GRUNDFOS DATA BOOKLET<br />
DME and DMS<br />
DIGITAL DOSING
2<br />
Contents<br />
General data<br />
Performance range, DME 3<br />
Performance range, DMS 3<br />
DME and DMS 4<br />
Digital Dosing 4<br />
Type key 5<br />
Codes 5<br />
Functions<br />
Overview of functions 6<br />
Performance range 7<br />
Functional description, DME 8<br />
Functional description, DMS 8<br />
Control panel 9<br />
Menu 11<br />
Operating modes 12<br />
Dosing monitoring 16<br />
Control panel lock 17<br />
Wiring diagram, DME and DMS-A (0-48 l/h) 18<br />
Wiring diagram, DME (60-940 l/h) 19<br />
Construction<br />
Sectional drawing, DME (0-48 l/h) 21<br />
Material specification 21<br />
Sectional drawing, DME (60-940 l/h) 22<br />
Material specification 22<br />
Sectional drawing, DMS 23<br />
Material specification 23<br />
Dimensions<br />
Front-fitted control panel (0-48 l/h) 24<br />
Side-fitted control panel (0-48 l/h) 24<br />
Front-fitted control panel, DME (60-940 l/h) 25<br />
Technical data<br />
DME (0-48 l/h) 26<br />
DME (60-940 l/h) 27<br />
DMS 28<br />
Pump selection<br />
Standard range, DME (0-48 l/h) 29<br />
Non-standard range, DME (0-48 l/h) 30<br />
Standard range, DME (60-940 l/h) 31<br />
Non-standard range, DME (60-940 l/h) 33<br />
Standard range, DMS 34<br />
Non-standard range, DMS 36<br />
Pumped liquids<br />
List of pumped liquids 37<br />
<strong>Accessories</strong><br />
38
General data<br />
Performance range, DME<br />
p<br />
[bar]<br />
18<br />
16<br />
14<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
1 2.5 7.5 12 18.5 48 60 150 250 376 940<br />
Q [l/h]<br />
Performance range, DMS<br />
p<br />
[bar]<br />
11<br />
10<br />
9<br />
8<br />
7<br />
6<br />
5<br />
4<br />
3<br />
2<br />
1<br />
0<br />
DME 2-18<br />
DMS 2-11<br />
DME 8-10<br />
DMS 4-7<br />
DME DME<br />
12-6 19-6<br />
DME 60-10 DME 375-10<br />
DMS 8-5<br />
DME 48-3<br />
DME<br />
DME 150-4 DME 940-4<br />
DMS 12-3<br />
DMS<br />
0 1 2 3 4 5 6 7 8 9 10 11 12 13<br />
Q [l/h]<br />
DME and DMS<br />
TM027811mance ranges, 50 an<br />
TM027810<br />
3
4<br />
General data<br />
DME and DMS<br />
Digital Dosing<br />
Digital Dosing represents state-of-the-art technology.<br />
This patented Grundfos solution sets new standards,<br />
including new principles and methods.<br />
Precise and easy setting<br />
The operator can easily install and set the pump to<br />
discharge exactly the quantity of dosing liquid required<br />
in the application. In the display, the setting of the pump<br />
is read out directly in ml/h or l/h, pulse or batch, and the<br />
operation mode is easily identified by means of icons.<br />
Unique technology<br />
A unique drive and microprocessor control ensure that<br />
dosing liquids are discharged precisely and with low<br />
pulsation even when the pump is operating with high<br />
viscosity or degassing liquids. Instead of the conventional<br />
stroke length adjustment, the capacity of the<br />
DME is regulated by automatic ajustment of the motor<br />
speed during the discharge stroke and by fixed suction<br />
stroke speed, ensuring optimal and uniform mixing. The<br />
capacity of the DMS is regulated by automatic regulation<br />
of the stroke frequency.<br />
GR7777r<br />
DME and DMS<br />
Fewer variants to cover all needs<br />
The powerful variable speed motor, a turn-down ratio of<br />
1:1000/1:800 and a complete control interface including<br />
• full pulse control,<br />
• pulse batch control,<br />
• internal timer batch control,<br />
• analog 0/4-20 mA control,<br />
• level control and<br />
• fieldbus communication module<br />
ensure that nine DME pumps cover the range from 0 to<br />
940 litres per hour up to 18 bar. The switch mode power<br />
supply ensures that the same pump is working<br />
precisely, irrespective of the mains supply (100-240 V;<br />
50-60 Hz).<br />
The DMS version with synchronous motor and a turndown<br />
ratio of 1:100 (consisting of four pump sizes and<br />
two control versions) cover the range from 0 to 12 l/h.<br />
The DMS-A pumps have external pulse, analog 4-20<br />
mA and level control interface; the DMS-B version is<br />
without external control interface. The DMS-D is<br />
without control and user interface.<br />
The DME and DMS dosing pumps feature diaphragm<br />
dosing head with integrated vent valve, suction and<br />
discharge ball valves.<br />
The pumps are fitted with power cable and plug.<br />
See page 5 and onwards for further information.
General data<br />
Type key Codes<br />
Example DME 2 - 18 A - PP / E / C - F - 1 1 1G F<br />
Type range<br />
Maximum capacity [l/h]<br />
Maximum pressure [bar]<br />
Code for control variant<br />
Code for dosing head material<br />
Code for gasket material<br />
Code for valve ball material<br />
Code for control panel position<br />
Code for supply voltage<br />
Code for valves<br />
Code for connection suction/discharge<br />
Code for mains plug<br />
DME and DMS<br />
Example<br />
Control variant<br />
A<br />
AR A + alarm relay<br />
AP A + Profibus<br />
AG A + GENIbus<br />
A - PP / E / C - F - 1 1 1 F<br />
B Basic<br />
D Only on/off<br />
Dosing head material<br />
PP Polypropylene<br />
PV PVDF<br />
SS Stainless steel<br />
Gasket material<br />
E EPDM<br />
T PTFE<br />
V FKM<br />
Valve ball material<br />
C Ceramic<br />
SS Stainless steel 1.4401<br />
G Glass<br />
T PTFE<br />
Y Hastelloy C-22<br />
Control panel position<br />
F Front-fitted<br />
S Side-fitted<br />
X No control panel<br />
Supply voltage<br />
1 1 x 230 V, 50 Hz<br />
2 1 x 120 V, 60 Hz<br />
3 1 x 100-240 V, 50-60 Hz<br />
6 1 x 110 V, 50 Hz<br />
8 1 x 100 V, 50/60 Hz<br />
9 1 x 200 V, 50/60 Hz<br />
Valves<br />
1 Standard valve<br />
2 Spring-loaded valve<br />
Connection suction/discharge<br />
Tubing 6/9 mm<br />
1 Tubing 4/6 mm<br />
supplied with the pump<br />
Tubing 6/9 mm<br />
2 Tubing 6/12 + 9/12 mm<br />
supplied with the pump<br />
3 Tubing 4/6 mm<br />
4 Tubing 6/9 mm<br />
5 Tubing 6/12 mm<br />
6 Tubing 9/12 mm<br />
T Tubing 0.17"/0.25"<br />
R Tubing 0.25"/0.375"<br />
S Tubing 0.375"/0.5"<br />
A Threaded Rp 1/4<br />
B Threaded Rp 3/8<br />
V Threaded NPT 1/4"<br />
Y Threaded NPT 3/8"<br />
E Cementing d.10 mm<br />
F Cementing d.12 mm<br />
Q Tubing 19/27 + 25/34<br />
W Tubing 32/41 + 38/48<br />
A1 Threaded Rp 3/4"<br />
A2 Threaded Rp 1 1/4"<br />
Mains plug<br />
F EU (Schuko)<br />
B USA, Canada (120 V)<br />
G UK<br />
I Australia<br />
E Switzerland<br />
J Japan<br />
5
6<br />
Functions<br />
Overview of functions<br />
DME DMS<br />
DME and DMS<br />
0-48 l/h 60-940 l/h AR 60-940 l/h B variant A variant B variant D<br />
TM01 8941 0900<br />
Capacity control, see page 7<br />
Internal stroke frequency<br />
control<br />
<br />
Internal stroke speed control<br />
Control panel, see page 9<br />
<br />
Capacity setting in litres,<br />
millilitres or US gallons<br />
<br />
Display with background light<br />
and soft-touch buttons<br />
<br />
Easy set-up menu with<br />
language options<br />
<br />
On/off button <br />
Maximum capacity button<br />
(priming)<br />
<br />
Green indicator light for<br />
operating indication<br />
<br />
Red indicator light for<br />
fault indication<br />
<br />
Control panel lock <br />
Side-fitted as an option<br />
Operating modes, see page 12<br />
<br />
Manual control <br />
Pulse control <br />
Analog 0/4-20 mA control <br />
Timer-based batch control <br />
Pulse-based batch control<br />
Functions, see page 15<br />
<br />
Dosing monitoring <br />
Dual-level control <br />
Calibration of pump to actual<br />
installation<br />
<br />
Anti-cavitation<br />
(reduced suction speed)<br />
<br />
Capacity limitation <br />
Counters for strokes, operating<br />
hours and power on/off<br />
<br />
Fieldbus communication <br />
Overload protection <br />
Error message in display <br />
Leakage sensor <br />
Dosing signal output<br />
Power supply, page 15<br />
<br />
Switch-mode power supply<br />
Inputs/outputs, see page 18<br />
<br />
Input for pulse control <br />
Input for analog 0/4-20 mA<br />
control<br />
<br />
Input for dual-level control <br />
Input for external start/stop <br />
Alarm relay output (variant AR) <br />
Dosing output <br />
Input for external on/off switch <br />
TM02 8337 4903<br />
TM02 8338 4903<br />
TM01 8941 0900<br />
TM01 8943 0900<br />
TM02 8973 1304
Functions<br />
Performance range<br />
p<br />
[bar]<br />
18<br />
16<br />
14<br />
12<br />
10<br />
8<br />
6<br />
4<br />
2<br />
0<br />
DME 2-18<br />
DMS 2-11<br />
DME 8-10<br />
DMS<br />
4-7<br />
DMS<br />
8-5<br />
DME DME<br />
12-6 19-6<br />
DMS<br />
12-3<br />
DME 60-10 DME 375-10<br />
DME 48-3<br />
1 2.5 4 7.5 12 18.5 48 60 150 376 940<br />
Q [l/h]<br />
The maximum capacity is available at any counter-pressure<br />
if the pump has been calibrated to the actual installation.<br />
DMS, DME<br />
DME 150-4 DME 940-4<br />
DME and DMS<br />
TM02 7812 4103<br />
7
8<br />
Functions<br />
Functional description, DME<br />
The electronically controlled variable-speed motor of<br />
the DME pumps provides optimum control of the stroke<br />
speed. As shown in the figure below, the duration of<br />
each suction stroke is constant while the duration of<br />
each discharge stroke varies according to the capacity<br />
set, resulting in optimum discharge flow in any operating<br />
situation.<br />
The advantages are as follows:<br />
• The pump is always operating at full stroke length,<br />
irrespective of the capacity set, for optimum accuracy,<br />
priming and suction.<br />
• A capacity range of 1:1000 (0-48 l/h) for each pump<br />
size.<br />
Capacity<br />
setting<br />
100%<br />
50%<br />
10%<br />
Discharge<br />
Discharge<br />
Discharge<br />
Functional description, DMS<br />
The electronically controlled synchronous motor of the<br />
DMS pumps offers almost the same advantages as<br />
those of DME pumps. As shown in the figure below, the<br />
suction and discharge stroke speeds are constant while<br />
the stroke frequency varies according to the capacity<br />
set. The sinusoidal movement of the diaphragm offers<br />
the following advantages:<br />
• The pump is always operating at full stroke length,<br />
irrespective of the capacity set, for optimum accuracy,<br />
priming and suction.<br />
Capacity<br />
Discharge<br />
setting<br />
100%<br />
50%<br />
10%<br />
Suction<br />
Suction<br />
Suction<br />
Suction<br />
Discharge<br />
Suction<br />
Discharge<br />
Suction<br />
DME and DMS<br />
• A capacity range of 1:800 (60-940 l/h) for each<br />
pump size.<br />
• Even and constant dosing ensuring an optimum<br />
mixing ratio at the injection point.<br />
• Significant reduction of pressure surges, preventing<br />
mechanical stress on diaphragm, tubes, connections<br />
and other dosing parts exposed to leakage<br />
and wear.<br />
• The installation is less affected by long suction and<br />
discharge lines.<br />
• Easier dosing of highly viscous and gas-containing<br />
liquids.<br />
The optimum dosing control shown below takes place<br />
in any operating mode.<br />
duration<br />
duration<br />
duration<br />
• A capacity range of 1:100 for each pump size.<br />
• Reduction of pressure surges, preventing mechanical<br />
stress on diaphragm, tubes, connections and<br />
other dosing parts exposed to leakage and wear.<br />
• The installation is less affected by long suction and<br />
discharge lines.<br />
• Easier dosing of highly viscous and gas-containing<br />
liquids.<br />
duration<br />
duration<br />
duration<br />
TM01 8944 0900<br />
TM01 8945 0900
Functions<br />
Control panel<br />
LCD Display<br />
Menu/<br />
accept<br />
Navigation/<br />
settings<br />
Priming button<br />
Control panel fitted to the front.<br />
Control panel fitted to the side (not DMS-B).<br />
Priming button<br />
100%<br />
The pump control panel incorporates a 100% button.<br />
Press this button if the maximum capacity is required<br />
over a short period, e.g. during start-up. When the<br />
button is released, the pump automatically returns to<br />
the previous operating mode.<br />
When the buttons 100% and are pressed simultaneously,<br />
the pump can be set to run for a specific number<br />
of seconds at maximum capacity. The remaining<br />
numbers of seconds will appear in the display. This<br />
feature is useful when flushing the pump. The<br />
maximum value is 300 seconds.<br />
Press to stop the pump before the set time has<br />
passed.<br />
ml/h<br />
Navigation/<br />
settings<br />
Green<br />
indicator light<br />
Red<br />
indicator light<br />
On/off button<br />
TM01 8946 1202<br />
TM01 8941 0900<br />
TM01 8949 0900<br />
DME and DMS<br />
Indicator lights and alarm output (0-48 l/h)<br />
The green and red indicator lights on the pump indicate<br />
operation or fault.<br />
In control variant AR, the pump can activate an external<br />
alarm signal by means of a built-in alarm relay. The<br />
alarm signal is activated by means of an internal potential-free<br />
contact.<br />
The functions of the indicator lights and the built-in<br />
alarm relay appear from the table below.<br />
Condition<br />
Green<br />
LED<br />
Pump running On Off<br />
Set to stop Flashing Off<br />
Red LED Display<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
Pump fault Off On EEPROM<br />
Supply failure Off Off Off<br />
Pump running, low<br />
chemical level 1 On On<br />
Empty tank 2 Off On<br />
Analog signal<br />
< 2 mA<br />
The pump is not dosing<br />
enough according to the<br />
signal from the dosing<br />
monitor 3<br />
Off On<br />
On On<br />
More pulses than capacity On On<br />
Overheated Off On<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
MAX<br />
TEMP<br />
1 Control variant AR, only.<br />
2 Requires connection to level sensors.<br />
3 Requires dosing monitor function activated and a dosing<br />
monitor device connected to the pump.<br />
Alarm<br />
output 1<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
9
10<br />
Functions<br />
Indicator lights and alarm output (60-940 l/h)<br />
Condition<br />
Green<br />
LED<br />
Red<br />
LED<br />
Pump running On Off<br />
Set to stop Flashing Off<br />
Display<br />
Normal<br />
indication<br />
Normal<br />
indication<br />
Pump fault Off On EEPROM<br />
Supply failure Off Off Off<br />
Pump running, low<br />
chemical level<br />
On On LOW<br />
Empty tank 2 Off On EMPTY<br />
Analog signal < 2 mA Off On NO mA<br />
The dosed quantity is too<br />
small according to the<br />
signal from the dosing<br />
monitor 3<br />
On Off<br />
Overheating Off On<br />
Internal communication<br />
failure<br />
Off On<br />
NO<br />
FLOW<br />
MAX<br />
TEMP<br />
INT<br />
COM<br />
Internal Hall Failure 4 Off On HALL<br />
Diaphragm failure<br />
(leakage) 5 Off On LEAKAGE<br />
Max. pressure<br />
exceeded 5 Off 6 On<br />
More pulses than<br />
capacity<br />
On On<br />
OVER-<br />
LOAD<br />
MAX<br />
FLOW<br />
No detection of<br />
motor rotation 4 On On ORIGO<br />
Alarm<br />
output1<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 2 3<br />
NC NO C<br />
1 Control variant AR, only.<br />
2 Requires connection to level sensors.<br />
3 Requires activation of the dosing monitoring function and<br />
connection to a dosing monitor.<br />
4 Please contact a Grundfos service centre.<br />
5 Alarms can be reset after fault conditions are back to normal.<br />
6 The pump will make 10 attempts to restart before going into<br />
permanent off mode.<br />
DME and DMS
Functions<br />
Menu<br />
The DME and DMS dosing pumps feature a userfriendly<br />
menu which is activated by pressing the<br />
button. During start-up, all texts will appear in the<br />
English language, but other languages can be chosen,<br />
see page 14.<br />
The example shown below applies to DME pumps.<br />
<br />
<br />
<br />
Applies only to DME, 60-940 l/h pumps.<br />
mA<br />
DME and DMS<br />
D68se<br />
11
12<br />
Functions<br />
Operating modes<br />
Manual control<br />
The pump is dosing constantly according to the quantity<br />
set in l/h or ml/h by means of the buttons and .<br />
It automatically changes over between the measuring<br />
units.<br />
Setting range, DME:<br />
DME 2: 2.5 ml/h - 2.5 (1.8) l/h<br />
DME 8: 7.5 ml/h - 7.5 (5.6) l/h<br />
DME 12: 12 ml/h - 12 (9) l/h<br />
DME 19: 18,5 ml/h - 18.5 (14.5) l/h<br />
DME 48: 48 ml/h - 48 (37) l/h<br />
DME 60: 75 ml/h - 60 l/h<br />
DME<br />
150:<br />
200 ml/h - 150 l/h<br />
DME<br />
375:<br />
500 ml/h - 376 l/h<br />
DME<br />
940:<br />
1200 ml/h - 940 l/h.<br />
The figures in brackets indicate the maximum<br />
capacity when the anti-cavitation function is activated.<br />
Setting range, DMS:<br />
DMS 2: 25 ml/h - 2.5 l/h<br />
DMS 4: 40 ml/h - 4 l/h<br />
DMS 8: 75 ml/h - 7.5 l/h<br />
DMS 12: 120 ml/h - 12 l/h.<br />
Pulse control<br />
Applies to DME and DMS-A<br />
The pump is dosing according to an external pulse<br />
signal, e.g. from a water meter.<br />
There is no direct relation between pulses and dosing<br />
strokes. The pump automatically calculates its optimal<br />
speed to ensure the required quantity is dosed for each<br />
pulse. The quantity to be dosed is set in ml/pulse. The<br />
pump adjusts its speed and/or stroke frequency<br />
according to two factors:<br />
• frequency of external pulses and<br />
• the set quantity per pulse.<br />
Setting range, DME:<br />
DME 2-18: 0.000023 ml/pulse - 5.0 ml/pulse<br />
DME 8-10: 0.000069 ml/pulse - 15.0 ml/pulse<br />
DME 12-6: 0.000111 ml/pulse - 24.0 ml/pulse<br />
DME 19-6: 0.000204 ml/pulse - 37.0 ml/pulse<br />
DME 48-3: 0.000530 ml/pulse - 96.0 ml/pulse<br />
DME 60-10: 0.000625 ml/pulse - 120 ml/pulse<br />
DME 150-4: 0.00156 ml/pulse - 300 ml/pulse<br />
DME 375-10:0.00392 ml/pulse - 750 ml/pulse<br />
DME 940-4: 0.00980 ml/pulse - 1880 ml/pulse.<br />
DME and DMS<br />
Setting range, DMS:<br />
DMS 2: 0.00232 ml/pulse - 50 ml/pulse<br />
DMS 4: 0.00370 ml/pulse - 80 ml/pulse<br />
DMS 8: 0.00695 ml/pulse - 150 ml/pulse<br />
DMS 12: 0.01110 ml/pulse - 240 ml/pulse<br />
Analog 4-20 mA control<br />
Applies to DME and DMS-A<br />
The pump is dosing according to an external analog<br />
signal. The dosed capacity is proportional to the input<br />
value in mA.<br />
4-20 (default): 4 mA = 0%<br />
20 mA = 100%<br />
20-4: 4 mA = 100%<br />
20 mA = 0%<br />
0-20: 0 mA = 0%<br />
20 mA = 100%<br />
20-0: 0 mA = 100%<br />
20 mA = 0%.<br />
