Programming Example<br />

MULTIFLEX MANUAL 12<br />

EDITION 2 : NOV 2000<br />

SECTION 2<br />

The following example shows how to continue programming from the previous stage to achieve a<br />

simple level application including setting a high alarm.<br />

1.5<br />

(Pr.3)<br />

0.5 (Pr.5)<br />

1.0 (Pr.4)<br />

Having changed the value in Pr.1 to 1 (level)<br />

Press ▲ Display Pr.02 = 2 (units in metres)<br />

▲ Change Pr.03 = 1.5 (empty distance)<br />

▲ Change Pr.04 = 1.0 (operational span)<br />

▲ Display Pr.05 = 0.5 (blanking distance)<br />

▲ Display Pr.06 = 1.0 (rate of change of level in metres)<br />

Press Pr.08 Change Pr.08 = 1 (relay 1 designated normally energised)<br />

▲ Change Pr.09 = 0.7 (relay 1 set)<br />

▲ Change Pr.10 = 0.5 (relay 1 re-set)<br />

MODE to return to normal running.<br />

For a full description of parameter options refer to Section 4.<br />

Relay 1 Reset<br />

0.5 (Pr.10)<br />

Relay 1 Set<br />

0.7 (Pr.9)<br />

Note: The display does not show the decimal point until the first decimal figure is keyed in.