491-06.12.doc A-8<br />

Table 6: <strong>OASys</strong> Test Data (Continued)<br />

Test Summary Information Sensitivity to External Resistance Voltage Sensitivity - Damper Closed, Intake at 91°Fdb / 69°Fwb<br />

General High Fan Speed Medium Fan Speed<br />

Date (2006) 27-Sep 27-Sep 27-Sep 27-Sep 27-Sep 27-Sep 21-Sep 21-Sep 21-Sep 21-Sep 21-Sep 21-Sep 21-Sep<br />

Start Time 2:39p 2:54p 3:09p 3:24p 3:40p 3:47p 3:10p 2:50p 4:45p 3:34p 4:00p 4:22p 4:33p<br />

Duration (minutes) 10 10 10 10 5 5 10 15 10 10 10 10 10<br />

Barometric Pressure (in. <strong>of</strong> Hg)<br />

Inlet Air Properties<br />

29.56 29.56 29.56 29.56 29.55 29.55 29.33 29.33 29.25 29.32 29.31 29.29 29.26<br />

Dry Bulb Temperature (°F) 91.0 91.0 91.0 91.0 90.9 91.0 90.9 91.0 91.1 91.0 91.0 91.0 91.0<br />

Dew Point Temperature (°F) 57.9 57.9 58.0 57.6 57.6 57.7 56.7 57.9 57.7 58.0 58.3 58.0 57.3<br />

Wet Bulb Temperature (°F) 69.1 69.1 69.1 68.9 68.9 69.0 68.4 69.0 68.9 69.0 69.2 69.0 68.7<br />

Wet Bulb Depression (°F) 22.0 22.0 21.9 22.1 22.1 22.1 22.6 22.0 22.2 22.0 21.8 22.0 22.3<br />

Relative Humidity (%)<br />

Interstage Air Properties<br />

33.0 32.9 33.1 32.6 32.6 32.7 31.6 33.0 32.6 33.0 33.4 33.0 32.3<br />

Measured Dry Bulb Temperature (°F) 72.7 73.7 72.8 73.6 73.7 74.2 71.8 73.8 70.8 75.3 72.9 74.1 73.5<br />

Calculated Dry Bulb Temperature (°F) 1<br />

Supply Air Properties<br />

86.1 85.5 85.2 84.6 84.2 84.1 84.3 84.0 84.0 83.8 83.8 83.4 83.1<br />

Dry Bulb Temperature (°F) 69.4 69.1 68.9 68.4 68.1 68.1 67.3 67.8 67.6 67.7 67.8 67.6 67.1<br />

Dew Point Temperature (°F) 66.1 66.0 66.0 65.7 65.6 65.7 65.3 65.9 65.8 65.9 66.0 65.7 65.3<br />

Wet Bulb Temperature (°F) 67.6 67.4 67.3 66.9 66.8 66.9 66.3 66.9 66.7 66.8 67.0 66.7 66.3<br />

Relative Humidity (%) 91.2 91.7 92.3 92.9 93.4 94.0 95.2 95.4 95.7 95.7 95.8 95.6 96.0<br />

External Resistance (IW)<br />

Exhaust Air Properties<br />

0.00 0.10 0.20 0.30 0.40 0.50 0.30 0.30 0.30 0.30 0.30 0.30 0.30<br />

Dry Bulb Temperature (°F) 84.6 83.4 82.4 81.5 80.8 80.1 80.2 80.5 80.1 80.5 80.3 80.0 79.7<br />

Dew Point Temperature (°F) 77.8 77.4 76.8 76.1 75.5 75.0 74.6 75.2 75.0 75.2 75.2 75.1 74.8<br />

Wet Bulb Temperature (°F) 79.5 78.9 78.2 77.5 76.9 76.3 76.1 76.6 76.3 76.6 76.5 76.4 76.0<br />

