20<br />

Functions<br />

Cable 3: Stop dosing input and dosing monitor or dosing output<br />

Useful when the load (e.g. a relay) has one side<br />

connected to a power supply which is not the same one<br />

as connected to the sensor.<br />

When the dosing output is activated, the output<br />

provides the Gnd to the load.<br />

Recommended supply: max. 24 VDC.<br />

Max. current: 100 mA.<br />

Cable 4: Level input<br />

DME and DMS<br />

Number/colour<br />

Function<br />

1/brown 2/white<br />

Plug<br />

3/blue, +5V 4/black, GND 5/grey<br />

Type<br />

Stop input X X Contact<br />

Stop input 5V GND Supply 5V DC<br />

Dosing monitoring X X Contact<br />

Dosing monitoring GND 5V Supply 5V DC<br />

Dosing output<br />

(pump running)<br />

Open collector * NPN<br />

* Open collector can be used for a relay or a lamp.<br />

Number/colour<br />

Function<br />

1/brown 2/white<br />

Plug<br />

3/blue, +5V 4/black, GND 5/grey<br />

Type<br />

Low level X* X* Contact<br />

Low level 5V GND Supply 5V DC<br />

Empty tank X* X* Contact<br />

Empty tank 5V GND Supply 5V DC<br />

* The function for the potential free contact set can be chosen from the display (NO=Normally Open and NC=Normally Closed).