<strong>Humidifier</strong><br />
Control<br />
(external mode)<br />
24 VAC<br />
<strong>SKS</strong> - <strong>Steam</strong> <strong>or</strong> <strong>HTHW</strong> <strong>to</strong> <strong>Steam</strong> <strong>Humidifier</strong><br />
Stage 7 –Electrical Control Connections<br />
Neptronic® <strong>SKS</strong> modulating <strong>Steam</strong> <strong>Humidifier</strong> can be installed in conjunction with<br />
Neptronic® HRO20 humidity controller, see above wiring diagram (fig. 21). In this<br />
case humidity set point will be controlled by HRO20 humidity controller; humidifier<br />
will have <strong>to</strong> be set in external mode.<br />
In this external mode <strong>SKS</strong> can accept any modulating control signal (0-10Vdc, 2-<br />
10Vdc, 0-20mA <strong>or</strong> 4-20mA) wired <strong>to</strong> terminal 3.<br />
1 2 3 4 5 6 7 8 9 10<br />
Common<br />
Control demand<br />
Room humidistat<br />
<strong>Humidifier</strong><br />
Control<br />
(internal mode)<br />
Fan Proof<br />
Hi-Limit<br />
humidistat<br />
Interlock<br />
11<br />
Fan &<br />
alarms<br />
contacts<br />
(Fig. 21)<br />
23<br />
12 13<br />
COM<br />
24 VAC<br />
12<br />
13<br />
MOD<br />
14 15<br />
%RH<br />
16<br />
HRO20<br />
humidistat<br />
Neptronic® <strong>SKS</strong> modulating <strong>Steam</strong> <strong>Humidifier</strong> can be installed in conjunction with<br />
Neptronic® HRM-X <strong>or</strong> HDM-X remote humidity sens<strong>or</strong>. In this case humidity set<br />
point will be controlled by <strong>SKS</strong> humidifier; humidifier will be set in internal mode. see<br />
below wiring diagram.<br />
1 2 3 4 5 6 7 8 9 10<br />
Common<br />
24 VAC<br />
Room humidistat<br />
Fan Proof<br />
Hi-Limit<br />
humidistat<br />
Interlock<br />
To Term. #1<br />
To Term. #2<br />
To Term. #3<br />
(Fig. 22)<br />
11<br />
Fan &<br />
alarms<br />
contacts<br />
12 13<br />
HRM-X<br />
<strong>or</strong><br />
HDM-X<br />
1 COMMON<br />
2 24 VAC OR VDC<br />
3 0-10 VDC OUTPUT