7. Malfunction messages<br />

Malfunction Cause Solution<br />

Temperature malfunction Motor w<strong>in</strong>d<strong>in</strong>g temperature Allow pump to cool, alarm must be<br />

switch has activated confirmed on control unit. If motor w<strong>in</strong>d<strong>in</strong>g<br />

temperature cont<strong>in</strong>ues to cause<br />

malfunctions – replace pump<br />

Over current The maximum allowable pump Remove blockage <strong>in</strong><br />

power has been exceeded impeller (follow safety <strong>in</strong>structions<br />

(impeller blocked)<br />

Let pump run shortly <strong>in</strong> opposite direction<br />

(‘Ma<strong>in</strong>tenance’ – ‘Manual operation’ –<br />

‘Opposite rotation’<br />

Under current The m<strong>in</strong>imum allowable pump power Check power supply cable and repair<br />

has been reached (power supply cable / replace if necessary (replace pump<br />

to pump has been cut or damaged) if necessary)<br />

Let pump run shortly <strong>in</strong> opposite direction<br />

(‘Ma<strong>in</strong>tenance’ – ‘Manual operation’ –<br />

‘Opposite rotation’)<br />

Motor protection switch Motor protection switch has been Check that current supply is correct.<br />

has activated improperly set. Current to pump to Remove pump blockage (follow safety<br />

high due to defective or blocked pump. <strong>in</strong>structions). Replace pump if damaged<br />

or defective<br />

Excessive current due to phase failure. Check power supply for phase loss.<br />

Phase error Phase L1, L2 or L3 miss<strong>in</strong>g Check control unit, power cable and<br />

fuses<br />

Check current protection switch<br />

Activation limit System protection has activated - Can be confirmed on control unit<br />

due to more than <strong>10</strong>0.000 activations - System protection allows another<br />

<strong>10</strong>00 activation before alarm activates<br />

aga<strong>in</strong><br />

- Replace system protection (contact<br />

<strong>KESSEL</strong> Customer Service<br />

- Activation alarm will cont<strong>in</strong>ue to activate<br />

after every <strong>10</strong>00 pump activations<br />

Actuator valve malfunction End position of actuator valve is Check actuator valve for proper rotation<br />

not be<strong>in</strong>g reached / movement – remove any obstructions<br />

Rotat<strong>in</strong>g field malfunction Incorrect rotat<strong>in</strong>g field at power Swap two phases of power supply<br />

connection<br />

Relay malfunction Surge protection does not switch off Disconnect control unit from power<br />

supply. Replace surge protector –<br />

contact <strong>KESSEL</strong> customer service<br />