 107 105 98 115<br />
80 114 109 105 109 106 103 99 92 111<br />
60 112 106 103 105 103 100 96 90 108<br />
50 112 106 103 103 101 98 94 90 106<br />
40 116 109 105 103 101 97 94 90 106<br />
3794 100 117 117 114 116 114 111 110 104 119<br />
80 117 114 110 112 111 108 104 98 115<br />
60 115 111 108 109 108 105 101 96 112<br />
50 115 112 108 107 106 103 100 95 111<br />
40 119 115 110 107 106 102 99 95 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
12<br />
3147<br />
GREENHECK<br />
®
22 BISW<br />
Performance Data<br />
Wheel Diameter = 22 1/4 in.<br />
Outlet Area = 2.85 ft 2<br />
Tip Speed = 5.83 x RPM<br />
Maximum BHP = (RPM/867) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 2830<br />
<strong>IV</strong> 3413<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
8600 3017 2377 18.8 2463 20.6 2544 22.4 2629 24.4 2713 26.4 2794 28.5 2872 30.6 2948 32.8 3022 35.0<br />
9250 3245 2423 20.4 2508 22.3 2590 24.2 2668 26.2 2743 28.1 2822 30.2 2900 32.4 2976 34.6 3049 36.9 3190 41.5<br />
9900 3473 2475 22.1 2555 24.1 2636 26.1 2713 28.1 2788 30.2 2860 32.2 2930 34.3 3004 36.6 3077 38.9 3218 43.7<br />
10550 3701 2529 23.9 2609 26.0 2684 28.0 2759 30.2 2834 32.3 2906 34.5 2975 36.7 3043 38.9 3109 41.1 3245 45.9<br />
11200 3929 2584 25.8 2663 28.0 2738 30.1 2811 32.3 2880 34.6 2952 36.8 3021 39.1 3088 41.4 3153 43.7 3279 48.4<br />
11850 4157 2643 27.9 2717 30.1 2792 32.4 2864 34.7 2934 37.0 3001 39.3 3067 41.7 3134 44.0 3199 46.5 3324 51.3<br />
12500 4385 2704 30.1 2777 32.4 2848 34.7 2919 37.1 2988 39.5 3054 41.9 3119 44.4 3181 46.8 3245 49.3 3369 54.4<br />
13150 4614 2765 32.4 2838 34.8 2908 37.3 2975 39.7 3042 42.2 3108 44.7 3173 47.2 3235 49.8 3295 52.3<br />
13800 4842 2828 34.9 2899 37.4 2968 39.9 3035 42.5 3100 45.0 3163 47.6 3227 50.2 3289 52.8 3349 55.5<br />
14450 5070 2900 37.6 2962 40.2 3029 42.8 3096 45.4 3160 48.0 3222 50.7 3282 53.3 3343 56.0<br />
15100 5298 2972 40.5 3033 43.1 3092 45.7 3157 48.5 3220 51.2 3282 53.9 3342 56.7<br />
15750 5526 3045 43.5 3105 46.2 3164 49.0 3220 51.7 3282 54.5 3343 57.3<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
2000 100 97 97 100 101 97 96 91 81 103<br />
80 96 95 99 100 93 91 85 78 100<br />
60 95 94 96 97 92 89 85 81 98<br />
50 96 95 97 97 92 89 86 83 98<br />
40 99 97 97 96 91 89 86 83 97<br />
2830 100 106 106 106 110 106 105 102 93 112<br />
80 105 105 104 110 103 100 96 90 109<br />
60 104 103 103 107 101 98 95 91 107<br />
50 106 104 104 107 101 98 95 92 107<br />
40 109 107 106 105 100 98 95 92 107<br />
3413 100 109 111 111 114 111 109 107 100 116<br />
80 108 110 109 113 109 105 101 95 114<br />
60 108 109 108 110 107 103 100 96 112<br />
50 109 110 109 110 106 103 100 97 112<br />
40 112 113 111 109 105 102 100 97 111<br />
% WOV = (CFM x 100) / (RPM x 6.52)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
2000 100 107 104 104 105 100 99 95 85 106<br />
80 105 99 101 102 97 94 89 80 103<br />
60 102 97 98 98 94 91 86 80 99<br />
50 103 97 96 96 93 89 85 80 98<br />
40 106 99 97 96 92 88 84 80 98<br />
2830 100 115 112 110 114 109 107 106 97 115<br />
80 115 109 106 111 106 103 100 92 112<br />
60 113 105 104 107 104 100 96 90 108<br />
50 113 106 104 104 102 99 95 90 107<br />
40 117 109 105 105 101 98 94 90 107<br />
3413 100 119 117 115 117 114 112 110 104 120<br />
80 118 114 111 114 112 108 105 98 116<br />
60 116 111 109 110 108 105 101 96 113<br />
50 116 112 109 108 107 104 100 95 111<br />
40 120 115 110 108 106 103 99 95 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
2830<br />
GREENHECK<br />
®<br />
13
24 BISW<br />
Performance Data<br />
Wheel Diameter = 24 1/2 in.<br />
Outlet Area = 3.45 ft 2<br />
Tip Speed = 6.41 x RPM<br />
Maximum BHP = (RPM/750) 3<br />
Pressure <strong>Class</strong> Limits 2580<br />
<strong>Class</strong> Max. RPM<br />
III 2580<br />
<strong>IV</strong> 3110<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
12050 3492 2256 26.5 2332 29.0 2404 31.5 2477 34.1 2548 36.6 2617 39.2 2683 41.8 2747 44.5 2810 47.2<br />
12850 3724 2305 28.6 2376 31.1 2449 33.8 2518 36.4 2585 39.1 2654 41.8 2720 44.6 2784 47.3 2846 50.1 2966 55.7<br />
13650 3956 2357 30.8 2427 33.5 2493 36.1 2563 38.9 2629 41.7 2694 44.6 2756 47.4 2821 50.3 2883 53.2 3002 59.0<br />
14450 4188 2410 33.2 2479 35.9 2546 38.7 2609 41.5 2674 44.4 2738 47.4 2800 50.3 2861 53.4 2919 56.4 3039 62.5<br />
15250 4420 2466 35.8 2532 38.6 2598 41.5 2662 44.4 2723 47.3 2783 50.3 2845 53.4 2905 56.5 2963 59.7 3075 66.0<br />
16050 4652 2528 38.5 2589 41.4 2651 44.4 2715 47.4 2776 50.5 2835 53.5 2891 56.6 2949 59.8 3007 63.1<br />
16850 4884 2590 41.4 2651 44.4 2709 47.5 2768 50.6 2828 53.7 2887 56.9 2944 60.1 2998 63.4 3052 66.6<br />
17650 5115 2653 44.5 2713 47.6 2771 50.8 2827 54.0 2881 57.2 2940 60.5 2996 63.8 3051 67.1<br />
18450 5347 2718 47.8 2775 51.0 2832 54.3 2888 57.6 2942 60.9 2994 64.2 3049 67.7<br />
19250 5579 2787 51.5 2840 54.6 2895 58.0 2950 61.4 3003 64.8 3055 68.2<br />
20050 5811 2857 55.3 2909 58.6 2960 61.9 3013 65.4 3065 68.9<br />
20850 6043 2928 59.4 2979 62.8 3028 66.2 3077 69.6<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
14<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1800 100 98 95 104 97 94 96 92 82 102<br />
80 94 91 102 93 89 89 85 78 97<br />
60 94 87 97 89 87 86 84 80 94<br />
50 95 88 98 87 86 85 84 82 94<br />
40 98 93 100 89 86 86 85 82 95<br />
2580 100 105 106 109 110 103 103 102 95 111<br />
80 101 102 106 106 99 97 95 90 107<br />
60 101 100 101 102 96 94 93 90 103<br />
50 102 101 102 102 94 93 93 91 103<br />
40 105 105 106 104 96 94 93 91 104<br />
3110 100 108 111 113 113 109 107 106 101 115<br />
80 104 107 109 110 105 102 99 95 111<br />
60 104 105 105 105 101 99 97 95 107<br />
50 105 106 107 105 100 98 97 95 107<br />
40 108 110 110 107 102 98 97 96 109<br />
% WOV = (CFM x 100) / (RPM x 8.84)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1800 100 108 105 107 100 99 99 95 86 105<br />
80 103 102 104 97 96 94 90 82 101<br />
60 101 99 101 94 93 89 85 81 99<br />
50 101 99 99 93 91 87 84 81 97<br />
40 101 99 98 92 90 86 84 82 96<br />
2580 100 114 114 114 112 107 107 105 99 114<br />
80 109 110 110 109 104 103 100 94 111<br />
60 107 108 108 106 102 99 95 91 108<br />
50 108 108 106 104 100 97 94 91 106<br />
40 108 108 106 103 99 96 93 91 105<br />
3110 100 118 118 118 115 112 111 109 104 118<br />
80 113 114 114 112 109 107 105 100 115<br />
60 111 112 112 109 107 104 100 96 112<br />
50 111 112 111 107 105 102 99 96 110<br />
40 111 112 111 107 104 101 98 95 110<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
GREENHECK<br />
®
27 BISW<br />
Performance Data<br />
Wheel Diameter = 27 in.<br />
Outlet Area = 4.19 ft 2<br />
Tip Speed = 7.07 x RPM<br />
Maximum BHP = (RPM/638) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 2342<br />
<strong>IV</strong> 2823<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
14650 3496 2048 32.2 2117 35.3 2183 38.4 2249 41.5 2314 44.6 2376 47.7 2436 50.9 2494 54.1 2551 57.3<br />
