Typical Raw steam installation<br />
!<br />
<strong>SKS</strong> - <strong>Steam</strong> <strong>or</strong> <strong>HTHW</strong> <strong>to</strong> <strong>Steam</strong> <strong>Humidifier</strong><br />
Stage 3 – Pipew<strong>or</strong>k f<strong>or</strong> <strong>HTHW</strong> / Raw steam<br />
A strainer as well as an isolating valve should be installed upstream <strong>to</strong> the<br />
control valve on the raw steam supply pipe.<br />
Brass coupling should be used between the heat exchanger stainless steel<br />
pipes and steam inlet / condensate outlet piping.<br />
The condensate must be evacuated efficiently. Theref<strong>or</strong>e, a condensate<br />
pocket and stream trap should be installed <strong>to</strong> ensure proper condensate<br />
elimination.<br />
Only float and thermostatic type steam trap should be used <strong>to</strong> eliminate<br />
condensate from the heat exchanger. This steam trap needs be able <strong>to</strong><br />
withstand at least twice the humidifier duty.<br />
Do not use thermostatic <strong>or</strong> Thermodynamic traps <strong>to</strong> eliminate condensate<br />
from the heat exchanger. Those traps can be used as small capacity traps <strong>to</strong><br />
eliminate condensate from raw steam line only.<br />
After installation, field piping and <strong>Humidifier</strong> <strong>Steam</strong> piping should be checked<br />
f<strong>or</strong> leak.<br />
All leaks MUST be sealed pri<strong>or</strong> <strong>to</strong> commissioning the <strong>Humidifier</strong>.<br />
<strong>Steam</strong> supply size Size of the steam supply pipe and control valve should be calculated<br />
considering 1.35kg of raw steam f<strong>or</strong> each kg of clean steam produced and<br />
distributed in<strong>to</strong> AHU.<br />