16.06.2013 Views

Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric

Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric

Catalogue supplement XI/ON – The modular I/O ... - Moeller Electric

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>XI</strong>/<strong>ON</strong> and fieldbus protocols<br />

8<br />

<strong>XI</strong>/<strong>ON</strong> and PROFIBUS-DP<br />

Decentralized periphery<br />

Optimized for high speed, this PROFIBUS version<br />

is designed especially for communication<br />

between automation control systems and<br />

decentralized periphery devices. PROFIBUS-DP<br />

can be used to replace cost-intensive, parallel<br />

signal transmission from digital and analogue<br />

sensors and actuators. PROFIBUS-DP is based on<br />

DIN 19 245 Part 1 and Part 4. During the course<br />

of the European fieldbus standardization,<br />

PROFIBUS-DP has been included in the European<br />

fieldbus standard EN 50170.<br />

Maximum system extension without<br />

repeaters<br />

A PROFIBUS-DP bus line consists of at least a<br />

master and a slave. Without a repeater, a<br />

PROFIBUS-DP bus line can consist of up to 31<br />

slaves.<br />

<strong>The</strong> maximum number of 32 bus stations must<br />

not be exceeded without the use of a repeater!<br />

Maximum system extension with<br />

repeaters<br />

A maximum of 3 repeaters can be used within<br />

a PROFIBUS-DP structure. This increases the<br />

number of possible slaves to 122.<br />

<strong>The</strong> maximum number of 125 bus stations,<br />

including all slaves and repeaters, must not be<br />

exceeded!<br />

<strong>The</strong> PROFIBUS-DP addresses 000, 126 and 127<br />

are reserved and must not be used for <strong>XI</strong>/<strong>ON</strong>!<br />

Maximum bus length<br />

Baud rate<br />

(kBit/s)<br />

9.6<br />

187.5<br />

500<br />

1500<br />

3000<br />

12000<br />

max. length of a bus line<br />

without repeater (m)<br />

1200<br />

1000<br />

400<br />

200<br />

100<br />

100<br />

Topology<br />

Max. distance between two stations / cable type A<br />

(DIN 19 245 Part 3)<br />

PROFIBUS-DP communicates via a shielded<br />

twisted pair cable according to the RS 485<br />

standard. <strong>The</strong> network topology represents a<br />

linear structure with active bus termination on<br />

both ends.<br />

max. bus length<br />

with 3 repeaters (m)<br />

4800<br />

4000<br />

1600<br />

800<br />

400<br />

400<br />

<strong>Moeller</strong> NK2725-1042 GB<br />

<strong>The</strong> maximum bus length for PROFIBUS-DP<br />

depends on the transmission rate: Cable type<br />

Parameter<br />

Characteristic impedance<br />

Distributed capacitance<br />

Loop resistance<br />

Wire diameter<br />

Wire cross-section<br />

Terminating resistor<br />

Cable type A<br />

DIN 19 245 Part 3<br />

135 to 165 Ω<br />

(3 to 20 MHz)<br />

< 30 nF/km<br />

< 110 Ω/km<br />

> 0.64 mm<br />

> 0.34 mm 2<br />

220 Ω

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!