15450 3687 2084 34.3 2150 37.4 2216 40.6 2279 43.8 2342 47.1 2404 50.3 2464 53.6 2522 56.9 2578 60.3 2686 67.1<br />
16250 3878 2123 36.5 2186 39.7 2250 42.9 2312 46.2 2373 49.6 2432 53.0 2492 56.4 2550 59.9 2606 63.3 2714 70.4<br />
17050 4069 2163 38.8 2226 42.1 2286 45.4 2346 48.8 2406 52.3 2465 55.8 2521 59.3 2576 62.9 2634 66.5 2741 73.7<br />
17850 4260 2202 41.3 2265 44.7 2326 48.1 2384 51.5 2440 55.0 2498 58.6 2554 62.3 2609 66.0 2662 69.7 2769 77.2<br />
18650 4451 2246 43.9 2305 47.3 2365 50.9 2423 54.4 2478 58.0 2532 61.6 2587 65.4 2642 69.2 2695 73.0 2796 80.8<br />
19450 4642 2292 46.6 2348 50.2 2405 53.8 2462 57.4 2517 61.1 2571 64.9 2622 68.6 2675 72.5 2728 76.4<br />
20250 4832 2338 49.5 2394 53.2 2447 56.9 2502 60.6 2557 64.4 2610 68.2 2662 72.1 2711 76.0 2761 80.0<br />
21050 5023 2385 52.5 2440 56.3 2493 60.1 2544 63.9 2596 67.8 2649 71.8 2701 75.7 2751 79.7<br />
21850 5214 2432 55.7 2486 59.6 2539 63.5 2589 67.4 2639 71.4 2689 75.4 2740 79.5 2789 83.6<br />
22650 5405 2483 59.2 2533 63.0 2585 67.0 2635 71.1 2684 75.2 2731 79.3 2779 83.4<br />
23450 5596 2534 62.8 2582 66.7 2632 70.8 2682 74.9 2730 79.1 2777 83.3<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1700 100 100 98 106 99 96 97 92 83 103<br />
80 96 94 104 94 91 90 86 79 99<br />
60 95 90 99 90 88 87 85 82 96<br />
50 96 91 100 89 87 87 86 83 96<br />
40 99 96 102 91 88 87 86 84 97<br />
2342 100 107 106 111 109 104 104 102 94 111<br />
80 103 102 108 106 99 98 95 89 107<br />
60 103 100 103 101 96 95 93 90 103<br />
50 104 101 104 101 95 94 93 91 103<br />
40 107 105 107 103 96 95 94 92 105<br />
2823 100 110 112 114 115 109 108 107 100 116<br />
80 106 108 111 112 105 102 100 95 112<br />
60 107 106 107 108 101 99 98 95 109<br />
50 107 107 108 108 100 98 98 96 108<br />
40 110 111 111 110 102 99 98 96 111<br />
% WOV = (CFM x 100) / (RPM x 11.8)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1700 100 109 107 109 101 100 100 96 87 107<br />
80 104 104 105 98 97 95 91 83 103<br />
60 102 101 103 96 95 91 86 83 100<br />
50 103 100 101 94 92 89 86 83 98<br />
40 103 100 100 93 91 88 86 83 97<br />
2342 100 116 114 115 111 108 107 105 98 115<br />
80 111 111 111 108 105 103 100 94 111<br />
60 109 108 109 106 102 99 95 91 108<br />
50 109 108 107 104 100 97 94 91 106<br />
40 109 108 107 103 99 96 94 91 106<br />
2823 100 119 119 119 118 113 112 110 104 120<br />
80 114 115 115 115 110 108 105 100 116<br />
60 112 112 113 112 107 104 100 96 114<br />
50 113 113 112 111 105 102 99 96 112<br />
40 112 113 111 110 104 101 98 96 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
2342<br />
GREENHECK<br />
®<br />
15
30 BISW<br />
Performance Data<br />
Wheel Diameter = 30 in.<br />
Outlet Area = 5.17 ft 2<br />
Tip Speed = 7.85 x RPM<br />
Maximum BHP = (RPM/528) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 2102<br />
<strong>IV</strong> 2532<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
15050 2911 1755 32.5 1822 35.8 1892 39.4 1960 43.1 2026 46.9 2089 50.7 2150 54.5 2209 58.5<br />
16400 3172 1788 35.5 1855 39.0 1918 42.5 1979 46.1 2044 49.9 2107 53.9 2168 58.0 2227 62.1 2284 66.2 2394 74.7<br />
17750 3433 1822 38.6 1888 42.3 1951 46.0 2012 49.8 2071 53.6 2127 57.4 2186 61.5 2245 65.8 2302 70.1 2412 78.9<br />
19100 3694 1861 42.0 1922 45.7 1985 49.7 2046 53.6 2104 57.6 2160 61.7 2215 65.8 2268 69.9 2319 74.1 2430 83.3<br />
20450 3955 1907 45.8 1965 49.7 2021 53.6 2079 57.7 2137 61.9 2193 66.1 2248 70.4 2300 74.7 2351 79.1 2450 87.9<br />
21800 4216 1952 49.8 2011 53.9 2066 58.0 2119 62.1 2171 66.3 2227 70.8 2281 75.3 2334 79.8 2384 84.3 2482 93.5<br />
23150 4477 2003 54.2 2057 58.4 2111 62.7 2165 67.0 2215 71.4 2265 75.8 2315 80.3 2367 85.0 2418 89.8<br />
24500 4738 2054 58.8 2108 63.2 2159 67.7 2210 72.2 2261 76.8 2310 81.4 2357 86.0 2404 90.7 2451 95.5<br />
25850 5000 2107 63.8 2159 68.4 2210 73.0 2259 77.7 2306 82.4 2356 87.2 2403 92.0 2448 96.9 2493 102<br />
27200 5261 2161 69.0 2212 73.9 2261 78.7 2310 83.5 2357 88.4 2402 93.4 2448 98.4 2494 103<br />
28550 5522 2220 74.7 2266 79.7 2314 84.7 2362 89.8 2408 94.8 2453 100 2497 105<br />
29900 5783 2279 80.6 2325 85.8 2369 91.0 2414 96.3 2460 102 2504 107<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1500 100 99 100 105 98 97 97 91 81 103<br />
80 95 97 103 94 91 90 85 79 99<br />
60 94 93 98 90 89 87 85 82 95<br />
50 95 94 99 89 88 87 86 83 95<br />
40 99 98 101 91 88 88 86 84 97<br />
2102 100 109 107 113 108 104 105 102 94 112<br />
80 105 102 110 105 99 99 95 89 107<br />
60 105 99 106 100 97 96 94 91 104<br />
50 106 100 107 99 95 95 94 92 104<br />
40 109 105 109 101 96 95 95 92 105<br />
2532 100 112 112 115 115 109 109 107 100 117<br />
80 108 108 113 112 105 103 100 95 112<br />
60 108 106 108 107 102 100 98 95 109<br />
50 109 107 109 107 100 99 98 96 108<br />
40 112 111 112 109 102 100 99 97 110<br />
% WOV = (CFM x 100) / (RPM x 16.7)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1500 100 109 108 108 102 101 100 95 86 107<br />
80 105 104 105 99 97 95 90 82 103<br />
60 102 102 103 96 94 90 86 82 100<br />
50 103 101 100 94 92 89 86 83 98<br />
40 103 101 100 93 91 88 86 83 97<br />
2102 100 117 115 116 111 108 108 106 97 115<br />
80 112 111 113 108 106 104 100 94 111<br />
60 110 109 110 105 103 100 95 92 109<br />
50 111 109 108 104 101 98 95 92 107<br />
40 111 109 108 102 100 96 94 92 106<br />
2532 100 120 119 120 117 113 112 111 104 120<br />
80 115 115 116 114 110 108 105 99 116<br />
60 113 113 114 112 108 105 101 97 114<br />
50 114 113 112 110 106 103 99 96 112<br />
40 114 113 112 109 105 101 99 96 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
16<br />
2102<br />
GREENHECK<br />
®
33 BISW<br />
Performance Data<br />
Wheel Diameter = 33 in.<br />
Outlet Area = 6.26 ft 2<br />
Tip Speed = 8.64 x RPM<br />
Maximum BHP = (RPM/451) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1911<br />
<strong>IV</strong> 2302<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18 20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
17400 2779 1580 37.7 1648 41.8 1712 46.1 1774 50.5 1833 54.9 1891 59.4 1946 64.0<br />
19100 3051 1612 41.3 1672 45.4 1731 49.6 1791 54.1 1851 58.7 1908 63.4 1963 68.2 2017 73.1 2069 78.1<br />
20800 3322 1643 45.1 1704 49.5 1762 53.9 1817 58.3 1870 62.9 1925 67.6 1981 72.6 2034 77.7 2086 82.9 2186 93.4<br />
22500 3594 1676 49.2 1736 53.8 1793 58.4 1848 63.1 1902 67.9 1953 72.7 2003 77.6 2051 82.5 2104 87.9 2203 98.8<br />
24200 3865 1720 53.8 1772 58.5 1825 63.2 1880 68.1 1933 73.1 1984 78.2 2034 83.3 2081 88.4 2128 93.7 2220 104<br />
25900 4137 1763 58.8 1816 63.7 1867 68.6 1914 73.6 1965 78.7 2016 84.0 2065 89.3 2113 94.7 2159 100 2248 111<br />
27600 4408 1809 64.2 1859 69.3 1909 74.4 1958 79.6 2004 84.8 2049 90.1 2097 95.6 2144 101 2190 107 2279 118<br />
29300 4680 1858 70.0 1907 75.3 1953 80.6 2001 86.1 2047 91.5 2092 97.0 2134 103 2177 108 2222 114<br />