The maximum capacity limitation, see page 13, will<br />
influence the capacity. 100% (20 mA) corresponds to<br />
the maximum capacity or the set capacity limitation.<br />
Maximum capacity [%]<br />
100<br />
80<br />
60<br />
40<br />
20<br />
0<br />
0 4 8 12 16 20<br />
Input signal [mA]<br />
Timer-based batch control<br />
4-20 mA signal<br />
signal<br />
Applies to DME<br />
The pump is dosing the set quantity in batches at<br />
maximum capacity or the set capacity limitation.<br />
The time until the first dosing (NX) and the following<br />
sequences (IN) can be set in minutes, hours and days.<br />
The maximum time limit is 9 days, 23 hours and 59<br />
minutes (9:23:59) The lowest acceptable value is one<br />
minute. IN must be higher than the time required to<br />
perform one batch. If IN is lower than the time required,<br />
the next batch will be ignored.<br />
In case of supply failure, the set dosing quantity, the IN<br />
time and the remaining NX time are stored. When the<br />
supply is reconnected, the pump will start up with the<br />
NX time at the time of the supply failure. This way the<br />
timer cycle will continue, but it will be delayed according<br />
TM01 8218 0100
Functions<br />
to the time of the supply failure.<br />
NX<br />
Setting range:<br />
DME 2: 0.23 ml/batch - 5 l/batch<br />
DME 8: 0.69 ml/batch - 15 l/batch<br />
DME 12: 1.11 ml/batch - 24 l/batch<br />
DME 19: 2.04 ml/batch - 37 l/batch<br />
DME 48: 5.3 ml/batch - 96 l/batch<br />
DME 60: 6.25 ml/batch - 120 l/batch<br />
DME 150: 15.6 ml/batch - 300 l/batch<br />
DME 375: 39.1 ml/batch - 750 l/batch<br />
DME 940: 97.9 ml/batch - 1880 l/batch.<br />
Pulse-based batch control<br />
Applies to DME<br />
The pump is dosing the set quantity in batches at<br />
maximum capacity or the set capacity limitation. The<br />
quantity is dosed every time the pump receives an<br />
external pulse. If the pump receives new pulses before<br />
the batch is completed, these pulses will be ignored.<br />
Setting range:<br />
DME 2: 0.23 ml/batch - 5 l/batch<br />
DME 8: 0.69 ml/batch - 15 l/batch<br />
DME 12: 1.11 ml/batch - 24 l/batch<br />
DME 19: 2.04 ml/batch - 37 l/batch<br />
DME 48: 5.3 ml/batch - 96 l/batch<br />
DME 60: 6.25 ml/batch - 120 l/batch<br />
DME 150: 15.6 ml/batch - 300 l/batch<br />
DME 375: 39.1 ml/batch - 750 l/batch<br />
DME 940: 97.9 ml/batch - 1880 l/batch.<br />
Pulse<br />
Quantity pr. batch<br />
IN<br />
Quantity pr. batch<br />
Pulse<br />
t<br />
t<br />
TM01 8942 0900<br />
TM01 8947 0900<br />
DME and DMS<br />
Anti-cavitation (0-48 l/h)<br />
Applies to DME<br />
When this function is selected, the pump extends and<br />
smooths its suction stroke, resulting in softer priming.<br />
The anti-cavitation function is used:<br />
• when pumping liquids of high viscosity<br />
• when pumping degassing liquids<br />
• in the case of a long suction tube and<br />
• in the case of a high suction lift.<br />
The maximum capacity is reduced when this function is<br />
selected, see below.<br />
DME 2: 1.8 l/h<br />
DME 8: 5.6 l/h<br />
DME 12: 9 l/h<br />
DME 19: 14.5 l/h<br />
DME 48: 37 l/h.<br />
Anti-cavitation (60-940 l/h)<br />
The pump features an anti-cavitation function. When<br />
this function is selected, the pump extends and<br />
smoothes its suction stroke, resulting in softer priming.<br />
The anti-cavitation function is used:<br />
• when pumping liquids of high viscosity,<br />
• in the case of a long suction tube and<br />
• in the case of a high suction lift.<br />
Depending on the circumstances, during the suction<br />
stroke, the motor speed can be reduced by 75%, 50% or<br />
25% compared to the normal motor speed during the<br />
suction stroke.<br />
The maximum pump capacity is reduced when the anticavitation<br />
function is selected.<br />
Maximum capacity limitation<br />
Applies to DME<br />
This function offers the possibility of reducing the<br />
maximum capacity (MAX. CAP). It influences the functions<br />
in which the pump is normally operating at<br />
maximum capacity. Under normal operating conditions,<br />
the pump cannot operate at a capacity higher than the<br />
one stated in the display. This does not apply to the<br />
priming button.<br />
By means of this function, a large pump can be set to<br />
act as a much smaller pump. Together with the 1:1000/<br />
1:800 capacity range, the purposes of this function are:<br />
13
14<br />
Functions<br />
1. To utilize the smooth and even dosing characteristics<br />
of the pump at low capacities, to achieve<br />
– improved chemical mixing,<br />
– improved dosing through long discharge tubes and<br />
– improved dosing of high-viscous liquids.<br />
2. To improve the dosing of gas-containing liquids: In a<br />
large pump, as compared to a small pump, the displaced<br />
volume (1) is much larger than the non-displaced<br />
volume (2).<br />
2<br />
Small pump Large pump<br />
3. To cover several needs with just one pump size.<br />
4. To adapt the pump to a 4-20 mA signal control with<br />
4 mA corresponding to 0% and 20 mA to the set<br />
maximum capacity.<br />
In this way it is possible for instance to use a DME 48<br />
for dosing a very small quantity of liquid without<br />
changing the input signal. See example below.<br />
Example:<br />
A DME 48 receives a 12 mA input signal from a control<br />
instrument, resulting in a 50% output (according to the<br />
analog curve on page 12) and a capacity of 24 l/h. A<br />
new situation occurs where it is only necessary to dose<br />
2 l/h. The maximum capacity limitation is set to 4 l/h.<br />
The pump is still receiving a 12 mA signal resulting in a<br />
50% output and a capacity of 2 l/h.<br />
Q [l/h]<br />
48<br />
44<br />
40<br />
36<br />
32<br />
28<br />
24<br />
20<br />
16<br />
12<br />
8<br />
4<br />
0<br />
2<br />
1<br />
No cap. limitation<br />
The maximum capacity limitation will also reduce the<br />
pump speed in timer-based batch control, pulse-based<br />
batch control and during calibration where the pump is<br />
usually operating at maximum capacity.<br />
Calibration<br />
After start-up, the dosing pumps can be calibrated for<br />
the actual installation to ensure that the displayed value<br />
(millilitres or litres) is correct. A calibration program in<br />
the set-up menu facilitates calibration.<br />
1<br />
No cap. limitation<br />
Cap. limit. = 4 l/h<br />
0 4 8 12 16 20<br />
[mA]<br />
Cap. limit. = 4 l/h<br />
TM02 0158 3301<br />
TM01 9638 2700<br />
Counters<br />
DME and DMS<br />
The pump can display "non-resettable" counters for:<br />
• "Quantity"<br />
Accumulated dosed quantity in litres or US gallons.<br />
• "Strokes"<br />
Accumulated number of dosing strokes.<br />
• "Hours"<br />
Accumulated number of operating hours (power on).<br />
• "Power ON"<br />
Accumulated number of times the mains supply has<br />
been switched on.<br />
Languages<br />
The display text can be displayed in one of the following<br />
languages chosen in the set-up menu:<br />
• English<br />
• German<br />
• French<br />
• Italian<br />
• Spanish<br />
• Portuguese<br />
• Dutch<br />
• Swedish<br />
• Suomi<br />
• Danish<br />
• Czech<br />
• Slovak<br />
• Polish<br />
• Russian.<br />
Integrated venting valve<br />
The DME and DMS dosing pumps are provided with an<br />
integrated vent valve. The valve makes it very easy to<br />
prime the pump during start-up:<br />
The vent valve must be connected to the tank by means<br />
of a 4/6 mm PVC tubing.<br />
Vent valve<br />
TM01 8420 5099
Functions<br />
The vent valve must be connected to the tank by means<br />
of a 15/20 mm PVC tubing.<br />
DME 60-940 l/h<br />
Switch-mode power supply<br />
Applies to DME<br />
The DME pump is incorporates a switch-mode power<br />
supply. This makes the pump independent of variations<br />
in supply voltage and frequency. Operating range: 1 x<br />
100-240 V, 50-60 Hz.<br />
Level control<br />
Applies to DME and DMS-A<br />
The pump can be connected to a level control unit for<br />
monitoring of the chemical level in the tank.<br />
The pump can react to two level signals. The following<br />
table shows the pump reactions to the sensor signals:<br />
Level sensors Pump reaction<br />
Upper sensor activated<br />
Vent valve<br />
• Red indicator light is on.<br />
• Pump running.<br />
• Alarm relay activated.<br />
• Red indicator light is on.<br />
Lower sensor activated • Pump stopped.<br />
• Alarm relay activated.<br />
Applies to control variant AR<br />
Bus communication<br />
Applies to DME<br />
The pump is available with a built-in module for bus<br />
communication with GENIbus (variant AG, up to 48 l/h<br />
only) or PROFIBUS DP (variant AP) systems. These<br />
modules enable remote monitoring and setting via the<br />
fieldbus system.<br />
All DME features are available via bus communication.<br />
The PROFIBUS GDS-file can be downloaded from<br />
www.grundfos.com/dosing.<br />
Diaphragm leakage sensor (60-940 l/h)<br />
The pump can be fitted with a diaphragm leakage<br />
sensor. The sensor will detect leakage of the<br />
diaphragm. The sensor should be connected to the<br />
drain hole of the pump head. In case of leakage of the<br />
diaphragm, the signal from the sensor generates an<br />
alarm in the pump and the alarm relay will be activated.<br />
See page 41.<br />
TM02 7066 2503<br />
DME and DMS<br />
15
16<br />
Functions<br />
Dosing monitoring<br />
Applies to all DME and DMS-A(R) (0-48 l/h)<br />
Dosing stoke measured<br />
Monitor mounted on suction side<br />
(DME and DMS)<br />
The dosing monitor is designed to monitor the dosing of<br />
liquids which may cause gas accumulation in the<br />
dosing head, thus stopping the dosing process even if<br />
the pump is still operating.<br />
For every measured dosing stroke, the dosing monitor<br />
gives a pulse signal to the level input so that the pump<br />
can compare performed pump strokes (from internal<br />
stroke sensor) with externally measured physical<br />
strokes (from the dosing monitor). If an external dosing<br />
stroke is not measured together with the internal dosing<br />
stroke, this is considered a fault that may have been<br />
provoked by empty tank or gas in the dosing head.<br />
When used together with a DME pump, the monitor will<br />
only operate if it is mounted on the suction side of the<br />
pump.<br />
When used together with a DMS pump, the monitor will<br />
also operate if it is mounted on the discharge side of the<br />
pump.<br />
The dosing monitor should be connected to the level<br />
input (pins 2 and 3). This input must be configured to<br />
dosing monitoring. Consequently, it cannot be used as<br />
level input.<br />
Once the input has been set for dosing monitoring and<br />
a dosing monitor has been connected and set, the<br />
dosing monitoring function will be active.<br />
Definitions:<br />
• Correct dosing stroke: A pulse from the dosing monitor<br />
corresponds to the internal stroke signal within<br />
acceptable time.<br />
• Incorrect dosing stroke: There is no pulse from the<br />
dosing monitor corresponding to the internal stroke<br />
signal within the acceptable time (the pump is not<br />
pumping).<br />
Dosing stoke measured<br />
Monitor mounted on discharge side<br />
(DMS only)<br />
Dosing stoke measured<br />
DME and DMS<br />
Monitor mounted in dosing tube.<br />
In discharge tube: DMS (in-line)<br />
In suction tube: DME and DMS (in-line)<br />
Logic:<br />
If two incorrect dosing strokes are performed, the pump<br />
will continue operating, but it will change over to alarm<br />
mode. The red indicator light will be on and the alarm<br />
output, if any, will be activated (variant AR).<br />
For each correct stroke the counter is reset and the<br />
alarm output, if any, is deactivated.<br />
Operation in connection with vent valve:<br />
It is possible to add a self-acting solution for liquids that<br />
cause gas accumulation by using an automatic vent<br />
valve. The solution is the dosing monitor with a pump<br />
and an alarm output (control variant AR). The alarm<br />
output thus activates the vent valve, which will automatically<br />
vent gas accumulated in the dosing head. When<br />
the dosing head has been vented, the pump will start<br />
pumping again, the alarm output will be deactivated<br />
and the vent valve will close.<br />
TM02 2029 3201 - TM02 2030 3201 - TM02 2031 3201<br />
TM02 2048 4802
Functions<br />
Control panel lock<br />
It is possible to lock the buttons on the control panel to<br />
prevent maloperation of the pump. The locking function<br />
can be set to "ON" or "OFF". The default setting is<br />
"OFF".<br />
A PIN code must be entered to change from "OFF" to<br />
"ON". When "ON" is selected for the first time, "_ _ _ _"<br />
will appear in the display. If a code has already been<br />
entered, it will appear when an attempt to change to<br />
"ON" is made. This code can either be re-entered or<br />
changed.<br />
Units<br />
It is possible to select metric units (litre/millilitre) and<br />
US units (gallons/millilitre).<br />
Metric measuring units:<br />
• In manual and analog modes, set the quantity to be<br />
dosed in litres per hour (l/h) or millilitres per hour<br />
(ml/h).<br />
The drawing above shows all possible settings.<br />
3 x<br />
DME and DMS<br />
• In pulse mode, set the quantity to be dosed in ml/<br />
pulse. The actual capacity is indicated in litres per<br />
hour (l/h) or millilitres per hour (ml/h).<br />
• For calibration, set the quantity to be dosed in ml<br />
per 100 strokes.<br />
• In timer and batch modes, set the quantity to be<br />
dosed in litres (l) or millilitres (ml).<br />
• Under the "QUANTITY" menu item in the<br />
"COUNTERS" menu, the dosed quantity is indicated<br />
in litres.<br />
US measuring units:<br />
• In manual and analog modes, set the quantity to be<br />
dosed in gallons per hour (gph).<br />
• In pulse mode, set the quantity to be dosed in ml/<br />
pulse. The actual capacity is shown in gallons per<br />
hour (gph).<br />
• For calibration, set the quantity to be dosed in ml<br />
per 100 strokes.<br />
• In timer and batch modes, set the quantity to be<br />
dosed in gallons.<br />
• Under the "QUANTITY" menu item in the<br />
"COUNTERS" menu, the dosed quantity is indicated<br />
in gallons (gal).<br />
Operating display Operating display<br />
17
18<br />
Functions<br />
Wiring diagram, DME and DMS-A (0-48 l/h)<br />
See pages 26 and 28 for input/output data.<br />
Control input<br />
Level input<br />
Control cable<br />
Product no.:<br />
2 m cable: 96440447<br />
5 m cable: 96440448<br />
External stop in<br />
all other modes<br />
or<br />
Analog mode<br />
5<br />
"NO" black<br />
"NC" blue<br />
"COM" brown<br />
5 4 3 1 2 4 1 3 2<br />
4<br />
External stop in<br />
all other modes<br />
or<br />
Pulse/batch<br />
contact<br />
The level switch contacts (normally open) must be closed at low level/empty tank. Low level<br />
3<br />
1<br />
4<br />
1<br />
Level cable<br />
Product no.:<br />
2 m cable: 96440450<br />
5 m cable: 96440451<br />
3<br />
2<br />
Empty tank<br />
DME and DMS<br />
Number/colour<br />
Function<br />
1/brown 2/white<br />
Plug<br />
3/blue, +5V 4/black, GND 5/grey<br />
Type<br />
Pulse X X Contact<br />
Pulse 5V GND Supply 5V DC<br />
Analog (-) mA input (+) mA input mA signal<br />
Batch X X Contact<br />
Batch<br />
External start/stop<br />
5V GND Supply 5V DC<br />
Only Pulse/batch mode X X Contact<br />
Only Pulse/batch mode 5V GND Supply 5V DC<br />
All other modes X X Contact<br />
All other modes 5V GND Supply 5V DC<br />
Number/colour<br />
Function<br />
1/brown 2/white<br />
Plug<br />
3/blue, +5V 4/black, GND 5/grey<br />
Type<br />
Low level X X Contact<br />
Low level 5V GND Supply 5V DC<br />
Empty tank X X (+) mA input Contact<br />
Empty tank 5V GND Supply 5V DC<br />
Dosing monitoring X X Contact<br />
Dosing monitoring 5V GND Supply 5V DC<br />
TM03 1007 0905
Functions<br />
Wiring diagram, DME (60-940 l/h)<br />
Analog/Pulse/Leakage cable<br />
Product no.:<br />
2 m cable: 96440447<br />
5 m cable: 96440448<br />
Cable 1: Analog, pulse and leakage input<br />
Cable 2: Output for alarm relay<br />
1<br />
3<br />
2<br />
3<br />
2<br />
5<br />
4<br />
1<br />
5<br />
4<br />
3<br />
1<br />
3<br />
2<br />
5<br />
4<br />
1<br />
2<br />
3 1<br />
Relay cable<br />
Product no.:<br />
2 m cable: 96534214<br />
5 m cable: 96534215<br />
2<br />
1<br />
3<br />
Stop dosing cable<br />
Product no.:<br />
2 m cable: 96527109<br />
5 m cable: 96527111<br />
5<br />
3<br />
2<br />
2<br />
4<br />
1<br />
4<br />
1<br />
3<br />
2<br />
Level cable<br />
Product no.:<br />
2 m cable: 96440450<br />
5 m cable: 96440451<br />
DME and DMS<br />
Number/colour<br />
Function<br />
1/brown 2/white<br />
Plug<br />
3/blue, +5V 4/black, GND 5/grey<br />
Type<br />
Pulse X X Contact<br />
Pulse 5V GND Supply 5V DC<br />
Analog (-) mA input (+) mA input mA signal<br />
Batch X X Contact<br />
Batch 5V GND Supply 5V DC<br />
Leakage X X Contact<br />
Leakage 5V GND Supply 5V DC<br />
Number/colour 1/brown 2/white 3/blue<br />
Function<br />
Alarm relay output Common Normally open Normally closed<br />
TM0 27069 2503<br />
19
20<br />
Functions<br />
Cable 3: Stop dosing input and dosing monitor or dosing output<br />
Useful when the load (e.g. a relay) has one side<br />
connected to a power supply which is not the same one<br />
as connected to the sensor.<br />
When the dosing output is activated, the output<br />
provides the Gnd to the load.<br />
Recommended supply: max. 24 VDC.<br />
Max. current: 100 mA.<br />
Cable 4: Level input<br />
DME and DMS<br />
Number/colour<br />
Function<br />
1/brown 2/white<br />
Plug<br />
3/blue, +5V 4/black, GND 5/grey<br />
Type<br />
Stop input X X Contact<br />
Stop input 5V GND Supply 5V DC<br />
Dosing monitoring X X Contact<br />
Dosing monitoring GND 5V Supply 5V DC<br />
Dosing output<br />
(pump running)<br />
Open collector * NPN<br />
* Open collector can be used for a relay or a lamp.<br />
Number/colour<br />
Function<br />
1/brown 2/white<br />
Plug<br />
3/blue, +5V 4/black, GND 5/grey<br />
Type<br />
Low level X* X* Contact<br />
Low level 5V GND Supply 5V DC<br />
Empty tank X* X* Contact<br />
Empty tank 5V GND Supply 5V DC<br />
* The function for the potential free contact set can be chosen from the display (NO=Normally Open and NC=Normally Closed).
