66 BISW<br />

Performance Data<br />

Wheel Diameter = 66 in.<br />

Outlet Area = 25.05 ft 2<br />

Tip Speed = 17.28 x RPM<br />

Maximum BHP = (RPM/143) 3<br />

For belt driven applications over 250 Hp,<br />

consult factory<br />

Pressure <strong>Class</strong> Limits<br />

<strong>Class</strong> Max. RPM<br />

III 939<br />

<strong>IV</strong> 1130<br />

Static Pressure in Inches<br />

CFM OV 10 11 12 13 14 15 16 17 18<br />

20<br />

RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP<br />

86900 3469 820 180 847 196 871 212 896 227 920 243 943 259 969 277 995 296 1020 315<br />

91800 3664 837 194 862 210 887 226 912 243 934 259 957 276 979 293 1001 310 1026 329 1075 369<br />

96700 3860 854 208 878 225 902 241 926 259 950 276 972 293 993 311 1015 328 1036 346 1081 385<br />

101600 4055 871 223 896 241 919 258 942 275 965 293 987 311 1008 329 1029 348 1050 366 1089 403<br />

106500 4251 889 239 913 257 936 275 959 293 980 312 1002 330 1024 349 1045 368 1064 387 1104 425<br />

111400 4447 908 256 931 274 954 293 976 312 997 331 1018 350 1038 369 1059 389 1080 408 1118 448<br />

116300 4642 926 273 949 292 972 312 993 332 1015 351 1035 371 1055 391 1075 411 1095 431<br />

121200 4838 946 291 967 311 990 332 1011 352 1032 373 1052 393 1072 413 1092 434 1110 455<br />

126100 5033 966 309 987 331 1008 352 1029 373 1050 395 1070 416 1090 437 1109 458<br />

131000 5229 987 329 1008 351 1028 373 1048 396 1068 418 1088 440 1107 462<br />

135900 5425 1009 351 1028 373 1048 395 1067 418 1086 441 1106 464<br />

140800 5620 1032 374 1049 396 1068 418 1087 442 1106 466<br />

Performance shown is for model BISW arrangement 1, installation Type B - free inlet, ducted outlet.<br />

Performance ratings do not include the effects of appurtenances in the airstream.<br />

Power rating (BHP) does not include drive losses.<br />

24<br />

Sound Power [dB Ref 10 -12 watts]<br />

INLET SOUND POWER, Lwi<br />

RPM % WOV 1 2 3 4 5 6 7 8 LwiA<br />

700 100 114 114 105 101 100 95 89 83 105<br />

80 111 111 100 97 95 90 86 81 101<br />

60 107 107 97 94 93 90 87 85 99<br />

50 109 108 96 93 92 90 88 85 99<br />

40 113 111 100 95 93 91 89 86 101<br />

939 100 119 123 114 108 107 105 98 92 113<br />

80 115 121 110 104 103 99 94 89 110<br />

60 112 118 106 101 100 98 95 92 107<br />

50 114 118 106 100 99 97 96 93 107<br />

40 121 121 110 103 100 98 96 93 109<br />

1130 100 122 126 121 114 111 109 104 97 118<br />

80 118 124 118 110 107 104 99 95 115<br />

60 115 121 114 106 104 102 100 97 112<br />

50 117 121 114 106 103 102 100 98 112<br />

40 124 125 118 109 105 103 101 98 115<br />

% WOV = (CFM x 100) / (RPM x 168)<br />

OUTLET SOUND POWER, Lwo<br />

RPM % WOV 1 2 3 4 5 6 7 8 LwoA<br />

700 100 118 117 109 106 104 100 93 86 109<br />

80 115 113 105 102 98 94 88 82 105<br />

60 112 111 102 98 95 91 87 84 102<br />

50 112 110 101 97 93 91 88 84 101<br />

40 112 109 100 96 92 90 87 84 100<br />

939 100 124 126 117 114 111 108 102 95 117<br />

80 121 123 113 110 106 102 97 91 113<br />

60 117 121 110 106 102 99 95 92 110<br />

50 117 120 109 105 101 98 95 92 109<br />

40 118 119 109 104 100 97 95 92 108<br />

1130 100 127 130 124 119 115 113 108 101 122<br />

80 124 126 120 114 111 107 102 96 118<br />

60 120 124 118 111 107 104 100 97 115<br />

50 120 123 117 110 106 103 100 97 114<br />

40 121 123 116 109 105 102 100 97 113<br />

The sound power level ratings shown are in decibels, referred to 10 -12 watts calculated per AMCA Standard 301. Values shown are for inlet Lwi, LwiA<br />

and outlet Lwo, LwoA sound power levels for installation Type B: free inlet, ducted outlet. Outlet ratings include the effects of duct end correction.<br />

939<br />

GREENHECK<br />

®