31000 4952 1907 76.1 1955 81.7 2001 87.3 2046 92.9 2090 98.6 2135 104 2178 110 2219 116 2259 122<br />
32700 5223 1959 82.7 2005 88.5 2050 94.3 2094 100 2137 106 2178 112 2221 118 2262 124<br />
34400 5495 2013 89.7 2056 95.8 2100 102 2143 108 2185 114 2226 120 2266 127<br />
36100 5766 2069 97.2 2111 104 2151 110 2192 116 2234 123 2275 129<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1400 100 100 103 106 100 98 98 92 82 104<br />
80 96 99 103 95 93 91 86 79 99<br />
60 95 95 99 92 90 89 86 83 96<br />
50 96 96 99 90 89 88 87 84 96<br />
40 100 100 101 92 90 89 87 85 97<br />
1911 100 110 107 115 108 104 106 103 93 112<br />
80 107 102 112 104 100 99 96 89 108<br />
60 107 98 108 99 97 96 94 91 104<br />
50 108 100 109 98 96 95 95 92 104<br />
40 110 105 110 100 97 96 95 93 106<br />
2302 100 114 113 117 115 109 110 108 100 117<br />
80 110 109 114 111 105 103 101 95 112<br />
60 110 106 110 107 102 101 99 96 109<br />
50 111 107 111 106 101 100 99 97 109<br />
40 113 111 113 108 102 100 100 98 110<br />
% WOV = (CFM x 100) / (RPM x 22.2)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1400 100 110 109 109 103 102 101 95 86 108<br />
80 106 106 105 100 99 96 91 83 104<br />
60 104 104 103 98 95 91 87 83 101<br />
50 104 102 101 96 93 90 87 84 99<br />
40 104 102 100 95 92 89 87 84 98<br />
1911 100 118 115 117 110 109 109 106 97 116<br />
80 113 112 114 107 106 104 101 93 112<br />
60 111 109 111 105 104 100 96 92 109<br />
50 112 109 109 103 102 98 95 92 107<br />
40 112 109 109 102 101 97 95 92 106<br />
2302 100 121 120 121 117 113 113 111 104 120<br />
80 116 116 117 114 111 109 106 99 117<br />
60 114 114 115 111 108 105 101 97 114<br />
50 115 114 113 110 106 103 100 97 112<br />
40 115 114 113 109 105 102 99 97 111<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
1911<br />
GREENHECK<br />
®<br />
17
36 BISW<br />
Performance Data<br />
Wheel Diameter = 36 1/2 in.<br />
Outlet Area = 7.66 ft 2<br />
Tip Speed = 9.56 x RPM<br />
Maximum BHP = (RPM/381) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1727<br />
<strong>IV</strong> 2082<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
21700 2832 1435 47.0 1493 52.0 1551 57.2 1607 62.6 1661 68.1 1713 73.7 1763 79.3<br />
23700 3093 1462 51.3 1517 56.3 1569 61.5 1622 66.9 1676 72.6 1728 78.5 1778 84.4 1826 90.4 1874 96.5<br />
25700 3355 1489 55.8 1544 61.1 1596 66.6 1646 72.1 1695 77.7 1741 83.3 1793 89.6 1841 95.8 1888 102 1978 115<br />
27700 3616 1519 60.6 1572 66.2 1624 71.9 1674 77.7 1722 83.6 1768 89.5 1813 95.5 1857 102 1903 108 1993 122<br />
29700 3877 1557 66.1 1604 71.8 1651 77.6 1701 83.7 1749 89.8 1795 96.0 1840 102 1883 109 1925 115 2006 128<br />
31700 4138 1594 72.0 1642 78.0 1688 84.0 1731 90.0 1777 96.3 1823 103 1867 109 1910 116 1952 123 2033 136<br />
33700 4399 1635 78.3 1680 84.5 1725 90.8 1769 97.2 1810 104 1851 110 1895 117 1938 124 1980 131 2060 145<br />
35700 4660 1677 85.1 1721 91.5 1763 98.1 1806 105 1848 111 1888 118 1927 125 1965 132 2007 139<br />
37700 4921 1720 92.3 1763 99.1 1805 106 1845 113 1886 120 1926 127 1965 134 2002 141 2039 148<br />
39700 5182 1764 100 1806 107 1847 114 1887 121 1926 128 1963 136 2002 143 2040 150<br />
41700 5443 1811 108 1850 116 1890 123 1929 130 1968 138 2005 145 2041 153<br />
43700 5704 1860 117 1898 124 1934 132 1972 140 2010 148 2047 155<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1200 100 102 108 104 97 95 94 87 81 102<br />
80 97 106 100 93 91 88 83 78 98<br />
60 95 103 97 89 88 86 83 81 95<br />
50 97 103 97 88 87 85 84 81 95<br />
40 106 107 101 92 89 86 85 82 97<br />
1727 100 109 115 119 108 103 102 99 92 113<br />
80 103 111 117 104 99 98 94 88 110<br />
60 101 108 113 101 96 95 93 90 107<br />
50 103 109 114 100 95 94 92 91 107<br />
40 112 116 117 104 98 95 93 91 110<br />
2082 100 112 118 122 116 109 107 104 98 118<br />
80 107 114 119 112 105 102 99 94 114<br />
60 104 111 116 108 101 99 97 95 111<br />
50 106 113 117 108 101 98 97 95 111<br />
40 115 120 121 112 103 100 98 96 115<br />
% WOV = (CFM x 100) / (RPM x 30.1)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1200 100 111 112 107 102 99 97 92 85 106<br />
80 108 109 103 98 94 91 86 80 101<br />
60 102 107 101 95 91 88 84 80 99<br />
50 103 106 100 94 90 87 84 80 98<br />
40 104 105 99 93 89 85 83 80 97<br />
1727 100 117 120 121 112 108 106 103 97 116<br />
80 114 116 118 108 104 101 97 91 113<br />
60 109 112 117 105 101 97 94 90 110<br />
50 110 113 115 104 100 96 93 90 109<br />
40 111 113 114 103 99 95 92 90 108<br />
2082 100 120 123 125 119 113 110 108 102 121<br />
80 117 120 122 115 109 106 102 97 117<br />
60 112 115 120 112 106 102 99 95 115<br />
50 113 116 119 111 105 101 98 95 114<br />
40 114 116 118 111 104 100 97 95 113<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
18<br />
1727<br />
GREENHECK<br />
®
40 BISW<br />
Performance Data<br />
Wheel Diameter = 40 1/4 in.<br />
Outlet Area = 9.31 ft 2<br />
Tip Speed = 10.54 x RPM<br />
Maximum BHP = (RPM/326) 3<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1538<br />
<strong>IV</strong> 1852<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
31100 3340 1327 63.8 1371 69.4 1412 75.1 1453 80.8 1492 86.6 1537 93.1 1581 99.9 1624 107 1665 114<br />
33100 3555 1355 69.1 1398 74.9 1440 80.9 1479 86.8 1518 92.9 1555 99.0 1591 105 1635 112 1676 119 1755 134<br />
35100 3770 1386 74.8 1426 80.8 1466 86.9 1506 93.2 1544 99.5 1581 106 1617 112 1652 119 1686 125 1766 140<br />
37100 3984 1417 80.8 1457 87.1 1495 93.4 1533 99.9 1571 106 1608 113 1643 120 1678 126 1712 133 1777 147<br />
39100 4199 1449 87.2 1488 93.8 1526 100 1563 107 1598 114 1635 121 1670 128 1704 135 1738 142 1802 156<br />
41100 4414 1482 93.8 1520 101 1558 108 1594 115 1629 122 1663 129 1697 136 1731 143 1765 150 1828 165<br />
43100 4629 1515 101 1553 108 1589 115 1625 123 1660 130 1694 137 1726 144 1758 152 1791 159<br />
45100 4844 1551 108 1586 116 1622 123 1657 131 1691 139 1725 146 1757 154 1789 161 1820 169<br />
47100 5059 1587 116 1622 124 1655 132 1690 140 1724 148 1756 156 1788 163 1820 171<br />
49100 5273 1624 124 1658 132 1691 140 1723 149 1756 157 1789 165 1820 173<br />
51100 5488 1665 133 1695 141 1727 149 1759 158 1789 167 1821 175<br />
53100 5703 1707 143 1735 151 1764 159 1795 168 1825 177<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1100 100 104 110 104 97 96 95 88 81 102<br />
80 99 108 99 93 92 89 83 79 98<br />
60 97 105 96 90 89 87 84 81 96<br />
50 99 105 96 89 88 86 85 82 95<br />
40 108 108 100 92 89 87 85 83 98<br />
1538 100 110 116 118 108 104 102 98 92 113<br />
80 105 112 115 103 100 98 93 88 109<br />
60 102 109 112 100 96 95 93 90 106<br />
50 104 111 112 100 95 94 93 91 106<br />
40 113 117 115 103 98 95 93 91 109<br />
1852 100 113 119 121 115 109 107 103 97 117<br />
80 108 115 119 111 105 102 98 94 114<br />
60 106 112 115 107 101 99 97 95 111<br />
50 108 114 116 107 101 99 97 95 111<br />
40 117 121 120 111 103 100 98 96 114<br />
