Programming Example<br />
MULTIFLEX MANUAL 12<br />
EDITION 2 : NOV 2000<br />
SECTION 2<br />
The following example shows how to continue programming from the previous stage to achieve a<br />
simple level application including setting a high alarm.<br />
1.5<br />
(Pr.3)<br />
0.5 (Pr.5)<br />
1.0 (Pr.4)<br />
Having changed the value in Pr.1 to 1 (level)<br />
Press ▲ Display Pr.02 = 2 (units in metres)<br />
▲ Change Pr.03 = 1.5 (empty distance)<br />
▲ Change Pr.04 = 1.0 (operational span)<br />
▲ Display Pr.05 = 0.5 (blanking distance)<br />
▲ Display Pr.06 = 1.0 (rate of change of level in metres)<br />
Press Pr.08 Change Pr.08 = 1 (relay 1 designated normally energised)<br />
▲ Change Pr.09 = 0.7 (relay 1 set)<br />
▲ Change Pr.10 = 0.5 (relay 1 re-set)<br />
MODE to return to normal running.<br />
For a full description of parameter options refer to Section 4.<br />
Relay 1 Reset<br />
0.5 (Pr.10)<br />
Relay 1 Set<br />
0.7 (Pr.9)<br />
Note: The display does not show the decimal point until the first decimal figure is keyed in.