Physical data<br />

39SQ 0402 0404 0604 0606 0806 0808 1008 1010<br />

Height (including base frame) mm 560 800 800 1120 1120 1440 1440 1760<br />

Width mm 738 738 1058 1058 1378 1378 1698 1698<br />

1- Exhaust unit<br />

Air flow m 3 /s 0.58 1.17 1.75 2.63 3.5 4.67 5.83 7.29<br />

Length mm 660 820 900 1060 1140 1220 1300 1540<br />

2 - Supply unit heating<br />

Air flow m 3 /s 0.58 1.17 1.75 2.63 3.5 4.67 5.83 7.29<br />

Heating capacity kW 24.5 48.5 74.5 112.3 140.1 188.5 243.7 304.4<br />

Length mm 1380 1540 1620 1780 1860 1940 2180 2340<br />

3 - Supply unit heating and cooling<br />

Air flow m 3 /s 0.54 1 1.72 2.58 3.2 4.36 5.73 7.1<br />

Heating capacity kW 22.5 42.6 73.3 110 132.7 181.1 241 300.2<br />

Cooling capacity kW 10 19.2 33.1 49.9 63 86.2 112.3 139.7<br />

Length mm 1860 2020 2100 2260 2340 2420 2660 2820<br />

4 – Supply unit: mixing/heating/cooling<br />

Air flow m 3 /s 0.54 1 1.72 2.58 3.2 4.36 5.73 7.1<br />

Heating capacity kW 22.5 42.6 73.3 110 132.7 181.1 241 300.2<br />

Cooling capacity kW 10 19.2 33.1 49.9 63 86.2 112.3 139.7<br />

Length mm 2180 2340 2420 2660 2740 3060 3220 3460<br />

5 – Combined exhaust and supply unit<br />

Air flow m 3 /s 0.54 1 1.72 2.58 3.2 4.36 5.73 7.1<br />

Heating capacity kW 22.5 42.6 73.3 110 132.7 181.1 241 300.2<br />

Cooling capacity kW 10 19.2 33.1 49.9 63 86.2 112.3 139.7<br />

Length total mm 3220 3540 3700 4180 4340 4820 5140 5700<br />

Length section 1 mm 2450 2530 2930<br />

Length section 2 mm 2370 2610 2770<br />

Electric heater option<br />

Heating capacity 1 kW 7.5 7.5 18 27 36 36 45 60<br />

Heating capacity 2 kW 11.3 15 27 36 48 60 75 90<br />

Heating capacity 3 kW 15 22.5 36 54 72 96 120 150<br />

Heating capacity 4 kW 18.8 30 45 63 84 120 150 180<br />

Heating capacity 5 kW 30 37.5 54 81 108 144 180 225<br />

Pre-heating coil option<br />

Heating capacity kW 6.4 12.2 20.9 31.4 38.8 53 69.6 86.5<br />

1 – Exhaust unit<br />

Exhaust fan<br />

2 – Supply unit heating<br />

Return air damper<br />

G4+F7 filter<br />

Heating coil 2 rows<br />

Supply fan<br />

Standard conditions:<br />

Heating: air -10°C/90% rh, +25°C, water 80/60°C<br />

Cooling: air 28°C/50% rh, +16°C, water 7/12°C<br />

Pre-heating: air -5°C, +5°C, water 80/70°C<br />

External static pressure 300 Pa<br />

3 – Supply unit heating and cooling<br />

Return air damper<br />

G4 + F7 filters<br />

Heating coil 2 rows<br />

Cooling coil 6 rows<br />

Supply fan<br />

Notes on dimensions:<br />

• All dimensions are for indoor units with backward-curved fans, except size 0402 that has<br />

dimensions with a forward-curved fan<br />

• Casing length is exclusive of return air damper<br />

• Electric heater option: length varies with heating capacity<br />

• Pre-heating coil option: length + 160 mm<br />

• Contact your <strong>Carrier</strong> representative for certified dimensional drawings<br />

4 – Supply unit: mixing/heating/cooling<br />

Return air damper<br />

Fresh air damper<br />

G4 + F7 filters<br />

Heating coil 2 rows<br />

Cooling coil 6 rows<br />

Supply fan<br />

117<br />

5 – Combined exhaust and supply unit<br />

Return air damper<br />

Return fan<br />

Exhaust damper<br />

Mixing damper<br />

Fresh air damper<br />

G4 + F7 filters<br />

Heating coil 2 rows<br />

Cooling coil 6 rows<br />

Hospital exhaust and supply units with run-around coil for energy recovery<br />

39SQ