Stage 1 – Unit Positioning, Mounting and Levelling<br />
<strong>SKS</strong> humidifier must be installed <strong>to</strong> ensure the steam hose length is kept <strong>to</strong> the<br />
sh<strong>or</strong>test possible length.<br />
Maximum steam hose length between the humidifier and the steam distribution<br />
pipes is 5m.<br />
<strong>SKS</strong> humidifier should be installed with provision f<strong>or</strong> the <strong>Steam</strong> supply piping<br />
connections and <strong>Steam</strong> condensate trap installation.<br />
The humidifier should be located in an area that is fully accessible f<strong>or</strong> inspection<br />
and servicing. Observe the minimum access distances as shown in figure 6.<br />
<strong>SKS</strong> humidifier can be provided with adjustable legs (optional) in <strong>or</strong>der <strong>to</strong> ensure<br />
proper level when installed directly on the flo<strong>or</strong>.<br />
Provide a level, solid foundation f<strong>or</strong> the humidifier.<br />
Ensure that the flo<strong>or</strong> beneath the humidifier is water proof <strong>to</strong> withstand any water<br />
spillage during servicing <strong>or</strong> if a problem occurs.<br />
Ensure that the humidifier is properly attached through its legs using anch<strong>or</strong>s <strong>to</strong><br />
the flo<strong>or</strong>.<br />
<strong>SKS</strong>-200-CHP Models can be ceiling hung by using the appropriate Lifting and<br />
hanging bracket.<br />
<strong>SKS</strong> humidifier should be levelled, in <strong>or</strong>der <strong>to</strong> ensure proper slop f<strong>or</strong> condensate<br />
return by heat exchanger.<br />
11<br />
<strong>SKS</strong> Neptronic<br />
Rod & Nuts<br />
(M10 minimum)<br />
Lifting & Hanging<br />
Bracket<br />
(Fig. 5)<br />
The humidifier location should have an ambient temperature of less than 30˚C.<br />
Minimum<br />
Clearances 0.60m<br />
minimum<br />
0.60m<br />
minimum<br />
0.75m<br />
minimum<br />
0.60m<br />
minimum<br />
1m<br />
minimum<br />
(Fig. 6)<br />
Note: Above minimum clearances are indicated f<strong>or</strong> inspection and servicing access. <strong>SKS</strong><br />
<strong>Humidifier</strong> is designed f<strong>or</strong> a 0 clearance <strong>to</strong> combustible material.