% WOV = (CFM x 100) / (RPM x 38.0)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1100 100 112 114 106 103 99 98 93 85 106<br />
80 109 110 102 99 95 92 86 81 102<br />
60 104 109 100 96 92 89 85 81 99<br />
50 105 108 99 95 90 87 85 81 98<br />
40 106 107 98 94 89 86 84 81 97<br />
1538 100 118 120 120 112 108 106 102 96 116<br />
80 115 117 117 108 104 101 96 91 112<br />
60 110 114 115 105 101 97 94 90 110<br />
50 111 114 114 104 100 96 93 90 109<br />
40 112 114 113 103 99 95 92 90 108<br />
1852 100 121 124 124 118 113 111 107 102 121<br />
80 118 121 121 114 109 106 102 96 117<br />
60 113 117 119 112 106 102 99 95 114<br />
50 114 117 118 111 105 101 98 95 113<br />
40 115 117 117 110 104 100 97 95 112<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
GREENHECK<br />
®<br />
19
44 BISW<br />
Performance Data<br />
Wheel Diameter = 44 1/2 in.<br />
Outlet Area = 11.39 ft 2<br />
Tip Speed = 11.65 x RPM<br />
Maximum BHP = (RPM/276) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1392<br />
<strong>IV</strong> 1675<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
37700 3309 1198 77.3 1236 84.1 1274 90.9 1311 97.9 1346 105 1389 113 1429 121 1468 130 1505 138<br />
39900 3503 1219 82.9 1259 90.0 1297 97.2 1332 105 1367 112 1401 119 1438 127 1477 136 1514 144 1586 162<br />
42100 3696 1244 89.1 1281 96.3 1318 104 1355 111 1389 119 1422 127 1455 134 1487 142 1523 151 1595 169<br />
44300 3889 1270 95.6 1306 103 1341 111 1376 119 1411 126 1444 134 1476 142 1508 150 1538 159 1603 176<br />
46500 4082 1295 102 1331 110 1366 118 1399 126 1433 134 1466 142 1497 151 1529 159 1559 168 1618 184<br />
48700 4275 1322 110 1357 118 1391 126 1424 134 1456 143 1488 151 1520 160 1551 168 1580 177 1639 194<br />
50900 4468 1348 117 1383 126 1417 134 1449 143 1481 151 1512 160 1542 169 1573 178 1603 187<br />
53100 4661 1376 125 1410 134 1443 143 1475 152 1507 161 1537 169 1567 178 1595 188 1624 197<br />
55300 4855 1405 133 1437 142 1470 152 1501 161 1532 170 1562 179 1592 189 1620 198 1648 207<br />
57500 5048 1435 141 1466 151 1496 161 1528 170 1558 180 1588 190 1617 199 1645 209<br />
59700 5241 1465 150 1496 160 1525 170 1555 180 1585 190 1614 200 1643 210<br />
61900 5434 1498 160 1525 170 1555 180 1584 191 1612 201 1641 211<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
1000 100 106 111 104 98 96 95 88 82 103<br />
80 101 109 99 94 92 89 83 79 99<br />
60 99 106 96 90 90 87 85 82 96<br />
50 101 107 96 89 89 87 85 83 96<br />
40 109 109 100 92 90 88 86 83 99<br />
1392 100 112 117 117 108 104 103 98 92 112<br />
80 107 114 114 103 100 98 93 88 109<br />
60 104 111 110 100 97 96 93 90 106<br />
50 106 112 111 99 96 95 93 91 106<br />
40 115 117 114 103 98 96 94 92 109<br />
1675 100 115 121 120 114 109 107 104 97 117<br />
80 110 117 117 110 105 103 99 94 113<br />
60 107 114 114 107 102 100 98 95 110<br />
50 110 116 114 106 101 99 98 96 110<br />
40 118 121 117 110 103 101 99 96 113<br />
% WOV = (CFM x 100) / (RPM x 51.4)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
1000 100 113 115 107 103 100 98 92 85 107<br />
80 110 112 102 99 96 92 87 81 102<br />
60 105 110 100 96 92 89 85 81 100<br />
50 106 109 99 95 91 88 85 82 99<br />
40 107 108 98 94 90 87 85 82 98<br />
1392 100 119 121 119 112 109 107 102 96 116<br />
80 116 118 115 108 104 101 96 91 112<br />
60 111 115 114 105 101 98 94 90 109<br />
50 112 115 113 104 100 96 94 90 108<br />
40 113 115 112 103 99 95 93 90 107<br />
1675 100 123 125 123 118 114 111 108 102 121<br />
80 119 122 119 114 109 106 102 96 116<br />
60 114 118 117 111 106 103 99 95 114<br />
50 115 118 116 111 105 101 98 95 113<br />
40 116 118 115 110 104 100 98 95 112<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
20<br />
1392<br />
GREENHECK<br />
®
49 BISW<br />
Performance Data<br />
Wheel Diameter = 49 in.<br />
Outlet Area = 13.80 ft 2<br />
Tip Speed = 12.83 x RPM<br />
Maximum BHP = (RPM/235) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1264<br />
<strong>IV</strong> 1521<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
45000 3260 1083 91.9 1118 100 1153 108 1186 117 1222 126 1260 135 1296 145 1331 155<br />
48000 3478 1105 99.6 1141 108 1174 117 1207 126 1239 134 1270 143 1305 153 1340 163 1374 174<br />
51000 3695 1130 108 1163 117 1197 126 1230 135 1261 144 1292 153 1321 163 1350 172 1383 183 1448 205<br />
54000 3913 1156 117 1189 126 1220 135 1252 145 1284 154 1313 164 1343 174 1371 184 1399 193 1457 214<br />
57000 4130 1182 126 1215 136 1246 145 1276 155 1306 165 1336 175 1366 185 1393 195 1421 206 1474 226<br />
60000 4347 1209 136 1241 146 1272 156 1302 166 1331 177 1359 187 1387 197 1416 208 1442 219 1495 240<br />
63000 4565 1236 146 1268 157 1298 168 1328 178 1356 189 1384 200 1411 210 1438 221 1465 232<br />
66000 4782 1266 157 1295 168 1325 179 1354 191 1382 202 1410 213 1437 224 1463 235 1488 246<br />
69000 5000 1296 168 1324 180 1353 192 1381 203 1409 215 1436 227 1463 238 1488 250<br />
72000 5217 1326 180 1354 193 1382 205 1409 217 1436 229 1463 241 1489 253<br />
75000 5434 1360 194 1385 206 1412 218 1438 231 1463 244 1490 256<br />
78000 5652 1394 208 1417 220 1442 232 1468 245 1493 259<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
900 100 108 113 103 98 97 94 87 81 103<br />
80 104 111 99 94 93 89 83 79 100<br />
60 101 107 96 91 90 88 85 82 97<br />
50 102 108 95 90 89 87 85 83 97<br />
40 110 111 99 93 90 88 86 83 99<br />
1264 100 114 119 116 108 105 104 98 92 112<br />
80 109 116 112 103 101 99 93 89 108<br />
60 106 113 109 100 98 96 94 91 106<br />
50 108 114 109 99 97 95 94 91 105<br />
40 117 118 112 102 99 96 95 92 108<br />
1521 100 117 122 119 114 110 108 104 97 117<br />
80 112 119 115 110 106 103 99 94 113<br />
60 109 116 112 106 102 101 98 96 110<br />
50 111 117 112 106 102 100 98 96 110<br />
40 120 122 116 109 104 101 99 97 113<br />
% WOV = (CFM x 100) / (RPM x 68.6)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
900 100 114 116 107 104 100 98 92 85 107<br />
80 111 113 103 99 96 92 86 81 103<br />
60 107 111 100 96 92 89 85 81 100<br />
50 107 110 99 95 91 88 85 82 99<br />
40 108 109 98 94 90 87 85 82 98<br />
1264 100 121 122 118 113 109 107 103 96 116<br />
80 118 119 114 108 105 102 96 91 112<br />
60 112 117 112 105 101 98 94 91 109<br />
50 113 116 111 104 100 97 94 91 108<br />
40 114 115 110 104 99 96 94 91 107<br />
1521 100 124 126 121 118 114 112 108 102 121<br />
80 121 123 117 114 110 107 102 96 116<br />
60 115 120 115 111 106 103 99 96 113<br />
50 116 119 114 110 105 102 99 96 113<br />
40 117 119 113 109 104 101 98 96 112<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
1264<br />
GREENHECK<br />
®<br />
21
54 BISW<br />
Performance Data<br />
Wheel Diameter = 54 1/4 in.<br />
Outlet Area = 16.92 ft 2<br />
Tip Speed = 14.20 x RPM<br />
Maximum BHP = (RPM/198) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1142<br />
<strong>IV</strong> 1375<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
