4.2 Agency Approvals<br />

4.1.3 Proof-er<br />

If the Proof-er is not functioning properly, listed below are<br />

potential problems and corrective action.<br />

1. Proof-er does not return to the down position after it is<br />

activated.<br />

CAUSE REMEDY<br />

Defective return spring. Replace Spring.<br />

Buildup between the shaft Clean Proof-er to<br />

and housing restricting remove buildup.<br />

movement.<br />

Handle stops are not adjusted Adjust handle stop<br />

properly. screws in or out to allow<br />

the handle to move to<br />

the proper position.<br />

2. Switch will not trip when Proof-er is activated.<br />

CAUSE REMEDY<br />

The switch mechanism is Check switch<br />

defective and not the Proof-er. mechanism.<br />

Handle stops are not adjusted Adjust handle stop<br />

properly. screws in or out to allow<br />

the handle to move to<br />

the proper position.<br />

AGENCY APPROVED MODEL APPROVAL CLASSES<br />

FM All with an electric switch mechanism and a housing Class I, Div 1, Groups C & D<br />

listed as Type 4X/7/9 Class II, Div 1, Groups E, F & G<br />

All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & D<br />

listed as Type 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G<br />

CSA All with a Series HS or F electric switch mechanism<br />

and a housing listed as CSA Type 4X<br />

Class I, Div 2, Groups B, C & D<br />

All with an electric switch mechanism and a housing Class I, Div 1, Groups C & D<br />

listed as Type 4X/7/9 ➀ Class II, Div 1, Groups E, F & G<br />

All with an electric switch mechanism and a housing Class I, Div 1, Groups B, C & D<br />

listed as Type 4X/7/9 Class I, Div 1, Group B Class II, Div 1, Groups E, F & G<br />

ATEX / All with an electric switch mechanism and an ATEX II 2 G EEx d IIC T6<br />

IEC Ex ➂ ATEX housing ➁ 94/9/EC<br />

IEC Ex Ex d IIC T6<br />

IP66<br />

CE Low Voltage Directives 2006/95/EC Installation Category II<br />

Per Harmonized Standard:<br />

EN 61010-1/1993 & Amendment No. 1<br />

Pollution Degree 2<br />

12 45-610 Displacer Type Liquid Level Switches and Proof-er ® Switches