Relative Humidity (%)<br />

Water Properties<br />

80.3 82.0 83.2 83.8 83.9 84.4 83.3 83.8 84.3 83.8 84.5 85.2 85.0<br />

Basin Temperature (°F) 72.1 71.6 71.7 70.7 70.1 69.7 70.1 70.2 69.5 70.4 70.0 69.8 69.5<br />

Makeup Water Flow (gph) - measured 3.4 3.8 3.1 3.9 2.9 2.6 3.3 2.7 3.7 3.1 2.9 2.7 2.6<br />

Total Evaporation Rate (gph) - calculated 3.9 3.8 3.6 3.6 3.4 3.3 3.2 3.0 3.0 2.9 2.7 2.6 2.5<br />

Fraction to Supply Air (%)<br />

Power Consumption<br />

73% 68% 64% 61% 57% 53% 61% 59% 60% 58% 57% 55% 54%<br />

Voltage (V) 115 115 115 115 115 115 121 115 116 111 104 101 95<br />

Current (A) 6.4 6.4 6.4 6.4 6.4 6.4 4.4 4.3 4.3 4.3 4.3 4.3 4.3<br />

Power (W) 586 587 586 586 587 584 456 436 436 419 396 381 359<br />

Power Factor 0.80 0.80 0.80 0.80 0.80 0.80 0.87 0.87 0.87 0.88 0.88 0.88 0.88<br />

Fan Speed (RPM)<br />

Performance<br />

1,121 1,121 1,121 1,121 1,121 1,122 1,023 1,001 1,000 977 938 910 864<br />

Dry Bulb Temperature Drop (°F) 21.6 21.9 22.1 22.6 22.8 23.0 23.6 23.2 23.5 23.3 23.2 23.4 23.9<br />

Dew Point Temperature Rise (°F) 8.2 8.1 8.0 8.1 8.0 8.0 8.6 8.0 8.1 7.9 7.7 7.8 8.0<br />

Wet-Bulb Effectiveness (%) 98.4 99.8 100.9 102.2 103.3 104.1 104.7 105.4 105.9 106.0 106.2 106.5 107.2<br />

Supply Airflow Rate (CFM) 1,451 1,338 1,238 1,141 1,039 934 981 944 954 909 848 801 726<br />

Exhaust Airflow Rate (CFM) 194 232 263 293 324 352 283 285 275 277 271 269 265<br />

Intake Airflow Rate (CFM) 1,637 1,562 1,494 1,427 1,357 1,279 1,257 1,223 1,223 1,180 1,114 1,065 986<br />

Fan Intake CFM / W 2.79 2.66 2.55 2.44 2.31 2.19 2.76 2.80 2.81 2.82 2.82 2.80 2.75<br />

Room Capacity (tons; 80°F reference) 1.32 1.26 1.18 1.14 1.06 0.96 1.06 0.98 1.01 0.95 0.88 0.85 0.80<br />

Room EER (Btu/Wh, 80°F reference) 27.1 25.7 24.2 23.3 21.7 19.7 28.0 27.0 27.8 27.3 26.7 26.7 26.7<br />

CA T-20 ECER (Btu/Wh) 2<br />

- - - - - - - - - - - - -<br />

Sensible Cooling <strong>of</strong> Outside Air (tons) 2.70 2.52 2.35 2.22 2.04 1.84 1.98 1.87 1.91 1.81 1.68 1.60 1.48<br />

Outside Air EER (Btu/Wh) 55.2 51.6 48.2 45.4 41.7 37.9 52.1 51.4 52.6 51.7 50.8 50.5 49.5<br />

1<br />

Calculated interstage temperature is <strong>the</strong> intersection <strong>of</strong> <strong>the</strong> intake dew point and <strong>the</strong> supply wet bulb.<br />

2 ECER can only be derived when <strong>the</strong> supply resistance is 0.3" and <strong>the</strong> wet-bulb depression is >=25°F<br />

Appendix – Test Data