Construction<br />
Sectional drawing, DME (0-48 l/h)<br />
Construction<br />
3<br />
15<br />
14<br />
13<br />
2<br />
18<br />
The DME pump is a motor-driven diaphragm dosing<br />
pump consisting of the following main parts:<br />
Dosing head: Designed with a minimum of clearance<br />
space to optimise the priming and deaerating capabilities.<br />
The dosing head has built-in valve housings.<br />
Valves: Double-ball suction valve and single-ball<br />
discharge valve. Spring-loaded valves are available as<br />
an option.<br />
Vent valve: For priming and deaeration complete with<br />
connection for a 4/6 mm tubing.<br />
Connections: Sturdy and easy-to-use connections for<br />
various sizes of tubing, pipe thread or pipe cementing.<br />
Diaphragm: PTFE-coated, textile-reinforced EPDM<br />
diaphragm designed for long life.<br />
Backplate: With separation chamber, safety diaphragm<br />
and drain hole.<br />
Drive unit: With diaphragm connecting rod, crank, beltdrive<br />
and stepper motor, all mounted on a sturdy frame.<br />
Cabinet: Containing drive unit, electronics, control<br />
panel and various electrical connections.<br />
The pump can be supplied with spring-loaded valves.<br />
Spring material: Hastelloy.<br />
The spring is not shown in the sectional drawing.<br />
4<br />
5<br />
6<br />
7<br />
8<br />
10 11 12<br />
9<br />
1 16<br />
26<br />
25<br />
23<br />
20 19 22 21<br />
24<br />
17<br />
Material specification<br />
DME<br />
Pos. Description Material options<br />
1 Backplate PPE/PS 20% glass fibre<br />
2 Diaphragm Textile-reinforced EPDM, PTFE-coated<br />
3 Valve complete -<br />
4 O-ring EPDM/FKM<br />
5 Valve casing PP/PVDF/Stainless steel 1.4401<br />
6 Valve ball Ceramic/Stainless steel 1.4401<br />
7 Valve seat disk EPDM/FKM<br />
8 Valve seat ring PP/PVDF/Stainless steel 1.4401<br />
9 Connection complete -<br />
10<br />
Cone/thread piece/<br />
cementing piece<br />
PP/PVDF/Stainless steel 1.4401/PVC<br />
11 Clamping ring PP/PVDF<br />
12 Union nut PP/PVDF/Stainless steel 1.4401<br />
13 Vent valve screw PP/PVDF<br />
14 Vent valve ball Ceramic/Stainless steel 1.4401<br />
15 Vent valve O-ring EPDM/FKM<br />
16 Cabinet PPE/PS 20% glass fibre<br />
17 Power/alarm cable Rubber<br />
18 Dosing head PP/PVDF/Stainless steel 1.4401<br />
19 Drive belt Rubber, polyamide-reinforced<br />
20 Connecting rod Steel<br />
21 Origo sensor -<br />
22 Crank shaft Steel<br />
23 Power PCB -<br />
24 Operation PCB -<br />
25 Stepper motor -<br />
26 Drive frame Aluminium<br />
TM01 9994 3600<br />
21
22<br />
Construction<br />
Sectional drawing, DME (60-940 l/h)<br />
28<br />
27<br />
26<br />
25<br />
24<br />
23<br />
Material specification<br />
21<br />
22<br />
20<br />
19<br />
18<br />
17<br />
16<br />
15<br />
29<br />
31<br />
30<br />
14<br />
13<br />
39<br />
10 11<br />
12<br />
9<br />
32 36 37<br />
1 2 3 4 38<br />
Pos. Description Material options<br />
1 Backplate PPE/PS 20% glass fibre<br />
2 Spring DIN 17223 TYPE C<br />
3 Cabinet PPE/PS 20% glass fibre<br />
4 Origo sensor<br />
5<br />
Operation PCB<br />
(printed circuit board)<br />
6 Power cable Rubber<br />
7 Gear<br />
8 BLDC motor<br />
9 Drain hole or leakage sensor<br />
10 Hose nozzle PP/PVDF<br />
11 Union nut PP/PVDF<br />
12 Connection complete<br />
13 O-ring EPDM/FKM<br />
14 O-ring EPDM/FKM<br />
15 Venting valve ball Ceramic<br />
16 Spring Hastelloy C<br />
17 Spring Hastelloy C<br />
18 Venting valve house PP/PVDF<br />
19 Venting valve tap PP/PVDF<br />
20 O-ring EPDM/FKM<br />
21 End cover Steel<br />
22 Venting valve complete<br />
23 O-ring EPDM/FKM<br />
24 Valve seat PP/PVDF/SS 1.4401<br />
25 Valve ball<br />
Ceramic/Glass/SS 1.4401/<br />
Hastelloy C/PTFE<br />
26 Valve casing PP/PVDF/SS 1.4401<br />
33<br />
8<br />
34<br />
35<br />
7<br />
5<br />
6<br />
DME<br />
27 Spring Hastelloy C<br />
28 O-ring EPDM/FKM<br />
29 Valve complete<br />
30 Steel plate Steel<br />
31 Dosing head PP/PVDF/SS 1.4401<br />
32 Safety membrane<br />
33 Power PCB (printed circuit board)<br />
34 Crank shaft Steel<br />
35 I/O PCB (printed circuit board)<br />
36 Connecting rod Steel<br />
37 Steel plate Steel<br />
38 Steel frame Steel<br />
Textile-reinforced EPDM,<br />
39 Diaphragm<br />
PTFE-coated<br />
The pump is available with spring-loaded valves.<br />
Spring material: Hastelloy.<br />
The spring is not shown in the sectional drawing.<br />
TM0 28599 0604
Construction DMS<br />
Sectional drawing, DMS<br />
Construction<br />
14<br />
13<br />
2<br />
The DMS pump is a motor-driven diaphragm dosing<br />
pump consisting of the following main parts:<br />
Dosing head: Designed with a minimum of clearance<br />
space to optimise the priming and deaerating capability.<br />
The dosing head has built-in valve housings.<br />
Valves: Double-ball suction valve and single-ball<br />
discharge valve. Spring-loaded valves are available as<br />
an option.<br />
Vent valve: For priming and deaeration complete with<br />
connection for a 4/6 mm tubing.<br />
Connections: Sturdy and easy-to-use connections for<br />
various sizes of tubing, pipe thread or pipe cementing.<br />
Diaphragm: PTFE-coated, textile-reinforced EPDM<br />
diaphragm designed for long life.<br />
Backplate: With separation chamber, safety diaphragm<br />
and drain hole.<br />
Drive unit: With diaphragm connecting rod, crank, beltdrive<br />
and synchronous motor, all mounted on a sturdy<br />
frame.<br />
Cabinet: Containing drive unit, electronics, control<br />
panel and various electrical connections (DMS-A).<br />
The pump is available with spring-loaded valves.<br />
Spring material: Hastelloy.<br />
The spring is not shown in the sectional drawing.<br />
3<br />
15<br />
18<br />
4<br />
5<br />
6<br />
7<br />
8<br />
10 11 12<br />
9<br />
1 16<br />
26 21<br />
25<br />
20 19 22<br />
23<br />
24<br />
17<br />
Material specification<br />
Pos. Description Material options<br />
1 Backplate PPE/PS 20% glass fibre<br />
2 Diaphragm Textile-reinforced EPDM, PTFE-coated<br />
3 Valve complete -<br />
4 O-ring EPDM/FKM<br />
5 Valve casing PP/PVDF/Stainless steel<br />
6 Valve ball Ceramic/Stainless steel 1.4401<br />
7 Valve seat disk EPDM/FKM<br />
8 Valve seat O-ring PP/PVDF/Stainless steel 1.4401<br />
9 Connection complete -<br />
10<br />
Cone/thread piece/<br />
cementing piece<br />
PP/PVDF/Stainless steel 1.4401/PVC<br />
11 Clamping ring PP/PVDF<br />
12 Union nut PP/PVDF/Stainless steel 1.4401<br />
13 Vent valve screw PP/PVDF<br />
14 Vent valve ball Ceramic/Stainless steel 1.4401<br />
15 Vent valve O-ring EPDM/FKM<br />
16 Cabinet PPE/PS 20% glass fibre<br />
17 Power/alarm cable Rubber<br />
18 Dosing head PP/PVDF/Stainless steel 1.4401<br />
19 Drive belt Rubber, polyamide-reinforced<br />
20 Connecting rod Steel<br />
21<br />
Dosing stoke auxiliary<br />
spring<br />
-<br />
22 Crank shaft Steel<br />
23 Power PCB -<br />
24 Operation PCB -<br />
25 Synchronous motor -<br />
26 Drive frame Aluminium<br />
TM01 9995 3600<br />
23
24<br />
Dimensions<br />
Front-fitted control panel (0-48 l/h)<br />
D<br />
160<br />
Side-fitted control panel (0-48 l/h)<br />
D<br />
Dimensions are i mm.<br />
Pump type<br />
160<br />
100%<br />
110 B<br />
98<br />
DME 2<br />
DMS 2<br />
ml/h<br />
130<br />
110<br />
98<br />
C<br />
DMS 4<br />
C<br />
50<br />
DME 8<br />
DMS 8<br />
50<br />
B<br />
100%<br />
DME 12<br />
DMS 12<br />
A<br />
A<br />
ml/h<br />
DME and DMS<br />
DME 19 DME 48<br />
A 137 192<br />
B 239 294<br />
C 36 15<br />
D 168 188<br />
TM01 8953 1202<br />
TM01 8954 1202
Dimensions<br />
Front-fitted control panel, DME (60-940 l/h)<br />
C<br />
D<br />
Dimensions are i mm.<br />
A<br />
B<br />
G<br />
E H<br />
F<br />
I<br />
DME and DMS<br />
DME 60 DME 150 DME 375 DME 940<br />
A 198 198 238 238<br />
B 176 176 218 218<br />
C 331 345 471 496<br />
D 284 284 364 364<br />
E 180 180 230 230<br />
F 444 444 540 539<br />
G 41 28 31 6<br />
H 74 74 95 95<br />
I 187 187 246 246<br />
TM02 7062 2503<br />
25
26<br />
Technical data<br />
DME (0-48 l/h)<br />
Pump DME 2 DME 8 DME 12 DME 19 DME 48<br />
Mechanical data<br />
Weight and size<br />
Electrical data<br />
Signal input<br />
Maximum capacity without anti-cavitation 1<br />
Maximum capacity with anti-cavitation 1<br />
DME<br />
[l/h] 2.5 7.5 12 18.5 48<br />
[gph] 0.66 1.98 3.71 4.88 12.68<br />
[l/h] 1.8 5.6 9 14.5 37<br />
[gph] 0.49 1.48 2.78 3.66 9.51<br />
Maximum pressure<br />
[bar]<br />
[psi]<br />
18<br />
261<br />
10<br />
145<br />
6<br />
87<br />
6.2<br />
90<br />
2.6<br />
38<br />
Maximum stroke frequency 2 [stroke/min] 180 180 180 151 151<br />
Maximum suction lift during operation [m] 6<br />
Maximum suction lift when priming with wet valves [m] 1.8 3 3 3 3<br />
Maximum viscosity with spring-loaded valves 3 [mPas] (= cP) 500 500 500 500 100<br />
Maximum viscosity without spring-loaded valves 3 [mPas] (= cP) 200 200 200 200 100<br />
Maximum liquid temperature [°C] 50<br />
Minimum liquid temperature [°C] 0<br />
Maximum ambient temperature [°C] 45<br />
Minimum ambient temperature [°C] 0<br />
Accuracy of repeatability ±1%<br />
Weight [kg] 2.3 2.3 2.3 3.4 3.4<br />
Diaphragm diameter [mm] 28 38 43.5 55 77<br />
Supply voltage [V] 1 x 100-240 V, 50-60 Hz<br />
Maximum current consumption [A]<br />
at 100 V<br />
at 230 V<br />
0.27<br />
0.16<br />
0.35<br />
0.26<br />
Maximum power consumption P1 [W] 16.2 22.1<br />
Enclosure class IP 65<br />
Insulation class F<br />
Voltage in level sensor input [VDC] 5<br />
Voltage in pulse input [VDC] 5<br />
Minimum pulse-repetition period [ms] 3.3<br />
Impedance in analog 0/4-20 mA input [Ω] 250<br />
Maximum loop resistance in pulse signal circuit [Ω] 350<br />
Maximum loop resistance in level signal circuit [Ω] 350<br />
Signal output<br />
Maximum load of alarm relay output, at ohmic load [A]<br />
Maximum voltage, alarm relay output [V]<br />
2<br />
250<br />
Sound pressure The sound pressure level of the pump is lower than 70 db(A).<br />
Approvals CE, VDE, cUL, UL, METI<br />
1 At any counter-pressure if the pump is calibrated to the actual installation.<br />
2 The maximum stroke frequency varies according to calibration.<br />
3 Maximum suction lift: 1 metre.
Technical data<br />
DME (60-940 l/h)<br />
Pump DME 60 DME 150 DME 375 DME 940<br />
Mechanical data<br />
Weight and size<br />
Maximum capacity [l/h] 60 150 376 940<br />
Maximum capacity with anti-cavitation 75% [l/h] [l/h] 45 112 282 705<br />
Maximum capacity with anti-cavitation 50% [l/h] [l/h] 33.4 83.5 210 525<br />
Maximum capacity with anti-cavitation 25% [l/h] [l/h] 16.1 40.4 101 252<br />
Maximum pressure [bar] 10 4 10 4<br />
Maximum stroke frequency [stroke/min] 160<br />
Maximum suction lift during operation [m] 6<br />
Maximum suction lift when priming with wet valves [m] 1.5<br />
Maximum viscosity with spring-loaded valves 1 [mPas] (= cP)<br />
3000 mPas at 50% capacity<br />
Maximum viscosity without spring-loaded valves 1 [mPas] (= cP)<br />
200<br />
Maximum liquid temperature [°C] 50<br />
Minimum liquid temperature [°C] 0<br />
Maximum ambient temperature [°C] 45<br />
Minimum ambient temperature [°C] -10<br />
Accuracy of repeatability ±1%<br />
Weight [kg] 11.4 11.8 21 22.5<br />
Diaphragm diameter [mm] 79 106 124 173<br />
Supply voltage [V] 1 x 100-240 V, 50-60 Hz<br />
Electrical data<br />
Maximum current consumption [A]<br />
Maximum power consumption P1 [W]<br />
at 100 V<br />
at 230 V<br />
1.25<br />
0.67<br />
67.1<br />
2.40<br />
1.0<br />
240<br />
Enclosure class IP 65<br />
Insulation class B<br />
Cable data Supply cable 1.5 metre<br />
Signal input<br />
Voltage in level sensor input [VDC] 5<br />
Voltage in pulse input [VDC] 5<br />
Minimum pulse-repetition period [ms] 3.3<br />
Impedance in analog 0/4-20 mA input [Ω] 250<br />
Maximum loop resistance in pulse signal circuit [Ω] 350<br />
Maximum loop resistance in level signal circuit [Ω] 350<br />
Signal output<br />
Maximum load of alarm relay output, at ohmic load [A]<br />
Maximum voltage, alarm relay output [V]<br />
2<br />
42<br />
Approvals CE, VDE, CSA<br />
Sound pressure<br />
level<br />
The sound pressure level of the pump is lower than 70 dB (A).<br />
1 Maximum suction lift: 1 metre.<br />
DME<br />
27
28<br />
Technical data<br />
DMS<br />
Pump DMS 2 DMS 4 DMS 8 DMS 12<br />
Mechanical data<br />
Weight and size<br />
Electrical data<br />
Signal input<br />
Maximum capacity 1<br />
Maximum pressure<br />
Maximum stroke frequency 2 [stroke/min]<br />
DMS-A and<br />
AR, B<br />
DMS-D (50 Hz)<br />
DMS-D (60 Hz)<br />
DMS<br />
[l/h] 2.5 4 7.5 12<br />
[gph] 0.66 1.05 1.98 3.71<br />
[l/h] 3.3 ± 20% 5.7 ±18% 8.7 ± 8% 13.7 ± 6%<br />
[gph]<br />
0.87 ±<br />
20%<br />
1.5 ±18% 2.3 ± 8% 3.6 ± 6%<br />
[l/h] 3.9 ± 20% 6.9 ±18% 10.4 ± 8% 16.4 ± 6%<br />
[gph]<br />
1.03 ±<br />
20%<br />
1.82 ±18% 2.75 ± 8% 4.33 ± 6%<br />
[bar] 11 7 5.4 3.4<br />
[psi] 160 102 78 49<br />
DMS-A and AR, B 180<br />
DMS-D (50 Hz)<br />
DMS-D (60 Hz)<br />
Maximum suction lift during operation [m] 6<br />
Maximum suction lift when priming with wet valves [m] 1.8 2 3 3<br />
Maximum viscosity with spring-loaded valves 3 [mPas] (= cP)<br />
500<br />
Maximum viscosity without spring-loaded valves 3 [mPas] (= cP)<br />
200<br />
Maximum liquid temperature [°C] 50<br />
Minimum liquid temperature [°C] 0<br />
Maximum ambient temperature [°C] 45<br />
Minimum ambient temperature [°C] 0<br />
Accuracy of repeatability ±1%<br />
Weight [kg] 2.3<br />
Diaphragm diameter [mm] 28 32 38 42.5<br />
Supply voltage<br />
187.5<br />
225<br />
1 x 230 V –13%/+10%, 50/60 Hz<br />
1 x 120 V –12%/+8%, 60 Hz<br />
1 x 100 V ±6%, 50/60 Hz<br />
at 100 V 0.2<br />
Maximum current consumption [A]<br />
at 120 V 0.17<br />
at 230 V 0.09<br />
Maximum power consumption P1 [W] 20<br />
Enclosure class IP 65<br />
Insulation class F<br />
Voltage in level sensor input [VDC] 5<br />
Voltage in pulse input [VDC] 5<br />
Minimum pulse-repetition period [ms] 3.3<br />
Impedance in 0/4-20 mA analog input [Ω] 250<br />
Maximum loop resistance in pulse signal circuit [Ω] 350<br />
Maximum loop resistance in level signal circuit [Ω] 350<br />
Signal output<br />
Maximum load of alarm relay output at ohmic load [A]<br />
Maximum voltage, alarm relay output [V]<br />
2<br />
250<br />
Sound pressure The sound pressure level of the pump is lower than 70 db(A).<br />