56300 3327 984 116 1017 126 1047 136 1077 146 1106 157 1141 169 1173 181 1205 194 1236 206<br />
59800 3534 1004 125 1036 135 1067 146 1096 157 1125 168 1152 179 1179 190 1213 203 1243 216 1302 242<br />
63300 3741 1026 135 1056 145 1086 157 1116 168 1143 179 1171 191 1198 202 1224 214 1251 226 1310 253<br />
66800 3947 1048 145 1078 156 1106 168 1135 180 1163 191 1190 203 1216 215 1242 227 1267 240 1316 264<br />
70300 4154 1071 156 1100 168 1128 180 1155 192 1182 204 1209 216 1236 229 1261 241 1286 254 1334 280<br />
73800 4361 1094 168 1123 180 1151 193 1178 205 1204 218 1229 230 1255 243 1280 256 1304 269 1352 296<br />
77300 4568 1118 180 1146 193 1173 206 1200 219 1226 232 1251 245 1275 258 1299 271 1324 285<br />
80800 4775 1143 192 1170 206 1197 220 1223 233 1248 247 1273 260 1297 274 1321 288 1344 302<br />
84300 4982 1169 205 1195 220 1220 234 1246 248 1271 263 1296 277 1319 291 1343 305<br />
87800 5189 1195 219 1220 234 1245 249 1270 264 1294 279 1318 293 1342 308<br />
91300 5395 1223 235 1247 249 1271 265 1294 280 1318 296 1342 311<br />
94800 5602 1252 251 1274 265 1297 281 1320 297 1343 313<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
22<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
800 100 109 113 103 99 97 94 87 81 103<br />
80 106 111 99 95 93 89 83 79 100<br />
60 103 107 95 91 90 88 85 82 97<br />
50 104 108 95 90 89 88 86 83 97<br />
40 110 111 98 93 90 88 86 83 99<br />
1142 100 116 120 115 108 106 105 98 92 113<br />
80 111 118 110 103 102 99 93 89 109<br />
60 108 115 107 100 99 97 94 91 106<br />
50 110 115 107 99 98 96 95 92 106<br />
40 119 119 111 102 99 97 95 93 108<br />
1375 100 119 124 122 113 110 109 104 97 118<br />
80 114 121 119 109 106 104 99 94 114<br />
60 111 118 116 106 103 101 99 96 111<br />
50 114 119 116 105 102 101 99 97 111<br />
40 122 123 120 109 104 102 100 97 115<br />
% WOV = (CFM x 100) / (RPM x 93.0)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
800 100 115 116 107 103 101 98 91 84 107<br />
80 112 113 103 99 96 92 86 80 103<br />
60 108 111 100 96 92 89 85 81 100<br />
50 108 110 99 95 91 88 85 82 99<br />
40 108 109 98 94 90 87 85 82 98<br />
1142 100 122 123 117 113 109 108 103 95 116<br />
80 119 120 113 109 105 102 97 91 112<br />
60 113 119 110 106 102 99 95 91 109<br />
50 114 117 110 105 100 97 95 91 108<br />
40 116 116 109 104 99 96 94 91 107<br />
1375 100 125 127 125 118 114 112 108 101 122<br />
80 122 124 121 114 110 107 102 96 117<br />
60 117 121 119 111 107 103 100 96 115<br />
50 118 121 118 110 105 102 99 96 114<br />
40 119 120 117 109 105 101 99 96 113<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
1142<br />
GREENHECK<br />
®
60 BISW<br />
Performance Data<br />
Wheel Diameter = 60 in.<br />
Outlet Area = 20.70 ft 2<br />
Tip Speed = 15.71 x RPM<br />
Maximum BHP = (RPM/168) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1032<br />
<strong>IV</strong> 1243<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
72100 3483 903 150 932 163 960 176 987 189 1013 202 1038 215 1066 230 1095 246 1123 261<br />
76500 3695 923 162 950 175 978 189 1005 202 1030 216 1055 230 1079 244 1103 258 1130 274 1183 307<br />
80900 3908 944 175 971 189 997 203 1023 217 1048 231 1072 246 1096 260 1120 275 1143 290 1190 321<br />
85300 4120 965 189 991 203 1017 218 1042 232 1066 247 1091 262 1115 277 1137 293 1160 308 1203 339<br />
89700 4333 986 203 1012 218 1038 233 1062 249 1086 264 1109 279 1132 295 1156 311 1177 327 1220 359<br />
94100 4545 1008 218 1034 234 1059 250 1083 266 1106 282 1129 298 1151 314 1173 330 1196 347<br />
98500 4758 1031 234 1056 251 1080 267 1104 284 1127 301 1150 317 1172 334 1193 350 1213 367<br />
102900 4971 1056 250 1079 268 1102 286 1126 303 1148 320 1170 337 1192 355 1213 372<br />
107300 5183 1080 268 1103 286 1125 304 1147 322 1170 340 1192 359 1213 377<br />
111700 5396 1106 287 1127 305 1149 324 1170 343 1192 362 1213 380<br />
116100 5608 1133 308 1153 325 1173 344 1194 364 1215 384<br />
120500 5821 1161 330 1180 348 1198 366 1218 386<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
750 100 112 113 104 100 99 95 88 82 104<br />
80 108 111 100 96 94 90 85 80 100<br />
60 105 108 96 93 91 89 86 83 98<br />
50 107 108 96 92 91 89 87 84 98<br />
40 112 111 99 94 92 90 88 85 100<br />
1032 100 117 122 114 108 106 105 98 92 113<br />
80 113 120 110 104 102 99 93 89 109<br />
60 110 116 106 100 99 97 95 92 106<br />
50 112 117 106 99 99 97 95 92 106<br />
40 120 120 110 102 100 98 96 93 109<br />
1243 100 121 125 122 114 111 109 104 97 118<br />
80 116 122 118 109 107 104 99 94 114<br />
60 113 119 115 106 104 102 99 97 111<br />
50 115 120 115 105 103 101 100 97 111<br />
40 123 124 118 108 105 102 100 98 114<br />
% WOV = (CFM x 100) / (RPM x 126)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
750 100 117 117 108 105 102 99 92 85 108<br />
80 114 113 104 101 97 93 87 81 104<br />
60 110 111 101 97 94 90 86 83 101<br />
50 110 110 100 96 92 90 86 83 100<br />
40 110 109 99 95 91 89 86 83 99<br />
1032 100 123 125 117 113 110 108 103 95 117<br />
80 120 121 112 109 105 102 97 91 112<br />
60 115 120 110 106 102 99 95 91 110<br />
50 116 119 109 105 101 98 95 92 109<br />
40 117 118 108 104 100 97 95 92 108<br />
1243 100 126 128 124 118 115 113 108 101 122<br />
80 123 125 120 114 110 107 102 96 118<br />
60 118 123 118 111 107 104 100 96 115<br />
50 119 122 117 110 106 103 100 97 114<br />
40 120 121 116 109 105 101 99 96 113<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
GREENHECK<br />
®<br />
23
66 BISW<br />
Performance Data<br />
Wheel Diameter = 66 in.<br />
Outlet Area = 25.05 ft 2<br />
Tip Speed = 17.28 x RPM<br />
Maximum BHP = (RPM/143) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 939<br />
<strong>IV</strong> 1130<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
86900 3469 820 180 847 196 871 212 896 227 920 243 943 259 969 277 995 296 1020 315<br />
91800 3664 837 194 862 210 887 226 912 243 934 259 957 276 979 293 1001 310 1026 329 1075 369<br />
96700 3860 854 208 878 225 902 241 926 259 950 276 972 293 993 311 1015 328 1036 346 1081 385<br />
101600 4055 871 223 896 241 919 258 942 275 965 293 987 311 1008 329 1029 348 1050 366 1089 403<br />
106500 4251 889 239 913 257 936 275 959 293 980 312 1002 330 1024 349 1045 368 1064 387 1104 425<br />
111400 4447 908 256 931 274 954 293 976 312 997 331 1018 350 1038 369 1059 389 1080 408 1118 448<br />
116300 4642 926 273 949 292 972 312 993 332 1015 351 1035 371 1055 391 1075 411 1095 431<br />
121200 4838 946 291 967 311 990 332 1011 352 1032 373 1052 393 1072 413 1092 434 1110 455<br />
126100 5033 966 309 987 331 1008 352 1029 373 1050 395 1070 416 1090 437 1109 458<br />
131000 5229 987 329 1008 351 1028 373 1048 396 1068 418 1088 440 1107 462<br />
135900 5425 1009 351 1028 373 1048 395 1067 418 1086 441 1106 464<br />
140800 5620 1032 374 1049 396 1068 418 1087 442 1106 466<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
