<strong>SKS</strong> - <strong>Steam</strong> <strong>or</strong> <strong>HTHW</strong> <strong>to</strong> <strong>Steam</strong> <strong>Humidifier</strong><br />

31<br />

Programming mode<br />

To access menu, press on the but<strong>to</strong>n, LCD will display first step. You can scroll down <strong>to</strong> next step by<br />

pressing the but<strong>to</strong>n. Within a selected step, press on <strong>or</strong> but<strong>to</strong>ns <strong>to</strong> change values (when required)<br />

Seq<br />

#<br />

01<br />

01A<br />

01B<br />

01C<br />

01D<br />

02<br />

03<br />

04<br />

05<br />

06<br />

07<br />

08<br />

09<br />

10<br />

Display Description Values<br />

CONTROL<br />

EXTERNAL<br />

SP SOURC<br />

INTERNAL<br />

SETPOINT<br />

40% RH<br />

DUCT SRC<br />

DISABLE<br />

DUCT SP<br />

80% RH<br />

DRAIN<br />

8 HRS<br />

RUNNING<br />

0645HRS<br />

SERVICE<br />

1000HRS<br />

LOCK ON<br />

80% PWR<br />

RESET<br />

ALRM NO<br />

CTRL INP<br />

2-10 VDC<br />

HUM. INP<br />

2-10 VDC<br />

DUCT INP<br />

2-10 VDC<br />

<strong>SKS</strong> XXXX<br />

NEP r1.0<br />

Selection of Control mode.<br />

If External is selected, the control demand will be received by the<br />

control input; if Com P<strong>or</strong>t is selected, the control demand will be<br />

received by the communication p<strong>or</strong>t (BACnet option).<br />

Selection of the Set Point Source (Control Internal only).<br />

Selection of source f<strong>or</strong> room humidity set point.<br />

Selection of room relative humidity set point.<br />

(SP Source Internal only)<br />

Hi limit control mode.<br />

Selection of the source f<strong>or</strong> the duct high limit relative humidity<br />

(Control Internal only).<br />

Selection of high limit relative humidity set point.<br />

(Duct Source External only).<br />

Setting of au<strong>to</strong>matic drain cycle of evap<strong>or</strong>ation chamber.<br />

Note: In general, harder the water is, m<strong>or</strong>e often the drain cycle<br />

should be. Drain cycle setting does not affect the AFEC system.<br />

Number of running hours reading and reset<br />

To reset this counter: After service has been done, press<br />

simultaneously on & but<strong>to</strong>ns f<strong>or</strong> 30 seconds <strong>to</strong> reset the<br />

number of hours of operation <strong>to</strong> zero.<br />

Hour span between services.<br />

Note: In general, harder the water is, lower the number of hours of<br />

operation bef<strong>or</strong>e service should be.<br />

Selection of humidifier capacity reduction.<br />

i.e.: In this case, the humidifier will deliver 80% of its maximum<br />

rated output when at full demand.<br />

Reset of alarm<br />

To reset an alarm, press simultaneously on & but<strong>to</strong>ns.<br />

Control signal input selection.<br />

<strong>Humidity</strong> signal input selection.<br />

Duct <strong>Humidity</strong> signal input selection.<br />

Internal <strong>or</strong> External<br />

<strong>or</strong> Com P<strong>or</strong>t<br />

Default: External<br />

Internal <strong>or</strong> External<br />

<strong>or</strong> Com P<strong>or</strong>t<br />

Default: Internal<br />

Percentage<br />

From 10 <strong>to</strong> 90%<br />

Disable <strong>or</strong> External<br />

<strong>or</strong> Com P<strong>or</strong>t<br />

Default: Disable<br />

Percentage<br />

From 10 <strong>to</strong> 90%<br />

From 1 <strong>to</strong> 24 hours<br />

Increment: 1 hour<br />

Default: 4 hours.<br />

N/A<br />

Revision level of the program installed N/A<br />

Note:<br />

1. Any changes made in the Program Mode are saved in<strong>to</strong> a non-volatile mem<strong>or</strong>y.<br />

From 400 <strong>to</strong> 1500<br />

hours.<br />

Increment: 100<br />

Default: 1000 hours.<br />

From 00 <strong>to</strong> 100%.<br />

Increment: 1%<br />

Default: 100%<br />

Yes <strong>or</strong> No<br />

Default: No<br />

0-10VDC, 2-10VDC,<br />

0-20mA <strong>or</strong> 4-20mA<br />

Default : 2-10VDC<br />

0-10VDC, 2-10VDC,<br />

0-20mA <strong>or</strong> 4-20mA<br />

Default : 2-10VDC<br />

0-10VDC, 2-10VDC,<br />

0-20mA <strong>or</strong> 4-20mA<br />

Default : 2-10VDC