Approvals CE, VDE cUL, UL, METI 4<br />
1 Irrespective of counter-pressure if the pump is calibrated to the actual installation.<br />
2 The maximum stroke frequency varies according to calibration.<br />
3 Maximum suction lift: 1 metre.<br />
4 DMS-D: only CE and VDE.
Pump selection<br />
Standard range, DME (0-48 l/h)<br />
Power supply: 1 x 100-240 V, 50-60 Hz<br />
(Switch-mode).<br />
Mains plug: EU (Schuko).<br />
Valves: Double-ball on suction side, single-ball on discharge side.<br />
Max.<br />
capacity<br />
[l/h] 1<br />
2.5<br />
(1.8)<br />
7.5<br />
(5.6)<br />
12<br />
(9)<br />
18.5<br />
(14.5)<br />
48<br />
(37)<br />
Max.<br />
pressure<br />
[bar]<br />
18<br />
10<br />
6<br />
6.2<br />
2.6<br />
Materials 2<br />
Pump head Gaskets Valve balls<br />
Connection<br />
3<br />
PP EPDM Ceramic 4/6, 6/9<br />
PP FKM Ceramic 4/6, 6/9<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
PP EPDM Ceramic 4/6, 6/9<br />
PP FKM Ceramic 4/6, 6/9<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
PP EPDM Ceramic 4/6, 6/9<br />
PP FKM Ceramic 4/6, 6/9<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
Rp 1/4<br />
6/9,<br />
9/12<br />
6/9,<br />
9/12<br />
6/9,<br />
9/12<br />
Rp 3/8<br />
6/9,<br />
9/12<br />
6/9,<br />
9/12<br />
6/9,<br />
9/12<br />
Control panel<br />
position<br />
Type designation<br />
(variant A) 4<br />
DME and DMS<br />
Without<br />
alarm relay<br />
(variant A)<br />
Product<br />
number<br />
With alarm<br />
relay<br />
(variant AR)<br />
Front-fitted DME 2-18 A-PP/E/C-F-3111F 96434879 96434885<br />
Side-fitted DME 2-18 A-PP/E/C-S-3111F 96434882 96434888<br />
Front-fitted DME 2-18 A-PP/V/C-F-3111F 96443981 96443987<br />
Side-fitted DME 2-18 A-PP/V/C-S-3111F 96443984 96443990<br />
Front-fitted DME 2-18 A-PV/V/C-F-3111F 96434899 96434905<br />
Side-fitted DME 2-18 A-PV/V/C-S-3111F 96434902 96434908<br />
Front-fitted DME 2-18 A-SS/V/SS-F-31AAF 96437423 96437429<br />
Side-fitted DME 2-18 A-SS/V/SS-S-31AAF 96437426 96437432<br />
Front-fitted DME 8-10 A-PP/E/C-F-3111F 96434880 96434886<br />
Side-fitted DME 8-10 A-PP/E/C-S-3111F 96434883 96434889<br />
Front-fitted DME 8-10 A-PP/V/C-F-3111F 96443982 96443988<br />
Side-fitted DME 8-10 A-PP/V/C-S-3111F 96443985 96443991<br />
Front-fitted DME 8-10 A-PV/V/C-F-3111F 96434900 96434906<br />
Side-fitted DME 8-10 A-PV/V/C-S-3111F 96434903 96434909<br />
Front-fitted DME 8-10 A-SS/V/SS-F-31AAF 96437424 96437430<br />
Side-fitted DME 8-10 A-SS/V/SS-S-31AAF 96437427 96437433<br />
Front-fitted DME 12-6 A-PP/E/C-F-3111F 96434881 96434887<br />
Side-fitted DME 12-6 A-PP/E/C-S-3111F 96434884 96434890<br />
Front-fitted DME 12-6 A-PP/V/C-F-3111F 96443983 96443989<br />
Side-fitted DME 12-6 A-PP/V/C-S-3111F 96443986 96443992<br />
Front-fitted DME 12-6 A-PV/V/C-F-3111F 96434901 96434907<br />
Side-fitted DME 12-6 A-PV/V/C-S-3111F 96434904 96434910<br />
Front-fitted DME 12-6 A-SS/V/SS-F-31AAF 96437425 96437431<br />
Side-fitted DME 12-6 A-SS/V/SS-S-31AAF 96437428 96437434<br />
Front-fitted DME 19-6 A-PP/E/C-F-3122F 96434891 96434895<br />
Side-fitted DME 19-6 A-PP/E/C-S-3122F 96434893 96434897<br />
Front-fitted DME 19-6 A-PP/V/C-F-3122F 96443993 96443997<br />
Side-fitted DME 19-6 A-PP/V/C-S-3122F 96443995 96443999<br />
Front-fitted DME 19-6 A-PV/V/C-F-3122F 96434911 96434915<br />
Side-fitted DME 19-6 A-PV/V/C-S-3122F 96434913 96434917<br />
Front-fitted DME 19-6 A-SS/V/SS-F-31BBF 96437435 96437439<br />
Side-fitted DME 19-6 A-SS/V/SS-S-31BBF 96437437 96437441<br />
Front-fitted DME 48-3 A-PP/E/C-F-3122F 96434892 96434896<br />
Side-fitted DME 48-3 A-PP/E/C-S-3122F 96434894 96434898<br />
Front-fitted DME 48-3 A-PP/V/C-F-3122F 96443994 96443998<br />
Side-fitted DME 48-3 A-PP/V/C-S-3122F 96443996 96444000<br />
Front-fitted DME 48-3 A-PV/V/C-F-3122F 96434912 96434916<br />
Side-fitted DME 48-3 A-PV/V/C-S-3122F 96434914 96434918<br />
Stainl. steel<br />
Stainl. steel<br />
Front-fitted DME 48-3 A-SS/V/SS-F-31BBF 96437436 96437440<br />
FKM<br />
Rp 3/8<br />
1.4401<br />
1.4401<br />
Side-fitted DME 48-3 A-SS/V/SS-S-31BBF 96437438 96437442<br />
1 Values in brackets are maximum capacity if the anti-cavitation function has been selected.<br />
2 See list of pumped liquids on page 37.<br />
3 Underlined sizes are factory-fitted connections; others are supplied with the pump as standard.<br />
4/6, 6/9 and 9/12 are compression fittings for inner/outer tubing diameters stated in mm.<br />
Rp 1/4 and Rp 3/8 connections have inner thread for pipe connection.<br />
4 Also available in AR version.<br />
29
30<br />
Pump selection<br />
Non-standard range, DME (0-48 l/h)<br />
Example in bold: DME 2-18 A-SS/V/SS-F-32AAF<br />
Maximum<br />
capacity and<br />
pressure 2<br />
Control<br />
variant<br />
Materials of pump head,<br />
gaskets and valve balls<br />
[l/h] - [bar] See page 6 Dosing head:<br />
PP = Polypropylene<br />
PV = PVDF<br />
SS = Stainl. steel 1.4401<br />
Gaskets:<br />
E = EPDM<br />
V = FKMP<br />
T = PTFE<br />
DME Pump<br />
head<br />
2-18<br />
8-10<br />
12-6<br />
19-6<br />
48-3<br />
A<br />
AR<br />
AP 1<br />
AG 1<br />
A<br />
AR<br />
AP 1<br />
AG 1<br />
Valve balls:<br />
C = Ceramic<br />
SS = Stainl. steel 1.4401<br />
T = PTFE<br />
PP<br />
PV<br />
SS<br />
PP<br />
PV<br />
SS<br />
Gasket Ball<br />
E<br />
V<br />
T<br />
E<br />
T<br />
V<br />
E<br />
T<br />
V<br />
C<br />
SS<br />
T<br />
SS<br />
C<br />
SS<br />
T<br />
Control panel<br />
position<br />
F = Front-fitted<br />
S = Side-fitted<br />
1 Pumps equipped with bus communication module, see page 15.<br />
2<br />
2-18: 2.5 l/h, 18 bar<br />
8-10: 7.5 l/h, 10 bar<br />
12-6: 12 l/h, 6 bar<br />
19-6: 18.5 l/h, 6.2 bar<br />
48-3: 48 l/h, 2.6 bar<br />
E<br />
T<br />
V<br />
SS<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
Motor voltage Valves<br />
2 =<br />
1 = Standard<br />
1 x 120 V, 60 Hz 2 = Spring-loaded<br />
3 =<br />
1 x 100-240 V,<br />
50-60 Hz<br />
2<br />
3<br />
2<br />
3<br />
2<br />
3<br />
2<br />
3<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
Suction/discharge<br />
connection<br />
1 = Tubing 4/6+6/9<br />
2 = Tubing 6/9+6/12+9/12<br />
3 = Tubing 4/6<br />
4 = Tubing 6/9<br />
5 = Tubing 6/12<br />
6 = Tubing 9/12<br />
T = Tubing 0.17"/0.25"<br />
R = Tubing 0.25"/0.375"<br />
S = Tubing 0.375"/0.5"<br />
A = Threaded Rp 1/4<br />
B = Threaded Rp 3/8<br />
V = Threaded NPT 1/4"<br />
Y = Threaded NPT 3/8"<br />
E = Cementing d.10<br />
F = Cementing d.12<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A B<br />
V<br />
Y<br />
2<br />
4<br />
5<br />
6<br />
A<br />
E<br />
F<br />
A<br />
B<br />
V<br />
Y<br />
DME and DMS<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A B<br />
V<br />
Y<br />
2<br />
4<br />
5<br />
6<br />
A<br />
E<br />
F<br />
A<br />
B<br />
V<br />
Y<br />
Mains<br />
plug<br />
F = EU<br />
B =<br />
USA+CAN<br />
G = UK<br />
I = AU<br />
E = CH<br />
J = JP<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J
Pump selection<br />
Standard range, DME (60-940 l/h)<br />
Power supply: 1 x 100-240 V, 50-60 Hz<br />
(switch-mode).<br />
Mains plug: EU (Schuko).<br />
Valves: Single-ball on suction side;<br />
single-ball on discharge side.<br />
Max.<br />
capacity<br />
[l/h]<br />
Max.<br />
pressure<br />
[bar]<br />
Control<br />
variant<br />
60 10 AR<br />
60 10 B<br />
150 4 AR<br />
150 4 B<br />
376 10 AR<br />
376 10 B<br />
Materials<br />
Pump<br />
head Gaskets<br />
Valve<br />
balls<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Glass<br />
PP FKM Glass<br />
PVDF FKM Glass<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Glass<br />
PP FKM Glass<br />
PVDF FKM Glass<br />
SS FKM<br />
St. steel<br />
1.4401<br />
E<br />
Connection<br />
<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
Rp 3/4”<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
Rp 3/4”<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
Rp 3/4”<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
19/27<br />
25/34<br />
Rp 3/4”<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
Rp 1 1/4”<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
Rp 1 1/4”<br />
Control<br />
panel<br />
position<br />
Type designation<br />
DME and DMS<br />
Product<br />
number<br />
Front-fitted DME 60-10 AR-PP/E/C-F-31QQF 96524874<br />
Side-fitted DME 60-10 AR-PP/E/C-S-31QQF 96524879<br />
Front-fitted DME 60-10 AR-PP/V/C-F-31QQF 96524910<br />
Side-fitted DME 60-10 AR-PP/V/C-S-31QQF 96524911<br />
Front-fitted DME 60-10 AR-PV/V/C-F-31QQF 96524912<br />
Side-fitted DME 60-10 AR-PV/V/C-S-31QQF 96524913<br />
Front-fitted DME 60-10 AR-SS/V/SS-F-31A1A1F 96524914<br />
Side-fitted DME 60-10 AR-SS/V/SS-S-31A1A1F 96524915<br />
Front-fitted DME 60-10 B-PP/E/C-F-31QQF 96524916<br />
Side-fitted DME 60-10 B-PP/E/C-S-31QQF 96524917<br />
Front-fitted DME 60-10 B-PP/V/C-F-31QQF 96524918<br />
Side-fitted DME 60-10 B-PP/V/C-S-31QQF 96524919<br />
Front-fitted DME 60-10 B-PV/V/C-F-31QQF 96524920<br />
Side-fitted DME 60-10 B-PV/V/C-S-31QQF 96524921<br />
Front-fitted DME 60-10 B-SS/V/SS-F-31A1A1F 96524923<br />
Side-fitted DME 60-10 B-SS/V/SS-S-31A1A1F 96524924<br />
Front-fitted DME 150-4 AR-PP/E/C-F-31QQF 96524925<br />
Side-fitted DME 150-4 AR-PP/E/C-S-31QQF 96524926<br />
Front-fitted DME150-4 AR-PP/V/C-F-31QQF 96524927<br />
Side-fitted DME 150-4 AR-PP/V/C-S-31QQF 96524928<br />
Front-fitted DME 150-4 AR-PV/V/C-F-31QQF 96524929<br />
Side-fitted DME 150-4 AR-PV/V/C-S-31QQF 96524930<br />
Front-fitted DME 150-4 AR-SS/V/SS-F-31A1A1F 96524931<br />
Side-fitted DME 150-4 AR-SS/V/SS-S-31A1A1F 96524932<br />
Front-fitted DME 150-4 B-PP/E/C-F-31QQF 96524933<br />
Side-fitted DME 150-4 B-PP/E/C-S-31QQF 96524934<br />
Front-fitted DME 150-4 B-PP/V/C-F-31QQF 96524935<br />
Side-fitted DME 150-4 B-PP/V/C-S-31QQF 96524936<br />
Front-fitted DME 150-4 B-PV/V/C-F-31QQF 96524937<br />
Side-fitted DME 150-4 B-PV/V/C-S-31QQF 96524938<br />
Front-fitted DME 150-4 B-SS/V/SS-F-31A1A1F 96524939<br />
Side-fitted DME 150-4 B-SS/V/SS-S-31A1A1F 96524940<br />
Front-fitted DME 375-10 AR-PP/E/G-F-31WWF 96524941<br />
Side-fitted DME 375-10 AR-PP/E/G-S-31WWF 96524942<br />
Front-fitted DME 375-10 AR-PP/V/G-F-31WWF 96524943<br />
Side-fitted DME 375-10 AR-PP/V/G-S-31WWF 96524944<br />
Front-fitted DME 375-10 AR-PV/V/G-F-31WWF 96524945<br />
Side-fitted DME 375-10 AR-PV/V/G-S-31WWF 96524946<br />
Front-fitted DME 375-10 AR-SS/V/SS-F-31A2A2F 96524947<br />
Side-fitted DME 375-10 AR-SS/V/SS-S-31A2A2F 96524948<br />
Front-fitted DME 375-10 B-PP/E/G-F-31WWF 96524949<br />
Side-fitted DME 375-10 B-PP/E/G-S-31WWF 96524950<br />
Front-fitted DME 375-10 B-PP/V/G-F-31WWF 96524951<br />
Side-fitted DME 375-10 B-PP/V/G-S-31WWF 96524952<br />
Front-fitted DME 375-10 B-PV/V/G-F-31WWF 96524953<br />
Side-fitted DME 375-10 B-PV/V/G-S-31WWF 96524954<br />
Front-fitted DME 375-10 B-SS/V/SS-F-31A2A2F 96524956<br />
Side-fitted DME 375-10 B-SS/V/SS-S-31A2A2F 96524957<br />
31
32<br />
Pump selection<br />
940 4 AR<br />
940 4 B<br />
PP EPDM Glass<br />
PP FKM Glass<br />
PVDF FKM Glass<br />
SS FKM<br />
St. steel<br />
1.4401<br />
PP EPDM Glass<br />
PP FKM Glass<br />
PVDF FKM Glass<br />
SS FKM<br />
St. steel<br />
1.4401<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
Rp 1 1/4”<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
32/41<br />
38/48<br />
Rp 1 1/4”<br />
19/27, 25/34, 32/41 and 38/48 are inner/outer tubing diameters in mm for hose clamp connectors.<br />
Rp 3/4” and Rp 1 1/4” connections have inner thread for pipe connection.<br />
DME and DMS<br />
Front-fitted DME 940-4 AR-PP/E/G-F-31WWF 96524958<br />
Side-fitted DME 940-4 AR-PP/E/G-S-31WWF 96524959<br />
Front-fitted DME940-4 AR-PP/V/G-F-31WWF 96524960<br />
Side-fitted DME 940-4 AR-PP/V/G-S-31WWF 96524961<br />
Front-fitted DME 940-4 AR-PV/V/G-F-31WWF 96524962<br />
Side-fitted DME 940-4 AR-PV/V/G-S-31WWF 96524963<br />
Front-fitted DME 940-4 AR-SS/V/SS-F-31A2A2F 96524964<br />
Side-fitted DME 940-4 AR-SS/V/SS-S-31A2A2F 96524965<br />
Front-fitted DME 940-4 B-PP/E/G-F-31WWF 96524966<br />
Side-fitted DME 940-4 B-PP/E/G-S-31WWF 96524967<br />
Front-fitted DME 940-4 B-PP/V/G-F-31WWF 96524968<br />
Side-fitted DME 940-4 B-PP/V/G-S-31WWF 96524969<br />
Front-fitted DME 940-4 B-PV/V/G-F-31WWF 96524980<br />
Side-fitted DME 940-4 B-PV/V/G-S-31WWF 96524981<br />
Front-fitted DME 940-4 B-SS/V/SS-F-31A2A2F 96524982<br />
Side-fitted DME 940-4 B-SS/V/SS-S-31A2A2F 96524983
Pump selection<br />
Non-standard range, DME (60-940 l/h)<br />
Example in bold: DME 150-4 AR SS/V/SS-F-32A1A1F<br />
Maximum<br />
capacity and<br />
pressure 2<br />
Control<br />
variant<br />
Materials of dosing<br />
head, gaskets<br />
and valve balls<br />
[l/h] - [bar] See page 5 Dosing head:<br />
PP = Polypropylene<br />
PV = PVDF<br />
SS = Stainl. stee 1.4401<br />
DME Pump<br />
head<br />
60-10<br />
150-4<br />
375-10<br />
940-4<br />
B<br />
AR<br />
AP 1<br />
B<br />
AR<br />
AP 1<br />
Gaskets:<br />
E = EPDM<br />
V = FKM<br />
T = PTFE<br />
Valve balls:<br />
C = Ceramic<br />
SS = Stainl. steel 1.4401<br />
Y = Hastelloy C<br />
G = Glass<br />
PP<br />
PV<br />
SS<br />
PP<br />
PV<br />
SS<br />
Gasket Ball<br />
E<br />
V<br />
T<br />
E<br />
T<br />
V<br />
E<br />
V<br />
T<br />
C<br />
SS<br />
Y<br />
SS<br />
G<br />
SS<br />
Y<br />
Control<br />
panel<br />
position<br />
F = Front-fitted<br />
S = Side-fitted<br />
1 Pumps equipped with bus communication module, see page 15.<br />
2<br />
60-10: 60l/h, 10 bar<br />
150-4: 150 l/h, 4bar<br />
375-10: 375 l/h, 10 bar<br />
940-4: 940 l/h, 4 bar<br />
E<br />
T<br />
V<br />
SS<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
Motor voltage Valves<br />
2 =1 x 120 V, 60 Hz<br />
3 = 1 x 100-240 V,<br />
50-60 Hz<br />
2<br />
3<br />
2<br />
3<br />
2<br />
3<br />
2<br />
3<br />
Connection suction/<br />
discharge<br />
Q= 19/27 + 25/34<br />
1 = Standard W= 32/41 + 38/48<br />
2 = Springloaded A1= Threaded RP 3/4"<br />
A2= Threaded RP 1 1/4"<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
Q<br />
A1<br />
W<br />
A2<br />
DME and DMS<br />
Mains plug<br />
F = EU (DIN)<br />
B = USA+CAN<br />
G = UK<br />
I = AU<br />
E = CH<br />
J = JP<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
33
34<br />
Pump selection<br />
Standard range, DMS<br />
Power supply: 1 x 230 V, 50 Hz.<br />
Mains plug: EU (Schuko).<br />
Valves: Double-ball on suction side, single-ball on discharge side.<br />
Max.<br />
