High Voltage Control Unit Typ HST 01/01 - SCHNIER Elektrostatik ...
High Voltage Control Unit Typ HST 01/01 - SCHNIER Elektrostatik ...
High Voltage Control Unit Typ HST 01/01 - SCHNIER Elektrostatik ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
5.2 Constant<br />
Current Mode<br />
Operating Manual<br />
Nr. 81<strong>01</strong>23BE_02/00<br />
Page 13 of 17<br />
In the constant voltage mode the static current disconnection<br />
treshold can be adjusted between 0 and approx. 820 µA. When<br />
reaching approx. 80% of the adjusted disconnection treshold the<br />
"warning" signal is generated. As soon as the load decreases,<br />
the signal disappears. If the load nevertheless increases the<br />
controller indicates "fault" when the adjusted treshold value is<br />
reached. <strong>High</strong> voltage then will automatically be switched off. In<br />
order to switch the high voltage on again, the "HV on" signal has<br />
to be surpressed during at least one second either by (12) on the<br />
front plate or by means of the external control system.<br />
The dynamic di/dt disconnection treshold can be adjusted<br />
between 0 and approx. 999 µA/s. This part of the controller<br />
continuously monitors in which time a determined current value<br />
is reached, either during current rise or fall (current slope<br />
steepness). If the current slope is steeper than permitted by the<br />
adjusted value, the controller will indicate "fault". The fault reset<br />
procedure is the same as for static disconnection. The dynamic<br />
disconnection is independent of the static disconnection treshold.<br />
This means that a dynamic disconnection may also be triggered<br />
if the current is significantly below the static disconnection value.<br />
On the front plate of the HV control unit the type of disconnection,<br />
either static of dynamic, will be displayed. In addition a collective<br />
fault is output to the external control system.<br />
In constant current mode the operating current can be adjusted.<br />
This value is kept constant by regulating the output voltage. When<br />
reaching approx. 80% of the adjusted current value the "release"<br />
signal is output. By means of the "kV" nominal value the maximum<br />
admissible operating voltage between 40 and 100 kV can be<br />
limited.<br />
In constant current mode the static voltage disconnection treshold<br />
is fixed to approx. 38 kV. When reaching this value the device<br />
switches off and indicates "fault". In order to switch the high voltage<br />
on again, the "HV on" signal has to be surpressed during at least<br />
one second either by the switch (12) on the front plate or by means<br />
of the external control system. Before the controller disconnects<br />
the "warning" signal is generated at appox. 46 kV.