24<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
700 100 114 114 105 101 100 95 89 83 105<br />
80 111 111 100 97 95 90 86 81 101<br />
60 107 107 97 94 93 90 87 85 99<br />
50 109 108 96 93 92 90 88 85 99<br />
40 113 111 100 95 93 91 89 86 101<br />
939 100 119 123 114 108 107 105 98 92 113<br />
80 115 121 110 104 103 99 94 89 110<br />
60 112 118 106 101 100 98 95 92 107<br />
50 114 118 106 100 99 97 96 93 107<br />
40 121 121 110 103 100 98 96 93 109<br />
1130 100 122 126 121 114 111 109 104 97 118<br />
80 118 124 118 110 107 104 99 95 115<br />
60 115 121 114 106 104 102 100 97 112<br />
50 117 121 114 106 103 102 100 98 112<br />
40 124 125 118 109 105 103 101 98 115<br />
% WOV = (CFM x 100) / (RPM x 168)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
700 100 118 117 109 106 104 100 93 86 109<br />
80 115 113 105 102 98 94 88 82 105<br />
60 112 111 102 98 95 91 87 84 102<br />
50 112 110 101 97 93 91 88 84 101<br />
40 112 109 100 96 92 90 87 84 100<br />
939 100 124 126 117 114 111 108 102 95 117<br />
80 121 123 113 110 106 102 97 91 113<br />
60 117 121 110 106 102 99 95 92 110<br />
50 117 120 109 105 101 98 95 92 109<br />
40 118 119 109 104 100 97 95 92 108<br />
1130 100 127 130 124 119 115 113 108 101 122<br />
80 124 126 120 114 111 107 102 96 118<br />
60 120 124 118 111 107 104 100 97 115<br />
50 120 123 117 110 106 103 100 97 114<br />
40 121 123 116 109 105 102 100 97 113<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
939<br />
GREENHECK<br />
®
73 BISW<br />
Performance Data<br />
Wheel Diameter = 73 in.<br />
Outlet Area = 30.64 ft 2<br />
Tip Speed = 19.11 x RPM<br />
Maximum BHP = (RPM/121) 3<br />
For belt driven applications over 250 Hp,<br />
consult factory<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 848<br />
<strong>IV</strong> 1022<br />
Static Pressure in Inches<br />
CFM OV 10 11 12 13 14 15 16 17 18<br />
20<br />
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />
99700 3253 727 204 750 222 774 240 796 259 821 279 846 301 870 323 894 345<br />
106200 3466 741 220 766 239 788 259 810 278 832 298 852 317 876 339 900 362 923 386<br />
112700 3678 758 238 780 258 803 278 825 298 846 319 866 339 886 360 906 381 929 404<br />
119200 3890 775 258 797 278 818 298 840 319 861 341 880 362 900 384 920 405 938 427<br />
125700 4102 792 278 814 299 835 320 855 342 875 364 896 386 916 409 934 431 952 454<br />
132200 4314 809 299 831 322 852 344 872 366 891 389 910 411 930 435 949 458 967 482<br />
138700 4526 827 321 849 345 869 368 889 392 908 415 927 439 945 462 963 486 982 511<br />
145200 4738 846 344 867 369 887 394 906 418 925 443 944 467 962 492 979 516 996 541<br />
151700 4951 866 369 885 395 905 420 924 446 943 472 961 497 979 522 996 548<br />
158200 5163 886 394 905 421 923 448 942 475 960 501 978 528 996 555 1013 581<br />
164700 5375 907 422 925 449 943 477 960 505 978 533 996 560 1013 588<br />
171200 5587 930 453 945 479 963 507 980 536 997 565<br />
Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />
Performance ratings do not include the effects of appurtenances in the airstream.<br />
Power rating (BHP) does not include drive losses.<br />
Sound Power [dB Ref 10 -12 watts]<br />
INLET SOUND POWER, Lwi<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />
600 100 114 110 103 101 100 93 87 81 104<br />
80 112 106 99 97 94 89 84 80 100<br />
60 109 103 95 94 92 89 87 84 98<br />
50 109 103 94 93 91 90 87 84 97<br />
40 113 107 98 95 92 91 88 85 99<br />
848 100 120 124 114 109 108 104 98 92 114<br />
80 117 122 110 105 103 99 94 90 111<br />
60 114 119 106 102 100 98 95 93 108<br />
50 115 120 106 101 100 98 96 93 108<br />
40 122 122 109 103 101 99 97 94 110<br />
1022 100 124 128 121 114 112 109 104 97 119<br />
80 120 125 117 110 108 104 99 95 115<br />
60 117 122 114 107 105 103 100 97 112<br />
50 118 123 114 106 104 103 101 98 112<br />
40 125 127 117 109 106 103 101 99 115<br />
972 453<br />
978 474<br />
988 500<br />
1002 529<br />
% WOV = (CFM x 100) / (RPM x 227)<br />
OUTLET SOUND POWER, Lwo<br />
RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />
600 100 118 113 108 105 103 98 91 84 108<br />
80 115 109 104 101 97 92 86 81 103<br />
60 113 107 101 97 94 90 86 82 100<br />
50 112 106 100 96 93 90 86 83 99<br />
40 111 105 99 95 91 89 86 83 98<br />
848 100 125 127 117 114 111 108 102 95 118<br />
80 122 124 113 110 106 102 97 91 113<br />
60 118 123 111 107 103 100 96 92 111<br />
50 118 121 110 105 101 99 96 92 110<br />
40 119 120 109 104 100 98 96 92 109<br />
1022 100 128 131 124 119 116 113 108 101 123<br />
80 125 128 120 115 111 107 102 97 118<br />
60 121 125 118 112 108 105 101 97 116<br />
50 121 125 117 111 107 104 101 97 115<br />
40 122 124 116 110 105 103 100 97 114<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />
and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />
GREENHECK<br />
®<br />
25
30 BISWD<br />
26<br />
Direct Drive <strong>Fan</strong> Quick Selection<br />
Direct drive centrifugal fan wheel widths are available<br />
from 50% to 100% in 5% increments. Multiple fans sizes<br />
may be available to meet a specific performance<br />
requirement. The following charts allow for quick<br />
selection of fan size and RPM for specified operating<br />
points. The charts shown are for 60 Hertz motor RPMs -<br />
870, 1170, 1770.<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 2102<br />
<strong>IV</strong> 2532<br />
Wheel Diameter 30 in.<br />
Outlet Area 5.17 ft. 2<br />
GREENHECK<br />
®
33 BISWD<br />
36 BISWD<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1911<br />
<strong>IV</strong> 2302<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 2082<br />
Wheel Diameter 33 in.<br />
Outlet Area 6.26 ft. 2<br />
Wheel Diameter 36 1/2 in.<br />
Outlet Area 7.66 ft. 2<br />
GREENHECK<br />
®<br />
27
40 BISWD<br />
44 BISWD<br />
28<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 1852<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1392<br />
<strong>IV</strong> 1675<br />
Wheel Diameter 40 1/4 in.<br />
Outlet Area 9.31 ft. 2<br />
Wheel Diameter 44 1/2 in.<br />
Outlet Area 11.39 ft. 2<br />
GREENHECK<br />
®
49 BISWD<br />
54 BISWD<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 1264<br />
<strong>IV</strong> 1521<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 1375<br />
Wheel Diameter 49 in.<br />
Outlet Area 13.80 ft. 2<br />
Wheel Diameter 54 1/4 in.<br />
Outlet Area 16.92 ft. 2<br />
GREENHECK<br />
®<br />
29
60 BISWD<br />
60 BISWD<br />
30<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 1243<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 1243<br />
Wheel Diameter 60 in.<br />
Outlet Area 20.70 ft. 2<br />
Wheel Diameter 60 in.<br />
Outlet Area 20.70 ft. 2<br />
GREENHECK<br />
®
66 BISWD<br />
73 BISWD<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
III 939<br />
<strong>IV</strong> 1130<br />
Pressure <strong>Class</strong> Limits<br />