capacity [l/h]<br />
Max.<br />
pressure [bar]<br />
2.5<br />
11<br />
Control<br />
variant<br />
1<br />
A<br />
AR<br />
B<br />
3.3 D<br />
4<br />
7<br />
A<br />
AR<br />
B<br />
5.7 D<br />
Pump<br />
head<br />
Materials 2<br />
Gaskets<br />
Valve<br />
balls<br />
Connection<br />
3<br />
Control<br />
panel<br />
position<br />
Type designation<br />
(variants A 4 and B)<br />
DME and DMS<br />
Product<br />
number<br />
Without With<br />
alarm relay alarm relay<br />
(variant A) (variant AR)<br />
Variant<br />
D<br />
PP EPDM Ceramic 4/6, 6/9<br />
Front-fitted DMS 2-11 A-PP/E/C-F-1111F<br />
Side-fitted DMS 2-11 A-PP/E/C-S-1111F<br />
96437450<br />
96437451<br />
96446959<br />
96446960<br />
PP FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 2-11 A-PP/V/C-F-1111F<br />
Side-fitted DMS 2-11 A-PP/V/C-S-1111F<br />
96443969<br />
96443970<br />
96446961<br />
96446962<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 2-11 A-PV/V/C-F-1111F<br />
Side-fitted DMS 2-11 A-PV/V/C-S-1111F<br />
96437458<br />
96437459<br />
96446963<br />
96446964<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
Front-fitted DMS 2-11 A-SS/V/SS-F-11AAF<br />
Side-fitted DMS 2-11 A-SS/V/SS-S-11AAF<br />
96437466<br />
96437467<br />
96446965<br />
96446966<br />
PP EPDM Ceramic 4/6, 6/9 Front-fitted DMS 2-11 B-PP/E/C-F-1111F 96437474 -<br />
PP FKM Ceramic 4/6, 6/9 Front-fitted DMS 2-11 B-PP/V/C-F-1111F 96443977 -<br />
PVDF FKM Ceramic 4/6, 6/9 Front-fitted DMS 2-11 B-PV/V/C-F-1111F 96437478 -<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 Front-fitted DMS 2-11 B-SS/V/SS-F-11AAF 96437482 -<br />
PP EPDM Ceramic 4/6, 6/9 x DMS2-11 D-PP/E/C-X-1111F 96476529<br />
PP FKM Ceramic 4/6, 6/9 x DMS2-11 D-PP/V/C-X-1111F 96476532<br />
PVDF FKM Ceramic 4/6, 6/9 x DMS2-11 D-PV/V/C-X-1111F 96476533<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 x DMS2-11 D-SS/V/SS-X-11AAF 96476534<br />
PP EPDM Ceramic 4/6, 6/9<br />
Front-fitted DMS 4-7 A-PP/E/C-F-1111F<br />
Side-fitted DMS 4-7 A-PP/E/C-S-1111F<br />
96437452<br />
96437453<br />
96446967<br />
96446968<br />
PP FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 4-7 A-PP/V/C-F-1111F<br />
Side-fitted DMS 4-7 A-PP/V/C-S-1111F<br />
96443971<br />
96443972<br />
96446969<br />
96446970<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 4-7 A-PV/V/C-F-1111F<br />
Side-fitted DMS 4-7 A-PV/V/C-S-1111F<br />
96437460<br />
96437461<br />
96446971<br />
96446972<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
Front-fitted DMS 4-7 A-SS/V/SS-F-11AAF<br />
Side-fitted DMS 4-7 A-SS/V/SS-S-11AAF<br />
96437468<br />
96437469<br />
96446973<br />
96446974<br />
PP EPDM Ceramic 4/6, 6/9 Front-fitted DMS 4-7 B-PP/E/C-F-1111F 96437475 -<br />
PP FKM Ceramic 4/6, 6/9 Front-fitted DMS 4-7 B-PP/V/C-F-1111F 96443978 -<br />
PVDF FKM Ceramic 4/6, 6/9 Front-fitted DMS 4-7 B-PV/V/C-F-1111F 96437479 -<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 Front-fitted DMS 4-7 B-SS/V/SS-F-11AAF 96437483 -<br />
PP EPDM Ceramic 4/6, 6/9 x DMS4-7 D-PP/E/C-X-1111F 96476535<br />
PP FKM Ceramic 4/6, 6/9 x DMS4-7 D-PP/V/C-X-1111F 96476536<br />
PVDF FKM Ceramic 4/6, 6/9 x DMS4-7 D-PV/V/C-X-1111F 96476537<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 x DMS4-7 D-SS/V/SS-X-11AAF 96476538
Pump selection<br />
Max.<br />
capacity [l/h]<br />
Max.<br />
pressure [bar]<br />
Control<br />
variant<br />
1<br />
Pump<br />
head<br />
Materials 2<br />
Gaskets<br />
Valve<br />
balls<br />
Connection<br />
3<br />
Control<br />
panel<br />
position<br />
Type designation<br />
(variants A 4 and B)<br />
DME and DMS<br />
Product<br />
number<br />
Without With<br />
alarm relay alarm relay<br />
(variant A) (variant AR)<br />
PP EPDM Ceramic 4/6, 6/9<br />
Front-fitted DMS 8-5 A-PP/E/C-F-1111F<br />
Side-fitted DMS 8-5 A-PP/E/C-S-1111F<br />
96437454<br />
96437455<br />
96446975<br />
96446976<br />
A<br />
PP FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 8-5 A-PP/V/C-F-1111F<br />
Side-fitted DMS 8-5 A-PP/V/C-S-1111F<br />
96443973<br />
96443974<br />
96446977<br />
96446978<br />
AR<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 8-5 A-PV/V/C-F-1111F<br />
Side-fitted DMS 8-5 A-PV/V/C-S-1111F<br />
96437462<br />
96437463<br />
96446979<br />
96446980<br />
7.5<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
Front-fitted DMS 8-5 A-SS/V/SS-F-11AAF<br />
Side-fitted DMS 8-5 A-SS/V/SS-S-11AAF<br />
96437470<br />
96437471<br />
96446981<br />
96446982<br />
5.4<br />
PP EPDM Ceramic 4/6, 6/9 Front-fitted DMS 8-5 B-PP/E/C-F-1111F 96437476 -<br />
PP FKM Ceramic 4/6, 6/9 Front-fitted DMS 8-5 B-PP/V/C-F-1111F 96443979 -<br />
B PVDF FKM Ceramic 4/6, 6/9 Front-fitted DMS 8-5 B-PV/V/C-F-1111F 96437 80 -<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 Front-fitted DMS 8-5 B-SS/V/SS-F-11AAF 96437484 -<br />
PP EPDM Ceramic 4/6, 6/9 x DMS8-5 D-PP/E/C-X-1111F 96476540<br />
PP FKM Ceramic 4/6, 6/9 x DMS8-5 D-PP/V/C-X-1111F 96476541<br />
8.7 D PVDF FKM Ceramic 4/6, 6/9 x DMS8-5 D-PV/V/C-X-1111F 96476542<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 x DMS8- 5 D-SS/V/SS-X-11AAF 96476543<br />
PP EPDM Ceramic 4/6, 6/9<br />
Front-fitted DMS 12-3 A-PP/E/C-F-1111F<br />
Side-fitted DMS 12-3 A-PP/E/C-S-1111F<br />
96437456<br />
96437457<br />
96446951<br />
96446952<br />
A<br />
PP FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 12-3 A-PP/V/C-F-1111F<br />
Side-fitted DMS 12-3 A-PP/V/C-S-1111F<br />
96443975<br />
96443976<br />
96446953<br />
96446954<br />
AR<br />
PVDF FKM Ceramic 4/6, 6/9<br />
Front-fitted DMS 12-3 A-PV/V/C-F-1111F<br />
Side-fitted DMS 12-3 A-PV/V/C-S-1111F<br />
96437464<br />
96437465<br />
96446955<br />
96446956<br />
12<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4<br />
Front-fitted DMS 12-3 A-SS/V/SS-F-11AAF<br />
Side-fitted DMS 12-3 A-SS/V/SS-S-11AAF<br />
96437472<br />
96437473<br />
96446957<br />
96446958<br />
3.4<br />
PP EPDM Ceramic 4/6, 6/9 Front-fitted DMS 12-3 B-PP/E/C-F-1111F 96437477 -<br />
PP FKM Ceramic 4/6, 6/9 Front-fitted DMS 12-3 B-PP/V/C-F-1111F 96443980 -<br />
B PVDF FKM Ceramic 4/6, 6/9 Front-fitted DMS 12-3 B-PV/V/C-F-1111F 96437481 -<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 Front-fitted DMS 12-3 B-SS/V/SS-F-11AAF 96437485 -<br />
PP EPDM Ceramic 4/6, 6/9 x DMS 12-3 D-PP/E/C-X-1111F 96473184<br />
PP FKM Ceramic 4/6, 6/9 x DMS 12-3 D-PP/V/C-X-1111F 96476544<br />
13.7 D PVDF FKM Ceramic 4/6, 6/9 x DMS 12-3 D-PV/V/C-X-1111F 96476545<br />
Stainl. steel<br />
1.4401<br />
FKM<br />
Stainl. steel<br />
1.4401<br />
Rp 1/4 x DMS 12-3 D-SS/V/SS-X-11AAF 96476546<br />
1 See description of control variants on page 5.<br />
2 See list of pumped liquids on page 37.<br />
3 Underlined sizes are factory-fitted connections; others are supplied with the pump as standard.<br />
4/6 and 6/9 are compression fittings for inner/outer tubing diameters stated in mm.<br />
Rp 1/4 connection have inner thread for pipe connection.<br />
4 Also available in AR version.<br />
Variant<br />
D<br />
35
36<br />
Pump selection<br />
Non-standard range, DMS<br />
Example in bold: DMS 4-7 A-PP/V/C-S-1244F<br />
Max.<br />
capacity and<br />
pressure 2<br />
Control<br />
variant<br />
Materials of pump head,<br />
gaskets and valve balls<br />
[l/h] - [bar] See page 6 Dosing head:<br />
PP = Polypropylene<br />
PV = PVDF<br />
SS = Stainl. steel 1.4401<br />
DMS Pump<br />
head<br />
2-11<br />
4-7<br />
8-5<br />
12-3<br />
A-<br />
AR<br />
B<br />
D<br />
2 2-11: 2.5 l/h, 11 bar<br />
4-7: 4 l/h, 7 bar<br />
8-5: 7.5 l/h, 5.4 bar<br />
12-3: 12 l/h, 3.4 bar<br />
Gaskets:<br />
E = EPDM<br />
V = FKM<br />
T = PTFE<br />
Valve balls:<br />
C = Ceramic<br />
SS = Stainl. steel 1.4401<br />
T = PTFE<br />
PP<br />
PV<br />
SS<br />
PP<br />
PV<br />
SS<br />
PP<br />
PV<br />
SS<br />
Gasket Ball<br />
E<br />
V<br />
T<br />
V<br />
E<br />
E<br />
V<br />
T<br />
V<br />
E<br />
E<br />
V<br />
T<br />
V<br />
E<br />
C<br />
SS<br />
T<br />
SS<br />
C<br />
SS<br />
T<br />
Control panel<br />
position<br />
F = Front-fitted<br />
S = Side-fitted<br />
-F-<br />
-S-<br />
-F-<br />
-S-<br />
-F-<br />
SS -F-<br />
C<br />
SS<br />
T<br />
-X-<br />
SS -X-<br />
Motor<br />
voltage<br />
Valves<br />
1 =<br />
1 = Standard<br />
1 x 230 V, 50 Hz 2 = Spring-loaded<br />
2 =<br />
1 x 120 V, 60 Hz<br />
1 2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
Suction/discharge<br />
connection<br />
1 = Tubing 4/6+6/9<br />
2 = Tubing 6/9+6/12+9/12<br />
3 = Tubing 4/6<br />
4 = Tubing 6/9<br />
5 = Tubing 6/12<br />
6 = Tubing 9/12<br />
T = Tubing 0.17"/0.25"<br />
R = Tubing 0.25"/0.375"<br />
S = Tubing 0.375"/0.5"<br />
A = Threaded Rp 1/4<br />
B = Threaded Rp 3/8<br />
E = Cementing d.10<br />
F = Cementing d.12<br />
1<br />
2<br />
3<br />
4 5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
1<br />
2<br />
3<br />
4 5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
T<br />
R<br />
S<br />
A (PVC)<br />
E (PVC)<br />
F (PVC)<br />
A<br />
B<br />
V<br />
Y<br />
DME and DMS<br />
Mains<br />
plug<br />
F = EU<br />
B = USA+CAN<br />
G = UK<br />
I = AU<br />
E = CH<br />
J= JP<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
B<br />
G<br />
I<br />
E<br />
J<br />
F<br />
J<br />
F<br />
J
Pumped liquids<br />
List of pumped liquids<br />
The resistance table below is intended as a general<br />
guide for material resistance (at room temperature),<br />
and does not replace testing of the chemicals and pump<br />
materials under specific working conditions.<br />
Pumped liquid 20°C<br />
Concentration<br />
%<br />
PP<br />
DME and DMS<br />
The data shown are based upon information from<br />
various sources available, but many factors (purity,<br />
temperature, abrasive particles, etc.) may affect the<br />
chemical resistance of a given material.<br />
Note: Some of the liquids in this table may be toxic,<br />
corrosive or hazardous.<br />
Please be careful when handling these liquids.<br />
Pump housing<br />
Materials<br />
Gasket Ball<br />
PVDF<br />
25 – <br />
Acetic acid CH3COOH 60 – – <br />
85 – – – – <br />
Aluminium chloride AlCl3 40 – <br />
Aluminium sulphate Al2 (SO4 ) 3 60 <br />
Ammonia, aqueous NH4OH 28 – –<br />
Calcium hydroxide 7 Ca(OH) 2 –<br />
Calcium hypochlorite Ca(OCl) 2 20 – <br />
Chromic acid 5 10 <br />
H2CrO4 30<br />
40<br />
–<br />
–<br />
<br />
<br />
–<br />
–<br />
<br />
<br />
<br />
<br />
<br />
–<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
50 – – – <br />
Copper sulphate CuSO4 30 <br />
Ferric chloride3 FeCl3 100 – <br />
Ferric sulphate3 Fe2 (SO4 ) 3 100 <br />
Ferrous chloride FeCl2 100 – <br />
Ferrous sulphate FeSO4 50 <br />
Hydrochloric acid HCl<br />
< 25<br />
25-37<br />
<br />
<br />
<br />
<br />
–<br />
–<br />
<br />
<br />
<br />
–<br />
<br />
<br />
<br />
–<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
Hydrogen peroxide H2O2 30 <br />
10 <br />
Nitric acid HNO3 30<br />
40<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
–<br />
<br />
<br />
–<br />
–<br />
<br />
<br />
<br />
<br />
70 – – – – – <br />
Peracetic acid CH3COOOH 5 – – <br />
Potassium hydroxide KOH 50 – – –<br />
Potassium permanganate KMnO4 10 – <br />
Sodium chlorate NaClO3 30 <br />
Sodium chloride NaCl 30 – <br />
Sodium chlorite NaClO2 20 – – <br />
20 –<br />
Sodium hydroxide NaOH<br />
30 – –<br />
50 – –<br />
Sodium hypochlorite NaOCl 20 – <br />
Sodium sulphide Na2S 30 –<br />
Sodium sulphite 6 Na2SO3 20 –<br />
Sulphurous acid H2SO3 6 <br />
Sulphuric acid 4 H2SO4 < 80<br />
80-98<br />
<br />
<br />
<br />
<br />
–<br />
–<br />
<br />
–<br />
<br />
<br />
<br />
–<br />
<br />
–<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
–<br />
Suitable. 3 Risk of crystallisation.<br />
Stainl. steel<br />
1.4401<br />
Limited.<br />
4 Reacts violently with water and generates much heat.<br />
(Pump should be absolutely dry before dosing sulphuric acid.)<br />
– Not suitable. 5 Must be fluoride-free when glass balls are used.<br />
6 In neutral solutions.<br />
7 Saturated solution 0.1%.<br />
PVC<br />
FKM<br />
EPDM<br />
CSM<br />
PTFE<br />
Centellen C<br />
Ceramic<br />
Glass<br />
37
38<br />
<strong>Accessories</strong><br />
<strong>Accessories</strong><br />
Grundfos offers a comprehensive range of accessories<br />
covering every need when dosing with Grundfos dosing<br />
pumps.<br />
Overview<br />
Rigid suction line<br />
See page 53<br />
Foot valve<br />
See page 43<br />
Water meter<br />
see page 77<br />
Flow indicator<br />
See page 50<br />
Installation kit<br />
See page 39<br />
Counter-pressure or relief/<br />
isolating valve<br />
See page 57<br />
Automatic vent valve<br />
See page 62<br />
Multifunction valve<br />
See page 48<br />
Priming aid<br />
See page 67<br />
Tubing<br />
See page 42<br />
Rigid suction line<br />
with level sensors<br />
See page 53<br />
Level control unit<br />
See page 55<br />
Injection valve<br />
See page 45<br />
Pulsation dampener<br />
See page 64<br />
Pressure gauge<br />
See page 66<br />
Connector for pulsation dampener<br />
See page 65<br />
Pump connections<br />
See page 51<br />
Cable and plug<br />
See page 40<br />
Wall bracket<br />
See page 76<br />
Dosing monitor<br />
See page 49<br />
Tank<br />
See page 69<br />
Hand mixer<br />
See page 73<br />
Electric mixer<br />
See page 74<br />
Overview<br />
TM02 2099 3301
<strong>Accessories</strong><br />
Installation kit<br />
The installation kit includes:<br />
• foot non-return valve with strainer and weight<br />
• injection non-return valve, spring-loaded<br />
• 6 m PE discharge tubing<br />
• 2 m PVC suction tubing<br />
• 2 m PVC vent tubing.<br />
For pump types Size<br />
DME 2<br />
DME 8<br />
DME 12<br />
DMS 2<br />
DMS 4<br />
DMS 8<br />
DMS 12<br />
DME 19<br />
DME 48<br />
DN 4<br />
DN 8<br />
TM01 8956 0900<br />
Max. 2 metres<br />
Installation kit<br />
Max. 6 metres<br />
Max. 2 metres<br />
Valve materials Inner/outer tubing diameters Product<br />
number<br />
Housing Gasket Ball Suction Discharge Vent<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PVDF FKM Ceramic<br />
4/6 4/6 4/6 96457109<br />
6/9 6/9 4/6 96434858<br />
0.17"/1/4" 0.17"/1/4" 96480670<br />
1/4"/3/8" 1/4"/3/8" 96479881<br />
6/9 6/9 4/6 96446723<br />
4/6 4/6 4/6 96457110<br />
0.17"/1/4" 0.17"/1/4" 96480674<br />
1/4"/3/8" 1/4"/3/8" 96479898<br />
6/9 6/9 4/6 96434859<br />
4/6 4/6 4/6 96457111<br />
