<strong>SKS</strong> - <strong>Steam</strong> <strong>or</strong> <strong>HTHW</strong> <strong>to</strong> <strong>Steam</strong> <strong>Humidifier</strong><br />
31<br />
Programming mode<br />
To access menu, press on the but<strong>to</strong>n, LCD will display first step. You can scroll down <strong>to</strong> next step by<br />
pressing the but<strong>to</strong>n. Within a selected step, press on <strong>or</strong> but<strong>to</strong>ns <strong>to</strong> change values (when required)<br />
Seq<br />
#<br />
01<br />
01A<br />
01B<br />
01C<br />
01D<br />
02<br />
03<br />
04<br />
05<br />
06<br />
07<br />
08<br />
09<br />
10<br />
Display Description Values<br />
CONTROL<br />
EXTERNAL<br />
SP SOURC<br />
INTERNAL<br />
SETPOINT<br />
40% RH<br />
DUCT SRC<br />
DISABLE<br />
DUCT SP<br />
80% RH<br />
DRAIN<br />
8 HRS<br />
RUNNING<br />
0645HRS<br />
SERVICE<br />
1000HRS<br />
LOCK ON<br />
80% PWR<br />
RESET<br />
ALRM NO<br />
CTRL INP<br />
2-10 VDC<br />
HUM. INP<br />
2-10 VDC<br />
DUCT INP<br />
2-10 VDC<br />
<strong>SKS</strong> XXXX<br />
NEP r1.0<br />
Selection of Control mode.<br />
If External is selected, the control demand will be received by the<br />
control input; if Com P<strong>or</strong>t is selected, the control demand will be<br />
received by the communication p<strong>or</strong>t (BACnet option).<br />
Selection of the Set Point Source (Control Internal only).<br />
Selection of source f<strong>or</strong> room humidity set point.<br />
Selection of room relative humidity set point.<br />
(SP Source Internal only)<br />
Hi limit control mode.<br />
Selection of the source f<strong>or</strong> the duct high limit relative humidity<br />
(Control Internal only).<br />
Selection of high limit relative humidity set point.<br />
(Duct Source External only).<br />
Setting of au<strong>to</strong>matic drain cycle of evap<strong>or</strong>ation chamber.<br />
Note: In general, harder the water is, m<strong>or</strong>e often the drain cycle<br />
should be. Drain cycle setting does not affect the AFEC system.<br />
Number of running hours reading and reset<br />
To reset this counter: After service has been done, press<br />
simultaneously on & but<strong>to</strong>ns f<strong>or</strong> 30 seconds <strong>to</strong> reset the<br />
number of hours of operation <strong>to</strong> zero.<br />
Hour span between services.<br />
Note: In general, harder the water is, lower the number of hours of<br />
operation bef<strong>or</strong>e service should be.<br />
Selection of humidifier capacity reduction.<br />
i.e.: In this case, the humidifier will deliver 80% of its maximum<br />
rated output when at full demand.<br />
Reset of alarm<br />
To reset an alarm, press simultaneously on & but<strong>to</strong>ns.<br />
Control signal input selection.<br />
<strong>Humidity</strong> signal input selection.<br />
Duct <strong>Humidity</strong> signal input selection.<br />
Internal <strong>or</strong> External<br />
<strong>or</strong> Com P<strong>or</strong>t<br />
Default: External<br />
Internal <strong>or</strong> External<br />
<strong>or</strong> Com P<strong>or</strong>t<br />
Default: Internal<br />
Percentage<br />
From 10 <strong>to</strong> 90%<br />
Disable <strong>or</strong> External<br />
<strong>or</strong> Com P<strong>or</strong>t<br />
Default: Disable<br />
Percentage<br />
From 10 <strong>to</strong> 90%<br />
From 1 <strong>to</strong> 24 hours<br />
Increment: 1 hour<br />
Default: 4 hours.<br />
N/A<br />
Revision level of the program installed N/A<br />
Note:<br />
1. Any changes made in the Program Mode are saved in<strong>to</strong> a non-volatile mem<strong>or</strong>y.<br />
From 400 <strong>to</strong> 1500<br />
hours.<br />
Increment: 100<br />
Default: 1000 hours.<br />
From 00 <strong>to</strong> 100%.<br />
Increment: 1%<br />
Default: 100%<br />
Yes <strong>or</strong> No<br />
Default: No<br />
0-10VDC, 2-10VDC,<br />
0-20mA <strong>or</strong> 4-20mA<br />
Default : 2-10VDC<br />
0-10VDC, 2-10VDC,<br />
0-20mA <strong>or</strong> 4-20mA<br />
Default : 2-10VDC<br />
0-10VDC, 2-10VDC,<br />
0-20mA <strong>or</strong> 4-20mA<br />
Default : 2-10VDC