<strong>Class</strong> Max. RPM<br />
<strong>IV</strong> 1022<br />
Wheel Diameter 66 in.<br />
Outlet Area 25.05 ft. 2<br />
Wheel Diameter 73 in.<br />
Outlet Area 30.64 ft. 2<br />
GREENHECK<br />
®<br />
31
30 BISWD<br />
32<br />
Direct Drive Sound Data Sound Power [dB Ref 10 -12 watts]<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1770 2 102 102 108 102 98 98 94 86 106 1770 2 111 110 111 105 103 102 98 90 109<br />
4 101 100 107 100 97 96 92 85 104 4 109 108 109 104 102 100 96 89 108<br />
6 100 99 106 98 95 93 90 84 102 6 108 107 108 102 101 98 94 87 107<br />
8 99 97 103 96 93 92 89 85 100 8 107 106 107 101 99 96 92 87 105<br />
10 100 96 102 94 91 91 89 87 99 10 106 104 104 99 96 93 90 87 102<br />
33 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1770 4 106 103 111 103 100 100 96 88 108 1770 4 113 112 113 107 106 104 100 92 112<br />
6 104 102 110 102 98 98 94 87 106 6 112 111 112 106 105 103 99 91 110<br />
8 104 100 109 100 97 96 93 87 105 8 111 110 111 105 103 101 97 90 109<br />
10 104 99 107 98 96 95 92 88 103 10 110 108 110 104 102 99 95 90 108<br />
12 104 98 106 96 94 94 92 90 102 12 109 107 107 102 100 96 93 90 106<br />
36 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1770 8 104 111 117 105 100 98 95 89 111 1770 8 114 117 119 109 105 102 98 92 114<br />
10 103 110 116 104 99 97 94 89 110 10 113 116 118 108 104 100 97 91 113<br />
12 102 109 115 103 98 96 94 90 109 12 111 114 117 107 103 99 95 91 112<br />
14 102 109 114 101 96 95 93 91 108 14 109 113 117 106 101 98 94 91 111<br />
16 112 117 117 105 98 96 94 92 111 16 111 113 115 104 99 95 93 90 109<br />
40 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1770 12 107 114 118 109 103 101 97 92 112 1770 12 117 119 119 112 107 104 100 95 115<br />
14 106 114 117 108 102 100 97 93 112 14 115 118 119 111 107 103 99 94 115<br />
16 106 113 116 106 101 99 96 93 111 16 114 117 118 111 106 102 98 94 114<br />
18 105 112 114 105 100 98 96 93 110 18 112 116 118 110 104 101 97 94 113<br />
20 108 114 115 105 99 98 96 94 110 20 113 116 117 109 103 99 97 94 112<br />
44 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1170 2 107 113 108 101 99 97 91 85 106 1170 2 115 117 111 106 102 100 95 88 110<br />
4 106 112 107 100 97 95 89 84 105 4 114 116 110 105 101 98 93 87 108<br />
6 104 112 106 98 96 93 88 83 103 6 113 115 108 103 99 96 91 85 107<br />
8 102 110 104 96 94 92 88 84 102 8 110 113 107 101 98 94 90 85 105<br />
10 102 109 102 94 93 91 88 86 100 10 108 112 106 100 96 92 89 85 104<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi,<br />
LwiA and outlet Lwo, LwoA sound power levels for full (100%) width wheels, installation Type B: free inlet, ducted outlet. Outlet ratings include<br />
the effects of duct end correction.
Direct Drive Sound Data Sound Power [dB Ref 10 -12 watts]<br />
49 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1170 4 110 116 111 103 101 99 93 88 108 1170 4 117 119 113 108 105 102 97 90 112<br />
6 108 115 109 102 100 97 92 87 107 6 116 118 112 107 103 100 95 89 110<br />
8 107 114 108 101 98 96 91 86 106 8 115 117 111 106 102 99 94 88 109<br />
10 106 113 107 99 97 95 91 88 105 10 113 116 110 104 100 97 93 88 108<br />
12 105 112 105 97 96 94 91 89 103 12 111 115 109 103 99 95 92 88 107<br />
54 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1170 6 113 119 113 106 104 102 96 91 111 1170 6 120 122 115 111 107 105 99 93 114<br />
8 112 119 112 105 103 100 94 90 110 8 120 121 114 110 106 103 98 92 113<br />
10 111 118 111 103 102 99 94 90 109 10 118 120 113 109 105 102 97 91 112<br />
12 110 117 110 102 101 98 94 91 108 12 116 120 112 108 104 101 96 91 111<br />
14 109 115 108 101 99 97 95 92 107 14 114 119 111 107 102 99 95 91 110<br />
60 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
870 2 113 116 107 102 101 97 91 85 107 870 2 119 119 110 107 104 101 95 88 111<br />
4 112 115 106 101 99 96 90 85 106 4 118 118 109 106 103 99 93 87 109<br />
6 110 115 104 99 97 94 88 84 104 6 116 117 107 104 101 97 91 85 108<br />
8 109 113 102 98 96 93 89 85 103 8 114 116 106 103 99 95 91 86 106<br />
10 108 111 100 96 95 92 90 87 102 10 112 115 105 101 97 94 90 86 105<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
1170 10 115 122 116 108 105 103 97 93 113 1170 10 122 124 118 113 109 106 101 95 116<br />
12 114 121 115 107 105 102 97 93 112 12 121 123 117 112 108 105 100 94 116<br />
14 114 120 114 106 104 102 97 93 111 14 120 123 116 111 107 104 99 94 115<br />
16 113 119 113 105 103 101 98 94 111 16 118 122 116 110 106 103 99 95 114<br />
18 112 118 112 104 102 100 98 95 110 18 117 121 115 109 105 102 98 95 113<br />
66 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
870 4 115 119 109 104 103 99 93 88 109 870 4 121 122 113 109 106 103 97 90 113<br />
6 114 118 108 103 101 98 92 87 108 6 120 121 111 108 105 101 95 89 112<br />
8 113 118 107 102 100 97 91 87 107 8 119 120 110 107 103 99 94 88 110<br />
10 112 116 105 100 99 96 92 89 106 10 117 119 109 105 102 98 93 89 109<br />
12 111 115 103 99 98 95 93 90 105 12 115 118 108 104 100 97 93 89 108<br />
73 BISWD<br />
Inlet Sound Power, Lwi Outlet Sound Power, Lwo<br />
RPM Ps 1 2 3 4 5 6 7 8 LwiA RPM Ps 1 2 3 4 5 6 7 8 LwoA<br />
870 6 118 124 112 107 105 102 96 91 113 870 6 124 126 116 112 109 105 99 93 116<br />
8 117 123 111 106 104 101 95 90 112 8 123 125 115 111 108 104 98 92 115<br />
10 116 122 110 105 103 100 95 91 111 10 122 124 114 110 106 102 97 92 114<br />
12 115 121 109 104 102 99 95 92 110 12 120 124 113 109 105 101 97 92 113<br />
14 114 120 107 103 101 99 96 93 109 14 119 123 112 107 104 100 96 92 112<br />
The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi,<br />
LwiA and outlet Lwo, LwoA sound power levels for full (100%) width wheels, installation Type B: free inlet, ducted outlet. Outlet ratings include<br />
the effects of duct end correction.<br />
33
Dimensional Data<br />
Data shown on these pages is for general information only and should not be used for exact installation dimensions. Columns A, B and C<br />
have been rounded up to the nearest 1". All other columns are rounded to the nearest 1/8". For detailed dimensional data or dimensions<br />
involving partial width wheels consult factory. All dimensional drawings represent clockwise rotation. Counterclockwise would be a mirror<br />
image and would not affect overall dimensions. Rotation is determined from the drive side of the unit.<br />
34<br />
A<br />
Sizes 18-73<br />
Arrangement 1<br />
Size <strong>Class</strong><br />
18 <strong>IV</strong><br />
20 <strong>IV</strong><br />
22 <strong>IV</strong><br />
24 <strong>IV</strong><br />
27 <strong>IV</strong><br />
30 <strong>IV</strong><br />
33 <strong>IV</strong><br />
36 <strong>IV</strong><br />
40 <strong>IV</strong><br />
44 <strong>IV</strong><br />
49 <strong>IV</strong><br />
54 <strong>IV</strong><br />
60 <strong>IV</strong><br />
66 <strong>IV</strong><br />
73 <strong>IV</strong><br />
