Appendix – Figures<br />

Sensible Cooling Capacity (Tons)<br />

Sensible EER (Btu/Wh)<br />

4.0<br />

3.5<br />

3.0<br />

2.5<br />

2.0<br />

1.5<br />

1.0<br />

0.5<br />

Figure 22: Sensible Capacity versus Wet-Bulb Depression<br />

Low, 90°Fdb<br />

Low, 100°Fdb<br />

Low, 110°Fdb<br />

Medium, 90°Fdb<br />

Medium, 100°Fdb<br />

Medium, 110°Fdb<br />

High, 90°Fdb<br />

High, 100°Fdb<br />

High, 110°Fdb<br />

0.0<br />

10 15 20 25 30 35 40 45<br />

100<br />

90<br />

80<br />

70<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

Low, 90°Fdb<br />

Low, 100°Fdb<br />

Low, 110°Fdb<br />

Medium, 90°Fdb<br />

Medium, 100°Fdb<br />

Medium, 110°Fdb<br />

High, 90°Fdb<br />

High, 100°Fdb<br />

High, 110°Fdb<br />

491-06.12.doc A-6<br />

Intake Wet-Bulb Depression (°F)<br />

65°Fwb<br />

Figure 23: Sensible EER versus Wet-Bulb Depression<br />

OA Cap = 0.0888 × WBD<br />

75°Fwb<br />

OA Cap = 0.0713 × WBD<br />

Room<br />

Capacity<br />

(80°F Ref.)<br />

OA Cap = 0.0535 × WBD<br />

0<br />

10 15 20 25 30 35 40 45<br />

Intake Wet-Bulb Depression (°F)<br />

70°Fwb<br />

OA EER = 2.005 × WBD<br />

OA EER = 1.846 × WBD<br />

OA EER = 1.694 × WBD<br />

Room<br />

EER<br />

(80°F Ref.)