29.05.2013 Views

Burner System Management

Burner System Management

Burner System Management

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Set the air/fuel ratio curvepoints as described on chapter “Programming the LMV2x”<br />

Note: the other phases are<br />

Ph60 = operation (OP= in modulation)<br />

Ph62 = travelling to shutdown<br />

Ph70 = off but in prepurge after the burntime<br />

Ph72 = travelling to postpurging<br />

Ph74 = postpurge (countdown is displayed)<br />

Press ESC the parameter “546” (Setting the maximum load) is displayed<br />

Then press to exit the programming mode.<br />

The display will show:<br />

Press for a second time: the display will show the load percentage the burner is working at.<br />

When the generator reaches the programmed set-point, the burner will be in stand-by: the display will show<br />

22

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!