Example 4: Top to Vertical High Level Kit<br />
This example incorporates two 45 degree bends, a situation commonly encountered when having to route flue<br />
pipe around an obstacle such as a beam. When calculating the horizontal run the 45 degree bends equate to<br />
an additional 500mm per bend.<br />
Taking the ratio diagram as an example we can calculate the flue parameters for a top to vertical flue system.<br />
Total Height = A<br />
Total Horizontal = B<br />
In this example<br />
A = 4.5 Metres B = 1.5 Metres<br />
2 x 45deg bends have been used. The two 45 degree bends increase the horizontal length by one metre.<br />
(500mm extra horizontal length per 45 degree bend).<br />
Total height A = 4.5 Metres<br />
Total Horizontal B = 2.0 Metres<br />
In this example there is sufficient vertical rise for the horizontal run, as shown in the illustration on page 6.<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
<br />
(accessory)<br />
Components used<br />
Description Part No. Quantity<br />
Top to Vertical<br />
High Level Kit<br />
150mm<br />
MS91100<br />
180mm<br />
MS91101<br />
1<br />
1 metre length MS91028 MS91034 5<br />
Adjustable<br />
length<br />
MS91045 MS91046 1<br />
45° short bend MS91054 MS91055 2<br />
Wall band MS91052 MS91053 5<br />
Roof flashing MS91063 MS91063 1<br />
© EUROHEAT DISTRIBUTORS (H.B.S) LTD. 11<br />
Technical <strong>Guide</strong> IN1105 Ed 5 May 2009