Appendix – Figures<br />

CA T20 ECER (Btu/Wh)<br />

Water Consumption (GPH)<br />

40<br />

35<br />

30<br />

25<br />

20<br />

15<br />

High<br />

Medium<br />

Low<br />

Figure 18: CA T20 ECER versus Supply Airflow<br />

10<br />

0 200 400 600 800 1,000 1,200 1,400 1,600<br />

4.0<br />

3.8<br />

3.6<br />

3.4<br />

3.2<br />

3.0<br />

2.8<br />

2.6<br />

2.4<br />

2.2<br />

Large Symbols have <strong>the</strong> Required<br />

0.3" <strong>of</strong> water Resistance<br />

High<br />

Medium<br />

Low<br />

491-06.12.doc A-4<br />

Supply Airflow (CFM)<br />

Intake Air at<br />

91°Fdb / 69°Fwb<br />

Figure 19: Water Consumption Rate versus Supply Airflow<br />

Exhaust Damper Open<br />

Exhaust Damper Closed<br />

2.0<br />

0 200 400 600 800 1,000 1,200 1,400 1,600<br />

Supply Airflow (CFM)<br />

Intake Air at<br />

91°Fdb / 69°Fwb<br />

Exhaust Damper Open<br />

Exhaust Damper Closed