9. SonicControl (Optional)<br />

9.14 General malfunctions<br />

First attempt to resolve the problem. If the problem can not be solved place the ma<strong>in</strong> switch to the ‘0’ sett<strong>in</strong>g and then<br />

press the alarm button for a m<strong>in</strong>imum of 5 seconds. This will confirm the malfunction and enter the data <strong>in</strong>to the logbook<br />

(this will not however solve the problem).<br />

Malfunction Error Cause Remedial measures<br />

Deviation between grease Inaccurate Improper <strong><strong>in</strong>stallation</strong> Check type of <strong>separator</strong> and<br />

layer seen <strong>in</strong> <strong>in</strong>spection SonicControl of SonicControl sensor assure SonicControl sett<strong>in</strong>g is<br />

w<strong>in</strong>dow (if available) and measurement correct<br />

SonicControl grease Improper <strong>in</strong>itialization Newly calibrate<br />

layer read<strong>in</strong>g of SonicControl the sensor<br />

Dirt or debris on Check position and <strong><strong>in</strong>stallation</strong><br />

SonicControl sensor of SonicControl probe<br />

Sensors are not <strong>in</strong> proper Set type of grease<br />

position and are not able<br />

to sense accurately<br />

Type of grease <strong>separator</strong> Clean sensor probes<br />

or size/model improperly<br />

set<br />

9.15 System errors<br />

Malfunction Cause Remedial measures<br />

Odour nuisance Cable entrance po<strong>in</strong>t <strong>in</strong>to grease <strong>separator</strong> Check conduit entrance<br />

is not air tight for tightness – repair if necessary<br />

Water <strong>in</strong> grease Cable entrance po<strong>in</strong>t <strong>in</strong>to grease <strong>separator</strong> Check conduit entrance<br />

<strong>separator</strong> area is not water tight for tightness – repair if necessary<br />

9.16 Techical data<br />

Inputs<br />

Sensor <strong>in</strong>put Sensor <strong>in</strong>put SonicControl<br />