WATER REQUIREMENTS IN CIVIL USERS<br />
Water requirements in condominiums<br />
The first operation that is necessary for sizing a booster set is determining the quantity of water and the<br />
pressure it has to supply.<br />
The table at page 28 shows maximum water consumption values for each delivery point, depending on the<br />
plumbing amenities.<br />
The maximum theoretical requirement is given by the sum of the water consumption values of each delivery<br />
point. In actual fact, the delivery points are never used all together; only a few of them are used.<br />
Therefore, it is extremely important to determine the maximum number of delivery points that are more likely<br />
to be used at the same time.<br />
The first step is establishing the value of the contemporaneity factor, which depends on the number of delivery<br />
points.<br />
Values have been calculated with the following formulas:<br />
- Apartments with one bathroom<br />
- Apartments with two bathrooms<br />
f = 1/ (0.643 x Nr x Na) 1/2 x 1.05 with flush tank WC<br />
f = 1/ (0.857 x Nr x Na) 1/2 x 1 with controlled flushing system WC<br />
f = 1/ (0.545 x Nr x Na) 1/2 x 1.03 with flush tank WC<br />
f = 1/ (0.727 x Nr x Na) 1/2 x 0.8 with controlled flushing system WC<br />
where<br />
Nr = number of delivery points<br />
Na = number of apartments<br />
The table at page 29 shows the maximum contemporaneity flow-rate values for apartments with one or two<br />
bathrooms provided with flush tank WC or controlled flushing system WC. As regards apartments with one<br />
bathroom, 7 drawing points have been taken into consideration, while 11 points have been considered for<br />
apartments with two bathrooms.<br />
Water requirements for community buildings<br />
The requirements of buildings intended for specific uses, such as hospitals, hotels, offices, boarding schools,<br />
residential hotels, department stores, are different from those of condominiums, and both their global daily<br />
water consumption and the maximum contemporaneity flow rate are usually greater.<br />
The diagram at page 28 shows the requirements of a few communities, for guidance.<br />
These requirements must be determined case by case, with the utmost accuracy, according to particular needs<br />
and local provisions.<br />
25