0.17"/1/4" 0.17"/1/4" 96480675<br />
1/4"/3/8" 1/4"/3/8" 96479899<br />
9/12 9/12 4/6 96440445<br />
3/8"/1/2" 3/8"/1/2" 96479947<br />
9/12 9/12 4/6 96446724<br />
3/8"/1/2" 3/8"/1/2" 96479949<br />
9/12 9/12 4/6 96440446<br />
3/8"/1/2" 3/8"/1/2" 96479948<br />
TM02 21083401<br />
39
40<br />
<strong>Accessories</strong><br />
Cable and plug<br />
Cable and plug for connection of pump to external<br />
control devices, such as process controllers, flow<br />
meters, start/stop contacts, and level sensors.<br />
Grundfos level control units are factory-fitted with cable<br />
and plug connection for Grundfos dosing pumps.<br />
The cables and plugs fit all dosing pumps, types DME<br />
and DMS-A.<br />
Cable material: PUR (0.34 mm 2 )<br />
Plug type: M12.<br />
Signal<br />
Number of<br />
poles<br />
Pulse, 0/4-20 mA, start/stop 5<br />
Dual-level 4<br />
Cable moulded with plug<br />
Type<br />
Cable length<br />
[m]<br />
Cable and plug<br />
TM01 8955 0900<br />
Product number<br />
2 96440447<br />
5 96440448<br />
2 96440450 1)<br />
5 96440451 1)<br />
Cable moulded with plug<br />
5 Stop dosing input and dosing output 1)<br />
3 Alarm relay cable with plug<br />
2<br />
5<br />
96527109<br />
96527111<br />
1)<br />
2<br />
5<br />
96534214<br />
96534215<br />
- 4 Extension cable 2 96483235<br />
Pulse, 0/4-20 mA, start/stop<br />
Dual-level<br />
1)<br />
Only DME 60-940 l/h<br />
5<br />
4<br />
Plug with terminals without cable<br />
-<br />
-<br />
96440449<br />
96440452
<strong>Accessories</strong><br />
Diaphragm leakage sensor (60 - 940 l/h)<br />
Optoelectronic leakage sensor to be inserted in the<br />
drain hole behind the diaphragm for sensing diaphragm<br />
breakage or leakage.<br />
The sensor unit consists of:<br />
• Transmitter receiver<br />
• Holder for fitting sensor in the drain hole of backplate<br />
• M12 plug and wire to transmit signal to pump.<br />
When the liquid gets into contact with the sensor, the<br />
light refraction changes, causing the sensor to emit a<br />
signal.<br />
The signal emitted from the sensor triggers the pump<br />
to stop dosing and give pump output alarm.<br />
Pump type Size Type Cable length [m] Product number<br />
DME (60-940 l/h) M12<br />
Leakage sensor<br />
M12<br />
GR 8211p<br />
0.5 m 96534443<br />
Diaphragm leakage sensor<br />
41
42<br />
<strong>Accessories</strong><br />
Tubing<br />
Tubing in various materials, sizes and lengths.<br />
TM01 8958 0900<br />
Tubing<br />
Inner/outer diameters [mm] Material Maximum pressure [bar] Length [m] Product number<br />
4/6<br />
6/9<br />
9/12<br />
PE<br />
PVC<br />
ETFE<br />
PE<br />
PVC<br />
ETFE<br />
PE<br />
PVC<br />
16 10 96441188<br />
16 50 96441190<br />
0.5 10 96441189<br />
0.5 50 96441191<br />
20 10 96441351<br />
20 50 96441352<br />
13 10 96441192<br />
13 50 96441195<br />
0.5 10 96441193<br />
0.5 50 96441194<br />
20 10 96441353<br />
20 50 96441354<br />
13 10 96441196<br />
13 50 96441198<br />
0.5 2 96535083<br />
0.5 10 96441197<br />
0,5 50 96441199<br />
ETFE<br />
20<br />
20<br />
10<br />
50<br />
96441355<br />
96441356<br />
12/19 PVC, textile-reinforced 15 10 96534489<br />
15/20 PVC 0,5 2 96535081<br />
16/24<br />
14 10 96441200<br />
19/27 10 5 96574383<br />
19/27 10 10 96574385<br />
25/34 PVC, textile-reinforced<br />
10 10 96441201<br />
25/34 10 5 96535070<br />
32/41 9 5 96535077<br />
32/41 9 10 96535079
<strong>Accessories</strong><br />
Foot valve<br />
Foot valve complete with non-return valve, strainer and<br />
tube or pipe connection.<br />
Dimensions<br />
Max. flow<br />
rate [l/h]<br />
15 DN 4<br />
72 DN 8<br />
TM01 9285 1600/GR8109<br />
DN 4, DN 8 DN 6, DN 10, DN 15, DN 20, DN 25<br />
Tubing/non-return valve Hose clamp Pipe cementing<br />
Non-return valve<br />
TM01 9276 1600/TM02 6433<br />
Materials Connection Dimensions<br />
Size Housing Gasket Ball Type<br />
PP EPDM Ceramic Tubing<br />
PP FKM Ceramic Tubing<br />
PV FKM Ceramic Tubing<br />
PP EPDM Ceramic Tubing<br />
PP FKM Ceramic Tubing<br />
PV FKM Ceramic Tubing<br />
Inner/outer<br />
tubing or pipe<br />
diameters<br />
TM01 2201 1600<br />
d ø<br />
[mm]<br />
L<br />
[mm]<br />
Product<br />
number<br />
4/6 - 36 72 96440526<br />
6/9 - 36 72 96440527<br />
0.17"/1/4" - 36 72 96480503<br />
1/4"/3/8" - 36 72 96479782<br />
4/6 - 36 72 96446860<br />
6/9 - 36 72 96446861<br />
0.17"/1/4" - 36 72 96480589<br />
1/4"/3/8" - 36 72 96479784<br />
4/6 - 36 72 96440529<br />
6/9 - 36 72 96440530<br />
0.17"/1/4" - 36 72 96480620<br />
1/4"/3/8" - 36 72 96479787<br />
6/9 - 36 72 96441841<br />
9/12 - 36 72 96440528<br />
1/4"/3/8" - 36 72 96480621<br />
3/8"/1/2" - 36 72 96479798<br />
6/9 - 36 72 96446865<br />
9/12 - 36 72 96446864<br />
1/4"/3/8" - 36 72 96480622<br />
3/8"/1/2" - 36 72 96480623<br />
6/9 - 36 72 96441842<br />
9/12 - 36 72 96440531<br />
1/4"/3/8" - 36 72 96480624<br />
3/8"/1/2" - 36 72 96479801<br />
Foot valve<br />
TM01 9277 1600<br />
Valve kit<br />
96499704<br />
96499705<br />
96499708<br />
96499706<br />
96499707<br />
96499709<br />
43
44<br />
<strong>Accessories</strong><br />
Max. flow<br />
rate [l/h]<br />
48 DN 6<br />
150 DN 10<br />
375 DN 15<br />
940<br />
DN 20<br />
DN 25<br />
PVC - Glass Pipe cementing -/12 12 32 37 96440535<br />
Stainl.<br />
steel<br />
CSM Stainl. steel<br />
Hose clamp 6/- 7 32 74 96446862<br />
Threaded<br />
-/Rp 1/4" Rp 1/4" 32 37 96446863<br />
-/NPT 1/4" NPT 1/4" 32 37 96479794<br />
PP EPDM<br />
22/26 39 115 96527112<br />
19/27<br />
PP<br />
Ceramics Hose clamp<br />
22/26 39 115 96527113<br />
FKM<br />
25/34<br />
PVDF 22/26 39 115 96527114<br />
PVC FKM Glass<br />
Stainl.<br />
steel<br />
FKM<br />
CSM<br />
Stainl. steel<br />
PVC FKM Glass<br />
Stainl.<br />
steel<br />
CSM Stainl. steel<br />
Hose clamp 9/- 10 50 86 96440532<br />
Pipe cementing -/16 16 50 56 96440536<br />
Threaded RP 3/4" RP 3/4" 39 115 96534450<br />
Hose clamp 9/- 10 50 86 96446727<br />
Threaded<br />
-/Rp 1/2" Rp 1/2" 50 56 96446855<br />
-/NPT 1/2" NPT 1/2" 50 56 96480625<br />
Hose clamp 16/- 17 64 135 96440533<br />
Pipe cementing -/20 20 64 94 96440537<br />
Hose clamp 16/- 16 64 135 96446856<br />
Threaded<br />
-/Rp 1/2" Rp 1/2" 64 94 96446857<br />
-/NPT 1/2" NPT 1/2" 64 94 96480627<br />
PP EPDM<br />
33/42 57 167 96527115<br />
PP FKM Glass Hose clamp<br />
32/41<br />
38/48<br />
33/42 57 167 96527116<br />
PVDF FKM 33/42 57 167 96527118<br />
Stainl.<br />
steel<br />
FKM Stainl. steel Threaded RP 1 1/4" RP 1 1/4" 57 167 96534454<br />
PVC FKM Glass<br />
Stainl.<br />
steel<br />
Materials Connection Dimensions<br />
Size Housing Gasket Ball Type<br />
CSM Stainl. steel<br />
Hose clamp 25/- 26 90 175 96440534<br />
Pipe cementing -/32 32 90 120 96440538<br />
Hose clamp 25/- 26 90 175 96446858<br />
Threaded<br />
Inner/outer<br />
tubing or pipe<br />
diameters<br />
d ø<br />
[mm]<br />
L<br />
[mm]<br />
Product<br />
number<br />
-/Rp 1" Rp 1" 90 120 96446859<br />
-/NPT 1" NPT 1" 90 120 96480628<br />
Foot valve<br />
Valve kit
<strong>Accessories</strong><br />
Injection valve<br />
Injection valve complete with spring-loaded non-return<br />
valve, injection pipe and tube or pipe connection.<br />
Spring material: Hastelloy C22<br />
Opening pressure:<br />
DN 4, DN 8: 0.7 bar<br />
DN 6, DN 10,<br />
DN 15, DN 25: 1.1 bar.<br />
Maximum temperature:<br />
PP, PVDF: 50°C<br />
PVC: 40°C<br />
Stainless steel: 80°C.<br />
Dimensions<br />
d<br />
Max. flow rate<br />
[l/h]<br />
DN 4, DN 8 DN 6, DN 10, DN 15, DN 20, DN 25<br />
L<br />
Size<br />
12 DN 4<br />
Non-return valve<br />
TM01 9278 3100 - TM02 6434<br />
Material Connection Dimensions<br />
Housing Gasket Ball Type<br />
PP EPDM Ceramic Tubing<br />
PP FKM Ceramic Tubing<br />
PV FKM Ceramic Tubing<br />
TM01 9279 1600<br />
Inner/outer tubing or<br />
pipe diameters<br />
d<br />
L<br />
[mm]<br />
Injection valve<br />
Product<br />
number<br />
4/6 G 1/2" 33 96440576<br />
6/9 G 1/2" 33 96440577<br />
0.17"/1/4" NPT 1/2" 33 96480641<br />
1/4"/3/8" NPT 1/2" 33 96479805<br />
4/6 G 1/2" 33 96446739<br />
6/9 G 1/2" 33 96446740<br />
0.17"/1/4" NPT 1/2" 33 96480642<br />
1/4"/3/8" NPT 1/2" 33 96479806<br />
4/6 G 1/2" 33 96440581<br />
6/9 G 1/2" 33 96440582<br />
0.17"/1/4" NPT 1/2" 33 96480643<br />
1/4"/3/8" NPT 1/2" 33 96479807<br />
GR8107 - GR7098<br />
Valve kit<br />
96499608<br />
96499609<br />
96499600<br />
45
46<br />
<strong>Accessories</strong><br />
Max. flow rate<br />
[l/h]<br />
72 DN 8<br />
72 DN6<br />
150 DN 10<br />
940<br />
Size<br />
PP EPDM Ceramic<br />
PP FKM Ceramic<br />
PV FKM Ceramic<br />
Stainl.<br />
steel<br />
AF<br />
Stainl.<br />
steel<br />
Tubing<br />
Pipe cementing<br />
Tubing<br />
Tubing<br />
Pipe cementing<br />
Tubing<br />
Tubing<br />
Pipe cementing<br />
Tubing<br />
6/9 G 1/2" 33 96446736<br />
9/12 G 1/2" 33 96440578<br />
-/10 G 1/2" 33 96440574<br />
-/12 G 1/2" 33 96440575<br />
1/4"/3/8" NPT 1/2" 33 96480644<br />
3/8"/1/2" NPT 1/2" 33 96480645<br />
6/9 G 1/2" 33 96446741<br />
9/12 G 1/2" 33 96446880<br />
-/10 G 1/2" 33 96446737<br />
-/12 G 1/2" 33 96446738<br />
1/4"/3/8" NPT 1/2" 33 96480646<br />
3/8"/1/2" NPT 1/2" 33 96479808<br />
6/9 G 1/2" 33 96446742<br />
9/12 G 1/2" 33 96440583<br />
-/10 G 1/2" 33 96440579<br />
-/12 G 1/2" 33 96440580<br />
1/4"/3/8" NPT 1/2" 33 96480647<br />
3/8"/1/2" NPT 1/2" 33 96479809<br />
Hose clamp 6/- G 1/2" 100 96446878<br />
Threaded<br />
-/Rp 1/4" G 1/2" 100 96446879<br />
-/NPT 1/4" NPT 1/2" 100 96479804<br />
-/NPT 1/2" NPT 1/2" 100 96480629<br />
PP EPDM<br />
G 3/4" 105 96527119<br />
PP FKM Ceramics Hose clamp<br />
19/27<br />
25/34<br />
G 3/4" 105 96527120<br />
PVDF FKM G 3/4" 105 96527121<br />
PVC FKM Glass<br />
Stainl<br />
steel<br />
FKM<br />
Stainl<br />
steel<br />
Hose clamp<br />
Pipe cementing<br />
9/- G 1" 100 96440568<br />
16/- G 1" 100 96440567<br />
-/12 G 1" 100 96440565<br />
-/16 G 1" 100 96440566<br />
Threaded RP 3/4" G 3/4" 105 96534457<br />
Hose clamp 9/- G 1" 100 96446875<br />
AF<br />
Threaded<br />
-/Rp 3/8"<br />
-/Rp 1/2"<br />
G 1"<br />
G 1"<br />
100<br />
100<br />
96446876<br />
96446877<br />
-/3/8"NPT NPT 1" 100 96480640<br />
Hose clamp 16/- G 1" 100 96440571<br />
375 DN 15 PVC FKM Glass<br />
Pipe cementing<br />
-/16<br />
-/20<br />
G 1"<br />
G 1"<br />
100<br />
100<br />
96440569<br />
96440570<br />
PP EPDM<br />
G 1" 98 96527122<br />
DN20<br />
PP<br />
PVDF<br />
FKM<br />
FKM<br />
Glass Hose clamp<br />
32/41<br />
38/48<br />
G 1"<br />
G 1"<br />
98<br />
98<br />
96527123<br />
96527124<br />
Stainl<br />
steel<br />
FKM<br />
Stainl<br />
steel<br />
Threaded RP 1 1/4" G 1" 98 96534459<br />
DN 25 PVC FKM PVDF<br />
Material Connection Dimensions<br />
Housing Gasket Ball Type<br />
Hose clamp<br />
Pipe cementing<br />
Inner/outer tubing or<br />
pipe diameters<br />
d<br />
L<br />
[mm]<br />
25/- G 1 1/2" 100 96440573<br />
25"/- NPT NPT 1.5" 100 96480649<br />
-/32 G 1 1/2" 100 96440572<br />
-/32" NPT NPT 1.5" 100 96480648<br />
Injection valve<br />
Product<br />
number<br />
Valve kit<br />
96499601<br />
96499602<br />
96499603
<strong>Accessories</strong><br />
Hot injection valve<br />
Complete hot injection valve kit assembly with shut-off<br />
valve, pipe and tubing connection fitting for chemical<br />
injection into steam and hot water application.<br />
The hot injection valve assembly allows for direkt<br />
dosing injection into systems with temperature of max.<br />
150°C at the injection valve point.<br />
The hot injection valve kit is delivered non-assembled<br />
to facilitate adaptation to the actual application.<br />
Materials:<br />
Shut-off ball valve SS 1.4401<br />
Pipe SS 1.4401<br />
Pipe connection SS 1.4401<br />
Tubing connection PVDF<br />
Max. injection point temperature<br />
Dimensions:<br />
150°C<br />
Shut-off ball valve 1/2"<br />
Pipe 8/10 mm<br />
Pipe connection 1/2"<br />
Tubing connection 6/9.<br />
GR 7506<br />
Hot injection valve<br />
Max. flow rate [l/h] Size<br />
Connection<br />
Material<br />
Gasket Ball Type<br />
Connection<br />
Tubing diameter<br />
Product number<br />
20 DN 4 PVDF FKM Ceramic Tubing 6/9 96534472<br />
47
48<br />
<strong>Accessories</strong><br />
Multifunction valve<br />
Compact valve unit for direct mounting on the pump<br />
discharge connection. The valve has four functions:<br />
1. Constant counter-pressure<br />
2. Anti-siphoning<br />
3. Pump protection<br />
4. Manual pressure relief.<br />
Relief pressure: 11 bar<br />
Constant counter pressure: 1.5 bar<br />
Maximum volume: 50 l/h.<br />
Dimensions<br />
Pump type<br />
DME and DMS a)<br />
DME and DMS<br />
up to 48 l/h<br />
Multifunction valve<br />
Housing<br />
Materials<br />
Gasket Diaphragm A<br />
Dimensions<br />
E<br />
Product number<br />
PVDF FKM FKM M28 x 2 M28 x 2 96497411<br />
PP<br />
EPDM<br />
FKM<br />
EPDM<br />
FKM<br />
M30 x 3.5<br />
M30 x 3.5<br />
M30 x 3.5<br />
M30 x 3.5<br />
96440584<br />
96440585<br />
PVDF FKM FKM M30 x 3.5 M30 x 3.5 96440586<br />
PVC<br />
a) M28 x 2 fits stainless steel pump heads.<br />
EPDM EPDM M30 x 3.5 M30 x 3.5 96496470<br />
FKM FKM M30 x 3.5 M30 x 3.5 96446752<br />
TM01 9583 2100 - TM01 8961 0900<br />
TM01 2220 1498
<strong>Accessories</strong><br />
Dosing monitor<br />
The dosing monitor is used in connection with the<br />
dosing monitoring function of DME and DMS-A, AR<br />
pumps.<br />
The monitor sends a pulse signal (closed contact) for<br />
every measured dosing stroke.<br />
As the DME pump will often operate without pulsation<br />
on the discharge side, the monitor must always be<br />
installed on the suction side.<br />
The monitor for a DMS pump can be installed on both<br />
suction and discharge side.<br />
Maximum pressure: 10 bar<br />
Maximum volume: 50 l/h<br />
Maximum liquid temperature: 35°C<br />
Maximum liquid viscosity: 20 mPas<br />
Maximum load of pulse<br />
transmitter (reed contact): 48 VAC/VDC, 0.5 A<br />
Materials in contact with liquid: PMMA/PVC/FKM.<br />
Selection table<br />
Dosing stroke<br />
measured<br />
Monitor mounted on suction<br />
side (DME and DMS)<br />
Dosing stroke<br />
measured<br />
Monitor mounted on discharge<br />
side (DMS only)<br />
Dosing stroke<br />
measured<br />
Monitor mounted in dosing tube.<br />
In discharge tube: DMS<br />
In suction tube: DME and DMS<br />
Dosing monitor<br />
Mounting Pump head Gasket Connection kit Product number<br />
