Electric motors<br />
The choice of an operation type determines the<br />
selection of a motor for each function.<br />
The IEC 34 recommendation has defined several<br />
types of actuator standard duty cycles for determining<br />
the use conditions of an electric motor.<br />
IEC 34 STANDARD<br />
S1 : Continuous duty<br />
Operation with constant load over a sufficient duration for reaching<br />
a thermal equilibrium.<br />
S2 : Short time duty<br />
Short time operation, total cooling between each start.<br />
S3 : Intermittent periodic duty<br />
The starting current has no significant effect on temperature rise.<br />
To be followed by the max. operating time.<br />
S4 : Intermittent duty with starting<br />
Repetition of cycles including :<br />
● starting period D,<br />
● period of constant speed N,<br />
● rest period R.<br />
MODULATING<br />
To be followed by the duty factor in %, as well as the number of starts per hour.<br />
Our choice : S4<br />
13<br />
USER’S<br />
GUIDE<br />
CHOOSING<br />
THE RANGE<br />
Mechanical and<br />
electrical features<br />
The only duty cycle corresponding to the required<br />
actuator operation is S4. Its parameters will be<br />
optimised to fit each application.<br />
DUTY OBJECTIVE TYPE OF MOTOR TYPE OF DUTY FREQUENCY<br />
● Operating time Asynchronous AC : 360 starts/hour<br />
ON / OFF ● Successive starts 3 phase or single phase S4 - 30 % DC : 60 starts/hour<br />
Direct current<br />
● Operating time Asynchronous<br />
CLASS III ● Repetition of starts 3 phase or single phase S4 - 50 % 1 200 starts/hour<br />
(Direct current possible)<br />
● High number Asynchronous 3 phase<br />
CLASS II l of starts (Single phase possible) S4 - 100 % 1 800 starts/hour<br />
● Low inertia<br />
● Speed variation Brushless direct current<br />
CLASS I ● Continuous operation with servo drive S4 - 100 % NO LIMITS<br />
General technical data<br />
of AC motors<br />
➜ SQUIRREL CAGE type<br />
➜ Insulation CLASS F<br />
➜ Watertight enclosure<br />
➜ Built-in thermal protection<br />
General technical data<br />
of DC motors<br />
Applicable only for ON / OFF and Class III duty<br />
➜ <strong>CO</strong>MPOUND type winding<br />
➜ Insulation CLASS F<br />
➜ Watertight enclosure<br />
➜ Built-in thermal protection