Error code Diagnostic code Meaning for LMV20.100A2BC system Recommended measures<br />
96 # Error relay supervision<br />
3 Ignition transformer Relay contacts have welded. Test the contacts:<br />
4 Fuel valve 1<br />
1. Unit connected to power: Fan output must be dead.<br />
5 Fuel valve 2<br />
2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral conductor<br />
allowed.<br />
6 Fuel valve 3<br />
If one of the 2 tests fails, release the unit since contact have definitively welded and safety can no longer be<br />
ensured<br />
97 # Error relay supervision<br />
0<br />
Safety relay contacts have welded or external power<br />
supply fed to safety relay<br />
Test the contacts: 1. Unit connected to power: Fan output must be dead.<br />
2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral conductor<br />
allowed. If one of the 2 tests fails, release the unit since contacts have definitively welded and safety can no<br />
longer be ensured.<br />
98 # Error relay supervision<br />
1 Ignition transformer Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />
3 Fuel valve 1 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />
4 Fuel valve 1 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />
5 Fuel valve 2 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />
6 Fuel valve 3 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />
99 # Internal error relay control Make a reset; if error occurs repeatedly, replace the unit<br />
100 # Internal error relay control Make a reset; if error occurs repeatedly, replace the unit<br />
105 # Internal error contact sampling<br />
1 Pressure switch min<br />
1 Pressure switch max<br />
2 Pressure switch valve proving test<br />
3 Air pressure<br />
4 Load controller open<br />
5 Load controller on/off<br />
6<br />
7<br />
Load controller closed<br />
Safety loop / <strong>Burner</strong> flange<br />
Stuck-At failure: Can be caused by capacitive loads or supply of DC voltage to the mains voltage inputs. The<br />
diag-nostic code indicates the input where the problem occurred<br />
8 Safety valve<br />
9 Ignition transformer<br />
10 Fuel valve 1<br />
11 Fuel valve 2<br />
12 Fuel valve 3<br />
13 Reset<br />
106 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />
107 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />
108 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />
C.I.B. UNIGAS - M12916CB