2.0 UNPACKING AND INSTALLATION<br />

A quality installation begins on the receiving dock.<br />

Upon receipt and before unpacking, inspect the shipping container for damage or mishandling. If<br />

carton is damaged, note on shipper’s receipt and check for concealed damage. If any damage as a<br />

result of shipping is observed, file a damage claim with the shipper within 24 hours and contact<br />

your local <strong>Liebert</strong> representative or <strong>Liebert</strong> Customer Service and Support at 1-800-543-2378 to<br />

inform them of the damage claim and the condition of the equipment.<br />

If unit is to be stored before installation, it is recommended to store the unit in a dry environment<br />

with temperatures in the range of 0°C to 40°C. Use original packing materials or other suitable<br />

means to keep the unit clean. When opening the shipping carton, use care not to puncture the carton<br />

with sharp objects.<br />

The unit is of a size and weight that it can be easily moved to its intended location. Refer to the<br />

unit dimensions shown in Figure 2 and Figure 3. Typical unit weights are less than 70 pounds<br />

(32 kg) for the wall or underfloor enclosure and less than 40 pounds (18 kg) for the rackmount<br />

enclosure.<br />

2.1 Location Considerations<br />

The unit is designed to be installed indoors where the ambient air temperature is in the range of<br />

0°C and 40°C with a relative humidity of 0% to 95% non-condensing.<br />

The underfloor and wall mount enclosures are designed to withstand moderate amounts of moisture<br />

such as is normally available under a computer room raised floor. Do not operate the units in<br />

standing water.<br />

!<br />

CAUTION:<br />

Do not locate or operate the unit in hazardous areas where there<br />

is conductive or explosive dust, flammable liquids or gases, or<br />

corrosive substances.<br />

Altitude - The standard units are designed for full load operation up to 5000 feet (1500 meters)<br />

above sea level. For higher altitude applications, contact your local <strong>Liebert</strong> Representative or<br />

applications engineering.<br />

Heat Output - The units produce minimal heat output during normal operation. The typical heat<br />

output, which should be included in any calculations for room heat load, is less than 260 BTU/<br />

Hour (80 W/Hour).<br />

Rackmount Installation - The rackmount enclosure is designed to fit into an EIA Standard 19<br />

inch rack. For rackmount installation, support the unit on a shelf, bracket, or slide. Do not secure<br />

only by the front mounting plate. Secure the unit into the rack using four screws through the<br />

front plate. See Figure 2.<br />

Unpacking and Installation 5