Example 2: Top to Horizontal High Level Kit<br />
Taking the attached diagram as an example we can calculate the flue parameters for a top to horizontal flue<br />
system.<br />
Total Height = A<br />
Total Horizontal = B<br />
In this example<br />
A = 2.8 Metres B = 1.75 Metres<br />
Three x 90 degree bends have been used one of which (C) is the standard supply kit bend. This bend is ignored<br />
from the calculation as it is presumed it will always be used. The two remaining 90 degree bends increase the<br />
horizontal length by two metres.<br />
(one metre extra horizontal length per additional 90 degree bend).<br />
Total Height A = 2.8 Metres<br />
Total Horizontal B = 1.0 Metres<br />
In this example there is sufficient vertical rise for the horizontal run, as shown in the graph on page 6.<br />
Components used<br />
Standard kit<br />
terminal length<br />
T2<br />
Accessory 250mm<br />
length within wall<br />
Accessory short<br />
90 O bend<br />
Accessory 1metre length<br />
Wall band<br />
Accessory short<br />
90 O bend<br />
Description Part No. Quantity<br />
Top to 150mm 180mm<br />
HorizontalHigh<br />
Level Kit<br />
MS91102 MS91103<br />
1<br />
1 metre length MS91028 MS91034 1<br />
500mm length MS91029 MS91035 2<br />
250mm length MS91030 MS91036 1<br />
90° short bend MS91031 MS91037 2<br />
Wall band MS91052 MS91053 1<br />
B<br />
B+B= Total Horizontal<br />
A Total height<br />
Standard kit<br />
long 90 O bend<br />
Accessory<br />
500mm length<br />
Standard kit<br />
starter length<br />
T1<br />
© EUROHEAT DISTRIBUTORS (H.B.S) LTD. 9<br />
Technical <strong>Guide</strong> IN1105 Ed 5 May 2009<br />
A<br />
B