➀ With housing drain, CSA drops Group E and FM drops Group C.<br />

➁ Models B10 and B15 with “HS” switches and all Model C10 and C15 are not ATEX approved.<br />

➂ IEC Installation <strong>Instruction</strong>s:<br />

The cable entry and closing devices shall be Ex d certified suitable for the conditions of use<br />

and correctly installed.<br />

For ambient temperatures above +55° C or for process temperatures above +150° C, suitable<br />

heat resistant cables shall be used.<br />

Heat extensions (between process connection and housing) shall never be insulated.<br />

Special conditions for safe use:<br />

When the equipment is installed in process temperatures higher than +85° C the temperature<br />

classification must be reduced according to the following table as per IEC60079-0.<br />

Maximum Process<br />

Temperature<br />

4.3 Specifications<br />

Temperature<br />

Classification<br />

< 85° C T6<br />

< 100° C T5<br />

< 135° C T4<br />

< 200° C T3<br />

< 300° C T2<br />

< 450° C T1<br />

These units are in conformity with IECEx KEM 05.0020X<br />

Classification Ex d IIC T6<br />

T ambient -40° C to +70° C<br />

4.3.1 Basic Electrical Ratings<br />

Displacer<br />

4.3.2 Pressure/Temperature Ratings<br />

Switch Series and Non-Inductive Ampere Rating<br />

B C D F HS O Q<br />

120 VAC 15.00 15.00 10.00 0.25 5.00 15.00 15.00<br />

240 VAC 15.00 15.00 — — 5.00 15.00 15.00<br />

24 VDC 6.00 10.00 10.00 4.00 5.00 — 6.00<br />

120 VDC 0.50 1.00 10.00 0.30 0.50 1.00 0.50<br />

240 VDC 0.25 0.50 3.00 — 0.25 0.50 0.25<br />

Threaded Models* 800 psig @ +100° F (55 bar @ +38° C)<br />

250 psig @ +400° F (17 bar @ +204° C)<br />

Flanged Models Limited to the pressure rating of the selected flange or displacer. Cast iron flanges are flat face type conforming to<br />

ANSI dimensional specifications<br />

Low Pressure 25 psig @ +200° F (1.7 bar @ +93° C)<br />

Proof-er Models<br />

Medium Pressure 125 psig @ +300° F (8.6 bar @ +149° C)<br />

Proof-er Models<br />

*Models with stainless steel displacers are rated 720 psig @ +100° F (50 bar @ +38° C)<br />