Open Channel Flow Metering<br />
Pr.45 Flow exponent (D=1)<br />
Enter the required value for the open channel flow device being used.<br />
e.g. Flow Device Enter<br />
Unity 1<br />
Rect. flume 3/2 2<br />
Rect. weir 3/2 2<br />
V-notch weir 5/2 3<br />
Special 4 (Refer to Pr.44)<br />
Parshall Flumes 5-14 Request Appendix 4<br />
Pr.46 Maximum Flow Rate (D=0.00)<br />
Enter the maximum flow rate in units per second, per minute, per hour or per day,<br />
corresponding to maximum head, set at Pr.4 and then define the time base at Pr.47.<br />
Pr.47 Time Base of Maximum Flow Rate (D=1)<br />
Enter the value corresponding to the flow rate time base.<br />
Enter 1 = units per second<br />
2 = units per minute<br />
3 = units per hour<br />
4 = units per day<br />
Pr.48 Totaliser Display Conversion (D=0)<br />
MULTIFLEX MANUAL 26<br />
EDITION 2 : NOV 2000<br />
SECTION 4<br />
Used to totalise on the display in flow units larger than those entered at Pr.46 (max. flow<br />
rate).<br />
Enter 0 - Multiples by 1<br />
1 - Multiples by 0.1<br />
2 - Multiples by 0.01<br />
3 - Multiples by 0.001<br />
4 - Multiples by 0.0001<br />
5 - Multiples by 0.00001<br />
6 - Multiples by 0.000001<br />
7 - Multiples by 0.0000001<br />
e.g. If Pr.46 is entered as litres, at Pr.48 enter '3' to totalise the flow in<br />
cubic metres.<br />
Note:1. Up to 15 mins of totaliser data can be lost if the unit is powered down.<br />
2. On returning to RUN mode after accessing PROG, the totaliser will speed up<br />
initially to 'catch-up' with the totalised flow.