Error code Diagnostic code Meaning for LMV20.100A2BC system Recommended measures<br />

96 # Error relay supervision<br />

3 Ignition transformer Relay contacts have welded. Test the contacts:<br />

4 Fuel valve 1<br />

1. Unit connected to power: Fan output must be dead.<br />

5 Fuel valve 2<br />

2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral conductor<br />

allowed.<br />

6 Fuel valve 3<br />

If one of the 2 tests fails, release the unit since contact have definitively welded and safety can no longer be<br />

ensured<br />

97 # Error relay supervision<br />

0<br />

Safety relay contacts have welded or external power<br />

supply fed to safety relay<br />

Test the contacts: 1. Unit connected to power: Fan output must be dead.<br />

2. Disconnect power: Disconnect fan. No resistive connection between fan output and neutral conductor<br />

allowed. If one of the 2 tests fails, release the unit since contacts have definitively welded and safety can no<br />

longer be ensured.<br />

98 # Error relay supervision<br />

1 Ignition transformer Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />

3 Fuel valve 1 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />

4 Fuel valve 1 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />

5 Fuel valve 2 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />

6 Fuel valve 3 Relay does not pull in. Make a reset; if error occurs repeatedly, replace the unit<br />

99 # Internal error relay control Make a reset; if error occurs repeatedly, replace the unit<br />

100 # Internal error relay control Make a reset; if error occurs repeatedly, replace the unit<br />

105 # Internal error contact sampling<br />

1 Pressure switch min<br />

1 Pressure switch max<br />

2 Pressure switch valve proving test<br />

3 Air pressure<br />

4 Load controller open<br />

5 Load controller on/off<br />

6<br />

7<br />

Load controller closed<br />

Safety loop / <strong>Burner</strong> flange<br />

Stuck-At failure: Can be caused by capacitive loads or supply of DC voltage to the mains voltage inputs. The<br />

diag-nostic code indicates the input where the problem occurred<br />

8 Safety valve<br />

9 Ignition transformer<br />

10 Fuel valve 1<br />

11 Fuel valve 2<br />

12 Fuel valve 3<br />

13 Reset<br />

106 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />

107 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />

108 # Internal error contact request Make a reset; if error occurs repeatedly, replace the unit<br />