Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric
Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric
Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>XI</strong>/<strong>ON</strong> and fieldbus protocols<br />
12<br />
<strong>XI</strong>/<strong>ON</strong> and DeviceNet<br />
Bus system DeviceNet<br />
<strong>The</strong> open, low-end network, DeviceNet, is based<br />
on CAN technology.<br />
<strong>The</strong> communication profile used by <strong>XI</strong>/<strong>ON</strong><br />
contains:<br />
• UCMM<br />
• Offline Connection Set<br />
• Polled I/O<br />
• COS/Cyclic<br />
• Bitstrobe<br />
• Device Heartbeat Message<br />
• Device Shut Sown Message<br />
<strong>The</strong> user can select a master/slave, multi master<br />
or a combined configuration, depending on<br />
application requirements.<br />
Maximum bus length<br />
<strong>The</strong> DeviceNet specifications permit the use of<br />
two types of cable: thick and thin.<br />
Depending on the type of cable used, the<br />
following maximum bus lengths for the three<br />
possible transfer rates are possible:<br />
Baud rate<br />
(kBit/s)<br />
125<br />
250<br />
500<br />
Maximum system extension<br />
Max. distance between 2 stations<br />
100 % thick Cable<br />
500 m (1640 ft)<br />
250 m (820 ft)<br />
100 m (328 ft)<br />
<strong>The</strong> branches can be up to 6 m (20 ft) long, but<br />
the total extent of all branches depends on the<br />
baud rate.<br />
A DeviceNet bus line consists of a scanner and<br />
at least another bus station.<br />
<strong>The</strong> maximum number of 64 bus stations<br />
(including the scanner) must not be exceeded.<br />
Mixed operation with other devices<br />
Within a DeviceNet structure, <strong>XI</strong>/<strong>ON</strong> can be<br />
used in conjunction with standardized DeviceNet<br />
fieldbus devices from various manufacturers.<br />
Topology<br />
DeviceNet uses a full trunk / branch line<br />
topology with up to 64 nodes.<br />
100 % thin Cable<br />
100 m (328 ft)<br />
<strong>Moeller</strong> NK2725-1042 GB