B<br />
A B<br />
TH BH UB DB TAU BAU<br />
D<br />
A<br />
B<br />
D<br />
TH<br />
BH<br />
A<br />
UB<br />
DB<br />
B<br />
TAU BAU<br />
Due to <strong>Greenheck</strong>’s policy of continuous product improvement, dimensions are subject to change.<br />
For complete dimensional information refer to the applicable <strong>Greenheck</strong> submittal drawing.<br />
A<br />
D<br />
B C<br />
Clockwise Top Horizontal (TH) discharge shown above<br />
D<br />
A<br />
C<br />
TH<br />
B<br />
BH<br />
BAU<br />
D<br />
UB<br />
TAU<br />
D<br />
DB<br />
F G J<br />
37 39 34 33 43 37 33 36 32 42 42 15 1 /2 24 18 15 7 /8 19 3 /8 14 5 /8 19 1 /4<br />
40 42 37 36 47 41 36 39 34 46 45 16 1 /2 26 19 1 /2 17 21 1 /4 16 21 1 /8<br />
44 46 40 39 52 44 39 43 38 50 50 18 1 /2 28 21 1 /2 18 3 /8 23 5 /8 17 3 /4 23<br />
48 50 44 43 57 48 43 47 42 55 53 20 30 24 19 7 /8 26 19 1 /2 25 7 /8<br />
53 54 48 47 62 53 47 52 46 60 57 22 33 26 21 3 /8 28 5 /8 21 1 /2 28 1 /2<br />
58 60 53 51 68 58 51 57 51 66 63 24 1 /2 36 29 23 3 /8 31 7 /8 23 7 /8 31 3 /4<br />
65 66 58 56 75 64 56 63 56 72 70 27 1 /2 40 32 25 1 /4 35 26 1 /4 34 7 /8<br />
71 73 63 61 82 70 61 69 62 79 75 30 1 /2 44 35 1 /2 27 1 /2 38 3 /4 29 38 1 /2<br />
78 80 69 67 90 77 67 76 69 87 80 33 1 /2 48 39 29 7 /8 42 5 /8 31 7 /8 42<br />
86 89 76 74 99 86 74 84 76 96 88 36 1 /2 53 1 /2 42 1 /2 32 5 /8 47 1 /8 35 1 /4 46 1 /2<br />
94 97 83 81 109 93 81 92 83 105 95 40 58 47 35 3 /8 51 3 /4 38 3 /4 51<br />
104 106 91 89 120 102 89 102 92 116 101 44 63 1 /2 52 38 3 /4 57 3 /8 42 7 /8 56 1 /2<br />
114 119 100 98 132 115 98 112 102 127 111 48 1 /2 72 57 42 3 /8 63 1 /2 47 1 /2 62 1 /2<br />
126 130 109 107 144 125 107 124 112 140 117 53 78 62 46 1 /4 69 3 /4 52 1 /8 69<br />
139 143 120 118 159 138 118 137 124 154 123 59 85 1 /2 69 50 3 /4 77 1 /4 57 5 /8 76<br />
BH UB DB TAU BAU<br />
G<br />
F<br />
J<br />
A<br />
B<br />
GREENHECK<br />
®<br />
D
Sizes 30-49<br />
Arrangement 4<br />
Size<br />
Sizes 30-73<br />
Arrangement 8<br />
A<br />
B C*<br />
A<br />
A B<br />
TH BH UB DB TAU BAU TH<br />
C*<br />
BH<br />
UB<br />
DB<br />
TAU BAU<br />
284T<br />
286T 324T<br />
326T 364T<br />
365T 404T<br />
405T 444T<br />
445T<br />
30 58 60<br />
33 65 66<br />
36 71 73<br />
40 78 80<br />
44 86 89<br />
49 94 97<br />
Size<br />
30 58 60<br />
33 65 66<br />
36 71 73<br />
40 78 80<br />
44 86 89<br />
49 94 97<br />
54 104 106<br />
60 114 119<br />
66 126 130<br />
73 139 143<br />
B<br />
D<br />
A<br />
B<br />
D<br />
A<br />
G<br />
F<br />
B C*<br />
D<br />
A<br />
D<br />
B<br />
BH UB DB TAU BAU<br />
D<br />
A<br />
J<br />
* Dimension “C” is dependent upon<br />
motor frame size and wheel/scroll<br />
width. The Dim. “C” shown is<br />
calculated assuming 100%<br />
wheel/scroll width and TEFC<br />
motors.<br />
Dimension “G” shown is for 100%<br />
wheel/scroll width.<br />
B<br />
TH<br />
G<br />
D<br />
F<br />
BH<br />
BAU UB<br />
TAU<br />
A<br />
D<br />
J<br />
DB<br />
B<br />
F G J<br />
53 51 68 58 51 57 51 66 53 55 — — — 24 1 /2 36 29 23 3 /8 31 7 /8 23 7 /8 31 3 /4<br />
58 56 75 64 56 63 56 72 56 59 61 — — 27 1 /2 40 32 25 1 /4 35 26 1 /4 34 7 /8<br />
63 61 82 70 61 69 62 79 — 61 64 71 — 30 1 /2 44 35 1 /2 27 1 /2 38 3 /4 29 38 1 /2<br />
69 67 90 77 67 76 69 87 — — — 73 79 33 1 /2 48 39 29 7 /8 42 5 /8 31 7 /8 42<br />
76 74 99 86 74 84 76 96 — — 71 77 83 36 1 /2 53 1 /2 42 1 /2 32 5 /8 47 1 /8 35 1 /4 46 1 /2<br />
83 81 109 93 81 92 83 105 — — — 80 86 40 58 47 35 3 /8 51 3 /4 38 3 /4 51<br />
A B C* D<br />
TH BH UB DB TAU BAU<br />
TH UB<br />
TAU BAU 284T 324T 364T 404T 444T 447T BH UB<br />
BH DB 286T 326T 365T 405T 445T 449T TH BAU TAU<br />
F G J<br />
53 51 68 58 51 57 51 66 89 92 — — — — 24 1 /2 36 29 23 3 /8 31 7 /8 23 7 /8 31 3 /4<br />
58 56 75 64 56 63 56 72 95 98 101 — — — 27 1 /2 40 32 25 1 /4 35 26 1 /4 34 7 /8<br />
63 61 82 70 61 69 62 79 — 103 106 113 — — 30 1 /2 44 35 1 /2 27 1 /2 38 3 /4 29 38 1 /2<br />
69 67 90 77 67 76 69 87 — — — 117 125 — 33 1 /2 48 39 29 7 /8 42 5 /8 31 7 /8 42<br />
76 74 99 86 74 84 76 96 — — 117 125 132 — 36 1 /2 53 1 /2 42 1 /2 32 5 /8 47 1 /8 35 1 /4 46 1 /2<br />
83 81 109 93 81 92 83 105 — — — 131 138 — 40 58 47 35 3 /8 51 3 /4 38 3 /4 51<br />
91 89 120 102 89 102 92 116 — — — — 150 155 44 63 1 /2 52 38 3 /4 57 3 /8 42 7 /8 56 1 /2<br />
100 98 132 115 98 112 102 127 — — — — 159 164 48 1 /2 72 57 42 3 /8 63 1 /2 47 1 /2 62 1 /2<br />
109 107 144 125 107 124 112 140 — — — — 164 170 53 78 62 46 1 /4 69 3 /4 52 1 /8 69<br />
120 118 159 138 118 137 124 154 — — — — — 176 59 85 1 /2 69 50 3 /4 77 1 /4 57 5 /8 76<br />
Due to <strong>Greenheck</strong>’s policy of continuous product improvement, dimensions are subject to change.<br />
For complete dimensional information refer to the applicable <strong>Greenheck</strong> submittal drawing.<br />
DB<br />
GREENHECK<br />
®<br />
35<br />
D
The model number codes on this page are a complete guide to ordering or specifiing <strong>Greenheck</strong> <strong>Class</strong> <strong>IV</strong> centifugal fan models.<br />
Belt Drive (BISW) Model Number Code<br />
<strong>Fan</strong> Size<br />
18 - 73<br />
Backward Inclined<br />
wheel, Single Width,<br />
belt drive<br />
Series 41 Construction<br />
36 - BISW - 41 - 1 - CW - TH - <strong>IV</strong> - A 500<br />
Arrangement<br />
1<br />
Rotation<br />
cw, ccw<br />
Direct Drive (BISWD) Model Number Code<br />
<strong>Fan</strong> Size<br />
Arr. 4 30 - 49<br />
Arr. 8 30 - 73<br />
Backward Inclined<br />
wheel, Single Width,<br />
Direct drive<br />
Series 41 Construction<br />
36 - BISWD - 41 - 4 - CW - TH - <strong>IV</strong> - 80P - A 500<br />
Arrangement<br />
4, 8<br />
Rotation<br />
cw, ccw<br />
<strong>Fan</strong> <strong>Class</strong><br />
<strong>IV</strong><br />
GREENHECK<br />
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410<br />
PH. 715-359-6171<br />
®<br />
Motor Horsepower<br />
400 = 40 750 = 75<br />
500 = 50 1000 = 100<br />
600 = 60 1250 = 125<br />
Motor RPM<br />
M = 3500 C = 870<br />
A = 1770 F = 690<br />
B = 1170<br />
Discharge Position<br />
TH = Top Horizontal TAU = Top Angular Up<br />
BH = Bottom Horizontal BAU = Bottom Angular Up<br />
UB = Up Blast TAD = Top Angular Down<br />
DB = Down Blast BAD = Bottom Angular Down<br />
<strong>Fan</strong> <strong>Class</strong><br />
<strong>IV</strong><br />
Discharge Position<br />
TH = Top Horizontal TAU = Top Angular Up<br />
BH = Bottom Horizontal BAU = Bottom Angular Up<br />
UB = Up Blast TAD = Top Angular Down<br />
DB = Down Blast BAD = Bottom Angular Down<br />
Motor Horsepower<br />
400 = 40 750 = 75<br />
500 = 50 1000 = 100<br />
600 = 60 1250 = 125<br />
Motor RPM<br />
A = 1770 C = 870<br />
B = 1170<br />
Percentage Wheel Width<br />
100 = 100% 70P = 70%<br />
90P = 90% 60P = 60%<br />
80P = 80% 50P = 50%<br />
Cent. <strong>Fan</strong> <strong>Class</strong> <strong>IV</strong> PM (Series 41) R<br />
July 1998