In-line PP, PVDF<br />
Discharge side a) PP, PVDF<br />
Suction side PP, PVDF<br />
a) Not suitable for DME pumps.<br />
Not suitable for stainless steel pump heads.<br />
FKM<br />
4/6, 6/9, 9/12 mm<br />
0.17"/1/4", 1/4"/3/8", 3/8"/1/2"<br />
96470722<br />
96470726<br />
FKM 4/6, 6/9, 9/12 mm 96470721<br />
FKM<br />
EPPM<br />
0.17"/1/4", 1/4"/3/8", 3/8"/1/2"<br />
96470725<br />
96493010<br />
FKM Not needed<br />
96470723<br />
EPPM Pump connection is used for monitor<br />
96492899<br />
FKM Not needed<br />
96470724<br />
EPPM Pump connection is used for monitor<br />
96493011<br />
TM02 2472 4401<br />
TM02 2029 3201 - TM02 2030 3201 - TM02 2031 320 1<br />
49
50<br />
<strong>Accessories</strong><br />
Flow indicator<br />
The flow indicator is used for discharge monitoring.<br />
When the dosing pump is discharging liquid, the white<br />
ball will jump in the transparent pipe. Each dosing<br />
stroke causes a ball jump. The design of the flow indicator<br />
allows ball movements to be seen at flow rates<br />
from 0.1 to 45 l/h.<br />
At a steady flow, the ball will always be in the top position.<br />
The flow indicator installs and retrofits easily.<br />
Material: PVC grey, PVC transparent,<br />
PVDF, FKM, ceramic AI2O3. Maximum pressure: 10 bar<br />
Maximum pulsed flow: 45 l/h.<br />
Dimensions<br />
Pump type<br />
DME and DMS<br />
up to 48 l/h<br />
TM01 9791 3100<br />
TM01 9800 3200<br />
Dimensions<br />
A B C [mm] D [mm]<br />
Flow indicator<br />
Product number<br />
M30 x 3.5 M30 x 3.5 44 55 96446763
<strong>Accessories</strong><br />
Pump connections<br />
Separate, retrofit pump connections for adapting<br />
standard Grundfos pumps to installation-specific<br />
tubing, pipe types and sizes.<br />
The product number includes one connection with<br />
union.<br />
GR6987<br />
Pump connections<br />
For pump type Connection type Inner/outer tubing or pipe diameters/thread Material Product number<br />
DME 2<br />
DME 8<br />
DME 12<br />
DME 19<br />
DME 48<br />
DMS 2<br />
DMS 4<br />
DMS 8<br />
DMS 12<br />
Tubing<br />
Pipe cementing<br />
Inner thread<br />
4/6<br />
6/9<br />
6/12<br />
9/12<br />
DME 60-150 Hose clamp 19/27 + 25/34<br />
DME 375-940 Hose clamp 32/41 + 38/48<br />
Fits only stainless steel pumps.<br />
Polypropylene 96440468<br />
PVDF 96440469<br />
Polypropylene 96440470<br />
PVDF 96440471<br />
Polypropylene 96440472<br />
PVDF 96440473<br />
Polypropylene 96440474<br />
PVDF 96440475<br />
–/10 PVC 96440462<br />
–/12 PVC 96440464<br />
PVC 96440456<br />
–/Rp 1/4"<br />
PVDF<br />
St. steel 1.4401<br />
96440457<br />
964846 70<br />
St. steel 1.4401 96440458 *<br />
–/Rp 3/8" St. steel 1.4401 96440461 *<br />
PP 96535096<br />
PVDF 96535102<br />
PP 96535103<br />
PVDF 96535104<br />
51
52<br />
<strong>Accessories</strong><br />
Adaptor<br />
The adaptors are used for the connection of DME and<br />
DMS pumps to suction and discharge tubing sizes other<br />
than Grundfos standard sizes.<br />
The product number comprises two sets.<br />
Inner/outer tubing<br />
diameter<br />
Connection<br />
type<br />
Material<br />
Product<br />
number<br />
4/6<br />
PP<br />
PVDF<br />
96434861<br />
96434862<br />
6/9<br />
PP<br />
PVDF<br />
96434863<br />
96434865<br />
6/12<br />
PP<br />
PVDF<br />
96460449<br />
96460450<br />
9/12<br />
PP<br />
PVDF<br />
96460447<br />
96460448<br />
5/8<br />
Tubing<br />
PP<br />
PVDF<br />
96460434<br />
96460435<br />
6/8<br />
PP<br />
PVDF<br />
96460436<br />
96460437<br />
0.17"/1/4"<br />
PP<br />
PVDF<br />
96460438<br />
96460439<br />
1/4"/3/8"<br />
PP<br />
PVDF<br />
96460443<br />
96460444<br />
3/8"/1/2"<br />
PP<br />
PVDF<br />
96460445<br />
96460446<br />
12/-<br />
PP<br />
PVDF<br />
96534491<br />
96534493<br />
19/27<br />
Hose PP 96535109<br />
25/34<br />
clamp PVDF 96535110<br />
32/41<br />
PP 96535111<br />
38/48<br />
PVDF 96535112<br />
Rp 3/4"<br />
PVC 96533886<br />
Rp 1 1/4" PVC 96534799<br />
Rp 3/4” SS 96575256<br />
Rp 1 1/4” Inner SS 96575258<br />
NPT 3/4” thread PVC 96537892<br />
NPT 1 1/4” PVC 96567893<br />
NPT 3/4” SS 96537894<br />
NPT 1 1/4” SS 96537895<br />
TM02 2470 4401<br />
Adaptor
<strong>Accessories</strong><br />
Rigid suction line<br />
Pre-assembled rigid suction line with adjustable length<br />
for mounting in a tank. The suction line consists of foot<br />
valve with strainer, rigid suction pipe, tank connection<br />
thread and suction tube.<br />
For control variant A, the suction line is available with<br />
level sensors (NO-contacts) for warning and emptytank<br />
signals, supplied complete with cable and plug for<br />
pump connection.<br />
Material: PVC<br />
Material, wetted parts: PVC, glass<br />
Suction tubing length: 1.5 m, PVC-tube<br />
Level cable length: 1.5 m<br />
Level plug type: M12, 4-pole<br />
Maximum flow: 50 l/h<br />
Maximum load of<br />
level contacts: 50 V, 0.5 A<br />
Function of level contacts:<br />
Low level/empty tank = closed contact<br />
Black PE screw cap for ø33.5: 96483418.<br />
TM02 4551 1102/TM01 9288 1600<br />
Rigid suction line<br />
53
54<br />
<strong>Accessories</strong><br />
Dimensions<br />
With level sensors Without level sensors<br />
Maximum length L [mm] For Grundfos tank size [l] Inner/outer suction tubing diameters [mm]<br />
540 60<br />
750 100<br />
800 200<br />
900 300<br />
1125 500<br />
1250 1000<br />
TM01 2202 4701<br />
TM01 2377 1498<br />
Rigid suction line<br />
Product number<br />
With level sensors Without level sensors<br />
4/6 96441230 96417398<br />
6/9 96441236 96417401<br />
9/12 96449875 96449869<br />
0.17"/1/4" 96480729 96480710<br />
1/4"/3/8" 96479974 96480716<br />
3/8"/1/2" 96480737 96480723<br />
4/6 96441231 96446734<br />
6/9 96441237 96446735<br />
9/12 96449876 96449870<br />
0.17"/1/4" 96480730 96480711<br />
1/4"/3/8" 96480734 96480717<br />
3/8"/1/2" 96480738 96480724<br />
4/6 96441232 96417399<br />
6/9 96441238 96417402<br />
9/12 96449877 96449871<br />
0.17"/1/4" 96480731 96480712<br />
1/4"/3/8" 96479975 96480718<br />
3/8"/1/2" 96480739 96480725<br />
4/6 96441233 96441222<br />
6/9 96441239 96441224<br />
9/12 96449878 96449872<br />
0.17"/1/4" 96480732 96480713<br />
1/4"/3/8" 96480735 96480719<br />
3/8"/1/2" 96480000 96480726<br />
4/6 96441228 96421285<br />
6/9 96441234 96421286<br />
9/12 96449873 96449867<br />
0.17"/1/4" 96480727 96480707<br />
1/4"/3/8" 96479973 96480714<br />
3/8"/1/2" 96479999 96480720<br />
4/6 96441229 96417400<br />
6/9 96441235 96417403<br />
9/12 96449874 96449868<br />
0.17"/1/4" 96480728 96480709<br />
1/4"/3/8" 96480733 96480715<br />
3/8"/1/2" 96480736 96480721
<strong>Accessories</strong><br />
Level control unit<br />
For dosing pumps with level control input (variant A),<br />
complete with level sensors (NO-contacts), ceramic<br />
weight, cable and plug for pump connection.<br />
Material: PVC<br />
Level cable length: 2.5 m<br />
Level plug type: M12, 4-pole<br />
Maximum load of<br />
level contacts: 50 V, 0.5 A<br />
Function of level contacts:<br />
Low level/empty tank = closed contact<br />
Product number: 96440539.<br />
TM01 9587 2100<br />
Dimensions<br />
Level control unit<br />
TM01 9567 1600<br />
55
56<br />
<strong>Accessories</strong><br />
Counter-pressure or relief valve<br />
Adjustable valve for installation in the discharge tube.<br />
• Installed in-line, the valve functions as a counterpressure<br />
valve optimising dosing accuracy into systems<br />
with fluctuating pressure or as anti-siphoning<br />
valve when dosing into pressureless systems.<br />
• Installed in a T-connection with the valve outlet connected<br />
to the tank, the valve functions as a pressure<br />
relief valve or a safety valve, protecting the pump<br />
and the discharge tube against excessive pressures.<br />
Pressure range: 0-10 bar<br />
Diaphragm material: PTFE.<br />
Counter-pressure or relief valve<br />
TM01 9289 1600
<strong>Accessories</strong><br />
Counter-pressure or relief valve<br />
Size<br />
DN 6, DN 10, DN 15 DN 25, DN 32, DN 40<br />
Maximum<br />
flow rate [l/h]<br />
DN 6 25 Rp 1/4" 40 142<br />
DN 10 75 Rp 3/8" 55 147<br />
TM01 9290 1600<br />
A<br />
Dimensions<br />
C [mm] H [mm]<br />
Housing material<br />
Type<br />
PVC<br />
PVDF<br />
Counter-pressure or relief valve<br />
Connections<br />
TM01 9291 1600<br />
Inner/outer tubing or pipe<br />
diameters/thread<br />
Product number<br />
4/6 96440823<br />
6/9 96440825<br />
6/12 96440824<br />
Tubing<br />
9/12 96489009<br />
0.17"/1/4" 96487951<br />
1/4"/3/8" 96487906<br />
1/4"/1/2" 96487905<br />
Pipe cementing -/10 96440821<br />
Inner thread<br />
-/Rp 1/4" 96440822<br />
1/4" NPT 96487950<br />
4/6 96440828<br />
6/9 96440830<br />
Tubing<br />
6/12<br />
0.17"/1/4"<br />
96440829<br />
96487908<br />
1/4"/3/8" 96487972<br />
1/4"/1/2" 96487970<br />
Pipe cementing -/10 96440826<br />
Inner thread<br />
St. steel 1.4571 Inner thread<br />
PVC<br />
PVDF<br />
St. steel 1.4571<br />
-/Rp 1/4" 96440827<br />
1/4" NPT 96487907<br />
-/Rp 1/4" 96440831<br />
-1/4" NPT 96487973<br />
6/9 96449892<br />
Tubing<br />
6/12 96504917<br />
1/4"/3/8" 96487899<br />
Hose clamp 9/- 96440799<br />
Pipe cementing<br />
Inner thread<br />
-/12 96440796<br />
-/16 96440797<br />
-/Rp 3/8" 96440798<br />
-/3/8" NPT 96487898<br />
Tubing<br />
6/9<br />
1/4"/3/8"<br />
96449893<br />
96487941<br />
Hose clamp 9/- 96440803<br />
Pipe cementing<br />
Inner thread<br />
-/12 96440800<br />
-/16 96440801<br />
-/Rp 3/8" 96440802<br />
-/3/8" NPT 96487940<br />
Hose clamp 9/- 96440805<br />
Inner thread<br />
-/Rp 3/8" 96440804<br />
-3/8" NPT 96487942<br />
57
58<br />
<strong>Accessories</strong><br />
Size<br />
Maximum<br />
flow rate [l/h]<br />
DN 15 210 Rp 1/2" 75<br />
152<br />
130<br />
DN 25 390 Rp 1 140 240<br />
DN 32 640 Rp 1 1/4" 140<br />
DN 40 990 Rp 11/2" 152<br />
For stainless steel 1.4571<br />
A<br />
Dimensions<br />
C [mm] H [mm]<br />
Housing material<br />
Type<br />
242<br />
165<br />
252<br />
180<br />
PVC<br />
PVDF<br />
Counter-pressure or relief valve<br />
Hose clamp 16/- 96440807<br />
Pipe cementing -/20 96440806<br />
Inner thread<br />
-/Rp 1/2" 96440808<br />
-/1/2" NPT 96487943<br />
Hose clamp 16/- 96440810<br />
Pipe cementing -/20 96440809<br />
Inner thread<br />
St. steel 1.4571 Hose clamp<br />
PP<br />
-/Rp 1/2" 96440811<br />
-/1/2" NPT 96487944<br />
16/- 96440812<br />
-/Rp 1/2" 96440813<br />
-/1/2" NPT 96487945<br />
Hose clamp 25/- 96440815<br />
Inner thread<br />
St. steel 1.4571 Inner thread<br />
Connections<br />
Inner/outer tubing or pipe<br />
diameters/thread<br />
Product number<br />
-/Rp 1 96440814<br />
1/2" NPT 96487897<br />
-1"/ NPT 96487946<br />
-/Rp 1 96440816<br />
-/1" NPT 96487947<br />
PP Inner thread<br />
-/Rp 1 1/4"<br />
-/1 1/4" NPT<br />
96440817<br />
96487948<br />
St. steel 1.4571 Flange DN 32 96440818<br />
PP Inner thread<br />
-/Rp 1 1/2"<br />
-/1 1/2" NPT<br />
96440819<br />
96487949<br />
St. steel 1.4571 Flange DN 40 96440820
<strong>Accessories</strong><br />
Valve assembly<br />
Complete assembly of:<br />
• counter-pressure and relief valve or<br />
• relief and isolating valve.<br />
Valve diaphragm material: PTFE<br />
Pressure range of counter-pressure and relief valve:<br />
0-10 bar.<br />
TM01 9588 2100<br />
Valve assembly<br />
59
60<br />
<strong>Accessories</strong><br />
Counter-pressure and isolating valve/relief valve<br />
Valve functions Size<br />
Counter-pressure<br />
and isolating valve<br />
Counter-pressure<br />
and relief valve<br />
TM01 9589 1600<br />
TM01 9590 2100<br />
Maximum<br />
flow rate<br />
[l/h]<br />
DN6 25<br />
DN10 75<br />
DN15 210<br />
DN6 25<br />
DN10 75<br />
DN15 210<br />
Housing<br />
material<br />
TM01 9292 1600<br />
Counter-pressure and isolating valve/relief valve<br />
Type<br />
Connections Dimensions<br />
Inner/outer tubing or<br />
pipe diameters/<br />
thread<br />
A<br />
H<br />
[mm]<br />
TM01 9293 1600<br />
Product<br />
number<br />
4/6<br />
96440643<br />
PVC<br />
Tubing<br />
6/9<br />
6/12<br />
9/12 Rp 1/4" 155<br />
96440645<br />
96440644<br />
96488892<br />
Pipe cementing -/10 96440641<br />
Inner thread -/Rp 1/4" 96440642<br />
St.steel 1.4571 Inner thread -/Rp 1/4" 96440646<br />
PVC<br />
St.steel 1.4571<br />
PVC<br />
St.steel 1.4571<br />
Tubing 6/9<br />
96449895<br />
Hose clamp 9/- 96440596<br />
Pipe cementing<br />
-/12<br />
-/16 Rp 3/8"<br />
174<br />
96440593<br />
96440594<br />
Inner thread -/Rp 3/4" 96440595<br />
Hose clamp -/Rp 3/8" 96440598<br />
Inner thread -/Rp 1/4" 166 96440597<br />
Hose clamp 16/-<br />
96440600<br />
Pipe cementing<br />
Inner thread<br />
-/20<br />
-/Rp 1/2" Rp 1/2"<br />
180<br />
96440599<br />
96440601<br />
Hose clamp 16/- 96440602<br />
Inner thread -/Rp 1/2" 163 96440603<br />
4/6<br />
96440845<br />
PVC<br />
Tubing<br />
6/9<br />
6/12<br />
9/12 Rp 1/4" 155<br />
96440847<br />
96440846<br />
96489142<br />
Pipe cementing -/10 96440843<br />
Inner thread -/Rp 1/4" 96440844<br />
St.steel 1.4571 Inner thread -/Rp 1/4" 96440848<br />
PVC<br />
St.steel 1.4571<br />
PVC<br />
St.steel 1.4571<br />
Tubing 6/9<br />
96449894<br />
Hose clamp 9/- 96440835<br />
Pipe cementing<br />
-/12<br />
-/16 Rp 3/8"<br />
174<br />
96440832<br />
96440833<br />
Inner thread -/Rp 3/8" 96440834<br />
Hose clamp 9/- 96440837<br />
Inner thread -/Rp 3/8" 166 96440836<br />
Hose clamp 16/-<br />
96440839<br />
Pipe cementing<br />
Inner thread<br />
-/20<br />
-/Rp 1/2" Rp 1/2"<br />
180<br />
96440838<br />
96440840<br />
Hose clamp 16/- 96440841<br />
Inner thread -/Rp 1/2" 163 96440842
<strong>Accessories</strong><br />
Vent valve<br />
Manual vent valve for direct fiting into the DME and<br />
DMS pump heads up to 48 l/h.<br />
Pump type<br />
DME 2, DME 8<br />
DME 12, DME 19<br />
DME 48<br />
DMS 2, DMS 4<br />
DMS 8, DMS 12<br />
GR 8210<br />
Valve materials<br />
Housing Gasket Ball<br />
Venting valve<br />
Vent pipe Product number<br />
PP EPDM<br />
96534792<br />
PP FKM<br />
Ceramic 4/6<br />
96534794<br />
PV FKM 96534796<br />
61
62<br />
<strong>Accessories</strong><br />
Automatic vent valve<br />
Automatic vent valve for direct fitting on the pump<br />
discharge connection.<br />
Valve housing material: PMMA/PVC<br />
O-ring material: FKM<br />
Valve ball material: Glass<br />
Valve seat material: PVDF<br />
Pump head material: PP/PVDF<br />
Power cable length: 1.5 m<br />
Opening pressure: 10 bar<br />
Maximum flow: 45 l/h<br />
Supply voltage: 115/230 V, 50/60 Hz<br />
Plug type: EU (Schuko).<br />
The valve is available with and without timer.<br />
With timer:<br />
The valve is continuously connected to the power<br />
supply. The opening time and opening intervals are set<br />
on the timer.<br />
Without timer:<br />
The valve will open when power is supplied to the valve.<br />
This version is ideal for operation in connection with a<br />
dosing monitor.<br />
TM01 9591 2100/TM01 9592 2100<br />
Automatic vent valve
<strong>Accessories</strong><br />
Automatic vent valve (with timer)<br />
Pump type<br />
DME DMS<br />
up to 48 l/h<br />
A<br />
B<br />
Dimensions<br />
A + B<br />
M30 x 3.5<br />
Voltage Plug<br />
Automatic vent valve (with timer)<br />
Product number<br />
With timer Without timer<br />
Schuko (DIN) 96441085 96471079<br />
1 x 230 V, 50-60 Hz<br />
Switzerland<br />
UK<br />
96470743<br />
96471067<br />
96471080<br />
96471083<br />
Australia 96470744 96471085<br />
1 x 120 V, 50-60 Hz US 96441084 96471086<br />
TM01 2218 1498<br />
63
64<br />
<strong>Accessories</strong><br />
Pulsation dampener<br />
For the installation in the suction and the discharge<br />
tube, the pulsation pressure surges, and ensuring a<br />
steady flow. The dampener is particularly suitable for<br />
long discharge tubes and/or lines with a small diameter.<br />
Installed in the discharge tube, the dampener can be<br />
used for optimising dosing accuracy and for protection<br />
of pump and discharge line against pressure surges.<br />
Depending on the system pressure, it may be necessary<br />
to install a counter-pressure valve after the dampener<br />
to optimise its function.<br />
Maximum pressure: 10 bar.<br />
TM01 9593 2100<br />
Pulsation dampener
<strong>Accessories</strong><br />
Pulsation dampener<br />
Size<br />
Maximum<br />
flow rate<br />
[l/h]<br />
80 60<br />
250 150<br />
750 375<br />
2500 940<br />
Pulsation dampener<br />
Size 80 Size 250 Sizes 750 and 2500<br />
TM01 2206 1498<br />
Materials Connections Dimensions [mm]<br />
Housing Diaphragm Type<br />
PP<br />
PVC<br />
PP<br />
PVC<br />
PP<br />
PVC<br />
PP<br />
PVC<br />
Inner/outer tubing<br />
or pipe diameters/<br />
thread<br />
TM01 2207 1498<br />
A B C D E<br />
TM01 22081498<br />
Product<br />
number<br />
CSM Tubing<br />
6/9<br />
9/12<br />
96441075<br />
96488893<br />
FKM Tubing 6/9 96441074<br />
CSM Tubing<br />
FKM Tubing<br />
CSM<br />
FKM<br />
CSM<br />
FKM<br />
CSM<br />
FKM<br />
CSM<br />
FKM<br />
6/9 172 G 3/4" M6 50 96441077<br />
1/4"/3/8" 96480706<br />
6/9 96441076<br />
1/4"/3/8" 96479972<br />
Inner thread -/Rp 1/2"<br />
96440850<br />
Inner thread -/1/2" NPT 96480694<br />
Inner thread -/Rp 1/2" 96440849<br />
Inner thread<br />
Inner thread<br />
-/1/2" NPT<br />
-/Rp 1/2"<br />
314 140 G 1 1/4" M8 58<br />
96480693<br />
96440854<br />
Inner thread -/1/2" NPT 96480696<br />
Inner thread -/Rp 1/2" 96440852<br />
Inner thread -/1/2" NPT 96480695<br />
Inner thread -/Rp 1/2"<br />
96441071<br />
Inner thread -/1/2" NPT 96480700<br />
Inner thread -/Rp 1/2" 96441070<br />
Inner thread<br />
Inner thread<br />
-/1/2" NPT<br />
-/Rp 1/2"<br />
363 347 G 1 1/4" ø9 72<br />
96480698<br />
96441073<br />
Inner thread -/1/2" NPT 96480704<br />
Inner thread -/Rp 1/2" 96441072<br />
Inner thread -/1/2" NPT 96480703<br />
CSM Pipe cementing -/40<br />
96440856<br />
FKM<br />
CSM<br />
Pipe cementing<br />
Pipe cementing<br />
-/40<br />
-/40<br />
541 525 G 2 ø11 126<br />
96440855<br />
96440858<br />
FKM Pipe cementing -/40 96440857<br />
65
66<br />
<strong>Accessories</strong><br />
<strong>Accessories</strong> for pulsation dampeners<br />
Connector<br />
For direct fitting of pulsation dampener size 80 to pump<br />
discharge connection.<br />
Pump type A B C Product number<br />
DME<br />
DMS<br />
Rp 3/4" M30 32 96441089<br />
Dummy plug<br />
For installation of pulsation dampener in T-piece<br />
connection.<br />
Pulsation dampener<br />
size<br />
Dimension [mm]<br />
A<br />
Product number<br />
80 Rp 3/4" 96441092<br />
250, 750 Rp 1 1/4" 96441091<br />
2500 Rp 2 96441090<br />
Pressure gauge<br />
For measuring gas pressure in pulsation dampener.<br />
Pressure range Product number<br />
0-6 bar 96441096<br />
0-16 bar 96441095<br />
TM01 9596 2100<br />
TM01 2209 1498<br />
<strong>Accessories</strong> for pulsation dampeners<br />
TM01 9594 2100<br />
TM01 9595 2100<br />
TM01 2212 1498<br />
TM01 2211 1498
<strong>Accessories</strong><br />
Priming aid<br />
The priming aid is a transparent, air-tight collector with<br />
a screw cap on top. It is mounted between the tank and<br />
the pump. The inlet from the tank and the outlet to the<br />
pump are both at the bottom of the collector.<br />
The priming aid is supplied with a bracket for wall<br />
mounting and a rod for mounting on top of the tank.<br />
The priming aid has the following functions:<br />
• Priming.<br />
The priming aid facilitates priming in case of frequent<br />
stops and/or high suction lifts by eliminating<br />
or reducing the dry-suction phase.<br />
• Gas trap.<br />
Gas occurring in the suction tube is trapped in the<br />
top of the priming aid to prevent it from entering the<br />
dosing head.<br />
• Pulsation dampening.<br />
The dampening gas cushion in the top of the priming<br />
aid reduces pressure surges, resulting in optimum<br />
dosing accuracy and reduced risk of<br />
cavitation.<br />
Material: PVC.<br />
TM01 9597 2100<br />
Priming aid<br />
67
68<br />
<strong>Accessories</strong><br />
Priming aid<br />
Size/priming capacity [ml]<br />
95<br />
250<br />
Size 95 Size 250<br />
TM01 2214 1498<br />
Connections<br />
Type Inner/outer tubing diameters<br />
Tubing<br />
TM01 2216 1498<br />
Priming aid<br />
Product number<br />
4/6 96441079<br />
6/9 96441080<br />
0.17"/1/4" 96480692<br />
1/4"/3/8" 96479970<br />
6/9 96441078<br />
9/12 96483949<br />
1/4"/3/8" 96480690
<strong>Accessories</strong><br />
Tank<br />
Closed cylindrical tank with screw cap and threaded<br />
connection for rigid suction line.<br />
Material: PE.<br />
Liquid temperature: Minimum: –20°C.<br />
Maximum: +45°C.<br />
Pump mounting plate:<br />
The DME and DMS pumps can be mounted direct on<br />
the tank top by means of adapter plates.<br />
Material: PP.<br />
DME 2 to DME 12 and DMS: 96446765.<br />
DME 19 and DME 48: 96446766.<br />
Floor mounting bracket:<br />
Material: PE.<br />
Set of four: 96446767.<br />
TM01 9598 2100<br />
Tank<br />
69
70<br />
<strong>Accessories</strong><br />
Dimensions<br />
Floor mounting bracket<br />
Tank size [l]<br />
D<br />
Dimensions [mm]<br />
H<br />
Weight [kg] Product number<br />
60 415 575 4.5 96417362<br />
100 470 790 7.0 96417363<br />
200 600 845 13.0 96417364<br />
300 675 950 15.0 96441296<br />
500 815 1080 27.0 96417365<br />
1000<br />
Without pump mounting holes.<br />
1080 1358 39.0 96417366<br />
Tank<br />
TM01 2219 1498
<strong>Accessories</strong><br />
100-litre tank<br />
Closed square tank with screw cap and mounting platform<br />
for single or parallel pump mounting.<br />
The pump mounting platform is raised above the screw<br />
cap to protect pumps and connections when filling<br />
chemical into the tank.<br />
The height difference also allows for direct mounting of<br />
the dosing monitor on the suction side.<br />
Material: MDPE<br />
Weight: 15 kg<br />
Max. material temperature: +50°C<br />
Liquid temperature: Minimum –20°C<br />
Maximum +45°C.<br />
Mounting platform<br />
DME and DMS pumps can be fitted direct on the platform<br />
by means of brass inserts moulded into the platform.<br />
Mounting combination<br />
Single or parallel mounting of DME 0-48 l/h and DMS.<br />
The tank is prepared for the fitting of a 3/4" RG draining<br />
plug.<br />
Material thickness: 4 mm.<br />
Tank size Product number<br />
100 l 96489271<br />
GR7309<br />
100-litres tank<br />
71
72<br />
<strong>Accessories</strong><br />
Dimensions [mm]<br />
500 540<br />
ø152<br />
500<br />
137<br />
192<br />
670<br />
M5<br />
98<br />
98<br />
98<br />
TM02 6616 1103<br />
100-litres tank
<strong>Accessories</strong><br />
Hand mixer<br />
Hand mixer with adjustable length for mixing of chemicals<br />
in a tank. The mixer is designed for Grundfos<br />
chemical tanks.<br />
Material: PVC.<br />
Dimensions<br />
Tank size<br />
[l]<br />
Maximum length, L<br />
[mm]<br />
Product number<br />
60 450 96417377<br />
100 600 96417378<br />
200 750 96417379<br />
300 850 96446784<br />
500 950 96417380<br />
1000 1200 96417381<br />
TM01 9599 2100<br />
TM01 2222 1498<br />
Hand mixer<br />
73
74<br />
<strong>Accessories</strong><br />
Electric mixer<br />
Electric mixers ensure homogeneous mixing of the<br />
chemical solution in the tank. Mixing is essential for<br />
dissolving powder additives or liquid additives, which<br />
are not easily dilutable.<br />
The mixer is equipped with a single or three-phase<br />
motor, an mixer shaft connected to the motor shaft and<br />
a three-blade mixing propeller.<br />
The selection of the mixer size depends on whether<br />
readily-soluble substances, or permanently poorly<br />
miscible emulsions or insoluble suspensions are to be<br />
stabilised. The latter requires higher power input and, if<br />
necessary, continuous operation instead of intermittent<br />
operation.<br />
The shaft and the propeller must be submerged into the<br />
liquid during operation. The mixer must be protected<br />
against dry-running.<br />
Mixer shaft material: PTFE-coated, stainless<br />
steel<br />
DIN W.-Nr.1.4571<br />
Propeller material: PVDF<br />
Motor insulation class: F<br />
Enclosure class: IP 55.<br />
Shaft length<br />
L [mm]<br />
500<br />
700<br />
800<br />
900<br />
1000<br />
Voltage, frequency<br />
Motor size<br />
[kW]<br />
If the mixer is mounted on a Grundfos tank, a mounting<br />
plate must be used:<br />
Speed<br />
[min -1 ]<br />
Electric mixer<br />
Product number<br />
PTFE-coated stainless steel Stainless steel<br />
1 x 230 V, 50 Hz 0.09 1420 96446789 96449515<br />
3 x 400 V, 50 Hz 0.12 1370 96446796 96449522<br />
1 x 230 V, 50 Hz 0.09 1420 96446790 96449516<br />
3 x 400 V, 50 Hz 0.12 1370 96446797 96449523<br />
1 x 230 V, 50 Hz 0.09 1420 96446791 96449517<br />
3 x 400 V, 50 Hz 0.12 1370 96446798 96449524<br />
1 x 230 V, 50 Hz<br />
0.09<br />
0.18<br />
1420<br />
1450<br />
96446792<br />
96446793<br />
96449518<br />
96449519<br />
3 x 400 V, 50 Hz<br />
0.12<br />
0.25<br />
1370<br />
1420<br />
96446800<br />
96446801<br />
96449525<br />
96449526<br />
1 x 230 V, 50 Hz<br />
0.09<br />
0.18<br />
1420<br />
1450<br />
96446794<br />
96446795<br />
96449520<br />
96449521<br />
3 x 400 V, 50 Hz<br />
0.12<br />
0.25<br />
1370<br />
1420<br />
96446802<br />
96446804<br />
96449527<br />
96449528<br />
Tank size [l] Product number<br />
60 96467256<br />
100 96467257<br />
200 96467258<br />
300 96467259<br />
500 96467330<br />
1000 96471403<br />
TM01 9790 3100
<strong>Accessories</strong><br />
Dimensions<br />
Motor size<br />
[kW]<br />
0.09<br />
0.12<br />
0.18<br />
0.25<br />
Sealing flange<br />
Dimensions [mm]<br />
A B C D E F G H<br />
140 115 95 15 9 9.5 100 195<br />
160 130 110 - 9 9.5 100 220<br />
When mixing aggressive liquids, the use of a sealing<br />
flange for protection of the motor is recommended.<br />
Product number 96446805. The sealing flange is made<br />
of polypropylene and sealed with a V-ring.<br />
Note: The sealing flange fits 0.09 and 0.12 kW mixers.<br />
Other flanges are available on request.<br />
TM01 9806 3200<br />
Electric mixer<br />
75
76<br />
<strong>Accessories</strong><br />
Wall bracket<br />
Wall bracket for easy installation of the dosing pump on<br />
a wall.<br />
Dimensions<br />
A<br />
A<br />
221<br />
133<br />
75<br />
121<br />
123.5<br />
A-A<br />
ø5<br />
Pump type Material Product number<br />
DME and DMS<br />
up to 48 l/h<br />
PPO 96441202<br />
ø3.5<br />
TM02 4360 0602<br />
TM02 4306 0402<br />
Wall bracket
<strong>Accessories</strong><br />
Water meter<br />
In-line water meter with potential-free pulse signal for<br />
use in flow-proportional dosing applications.<br />
Qn 1.5 and Qn 2.5 meters are of the multi-jet, dry dial<br />
type for cold water up to 30°C or hot water up to 90°C.<br />
Qn 15 meters and up are of the helical vane type for<br />
cold water up to 50°C or hot water up to 120°C.<br />
Max. pressure: 16 bar.<br />
If the water meter is to be connected to the pump pulse<br />
input, a control plug should be used.<br />
Product number of control plug: 96440449.<br />
Qn 1.5 to Qn 15 meters are threaded.<br />
Qn 40 to Qn 150 meters are flanged.<br />
Cable length: 3 metres<br />
Maximum load, reed contact: 30 VAC/VDC, 0.2 A.<br />
Qn<br />
[m 3 /h]<br />
Pulse rate<br />
[l/pulse]<br />
Dimensions<br />
Maximum<br />
shortperiod<br />
capacity<br />
[m 3 /h]<br />
Maximum<br />
pressure<br />
[bar]<br />
Transitional<br />
capacity with<br />
error<br />
± 2% [l/h]<br />
Minimum<br />
capacity<br />
with error<br />
± 5% [l/h]<br />
Product number<br />
Maximum water temperature<br />
Water meter<br />
30°C 50°C 90°C 120°C<br />
1.5 1 3 16 120 50 96446846 - 96446897 -<br />
2.5 2.5 5 16 200 70 96446847 - 96446898 -<br />
15 10 30 16 3000 450 - 96446848 - 96446899<br />
1.5 0.25 3 16 120 50 96482640 - 96482643 -<br />
2.5 0.25 5 16 200 70 96482641 - 96482644 -<br />
15 2.5 30 16 3000 450 96482642 - 96482645 -<br />
40 100 80 10 4000 700 - 96446849 - 96446900<br />
60 25 120 10 6000 1200 - 96446850 - 96446901<br />
150 100 300 10 12000 3000 - 96446851 - 96446902<br />
Size Meter connections Installation kit connections<br />
Meter port-to-port length<br />
[mm]<br />
Port-to-port length incl. kit<br />
[mm]<br />
Threaded connections<br />
Qn 1.5 G 3/4" Rp 1/2" 165 245<br />
Qn 2.5 G 1" Rp 3/4" 190 288<br />
Qn 15<br />
Flanged connections<br />
G 2.5" Rp 2" 300 438<br />
Qn 40 DN 80 - 225 -<br />
Qn 60 DN 100 - 250 -<br />
Qn 150 DN 150 - 300 -<br />
GR5806p<br />
77
V7164097 0305<br />
Repl.: V7 16 40 97 03 04<br />
www.grundfos.com<br />
GB<br />
GRUNDFOS A/S . DK-8850 Bjerringbro . Denmark<br />
Telephone: +45 87 50 14 00.<br />
Being responsible is our foundation<br />
Thinking ahead makes it possible<br />
Innovation is the essence<br />
Subject to alterations.