A<br />

02<br />

<strong>SPLIT</strong> <strong>SYSTEMS</strong> <strong>AIRCONDITIONERS</strong><br />

<strong>DUCTABLE</strong> INDOOR UNITS (alternative voltages)<br />

AXCZ/FTBZ Series Cooling only<br />

AXCBZ/FTBZ Series Heat pump<br />

AXCZ/FTBZ, AXCBZ/FTBZ series are split system air conditioners, air to air, cooling only and heat pumps, for air conditioning<br />

applications up to 19,5kW. Complementary range fro power supplies not available on the DXCZ, DXCBZ<br />

range. Ductable indoor unit, ceiling concealed type.<br />

Cabinet is constructed on heavy gauge galvanized steel plate. Outdoor unit is finished with electrostatically applied<br />

and oven-polymerized polyester powder of high resistance against corrosion. Compressors are rotary, scroll or piston<br />

depending upon models. Indoor unit fans are centrifugal, direct drive. Outdoor unit fans are axial.<br />

Refrigerant piping are made of high-grade refrigeration copper including expansion device, filter drier, flare valves<br />

and four-way valve and suction accumulator for heat pumps. Electric panel is complete with contactors and protections.<br />

Outdoor units are supplied with operating R407c refrigerant charge (7,5m). Indoor units are supplied with<br />

nitrogen holding charge. Units are supplied ready for installation: electric supply, controller, refrigerant lines, electric<br />

interconnection and condensates drain.<br />

A<br />

02<br />

25


A 02<br />

<strong>SPLIT</strong> <strong>SYSTEMS</strong> <strong>AIRCONDITIONERS</strong><br />

<strong>DUCTABLE</strong> INDOOR UNITS (alternative voltages)<br />

AXCZ/FTBZ - AXCBZ/FTBZ Series<br />

TECHNICAL SPECIFICATIONS. COOLING ONLY<br />

MODEL<br />

Outdoor unit Indoor unit<br />

AXCZ 251<br />

AXCZ 271<br />

AXCZ 351<br />

AXCZ 371<br />

AXCZ 371<br />

AXCZ 401<br />

AXCZ 451<br />

AXCZ 501<br />

AXCZ 721<br />

FTBZ 251<br />

FTBZ 271<br />

FTBZ 351<br />

FTBZ 371<br />

FTBZ 371<br />

FTBZ 401<br />

FTBZ 451<br />

FTBZ 501<br />

FTBZ 721<br />

Cooling<br />

capacity<br />

kW<br />

7,4<br />

7,9<br />

9,6<br />

11,1<br />

11,1<br />

11,8<br />

12,9<br />

14,5<br />

19,0<br />

Input<br />

power<br />

kW<br />

2,66<br />

2,86<br />

3,36<br />

3,90<br />

3,85<br />

4,25<br />

4,64<br />

4,91<br />

6,16<br />

Input<br />

current<br />

A<br />

5,2<br />

5,4<br />

11,4<br />

18,7<br />

12,0<br />

13,5<br />

16,0<br />

17,0<br />

18,7<br />

Power supply<br />

(50 Hz ~)<br />

V<br />

400-3<br />

400-3<br />

230-3<br />

230-1<br />

230-3<br />

230-3<br />

230-3<br />

230-3<br />

230-3<br />

Sound level<br />

Outdoor unit Indoor unit<br />

dB (A)<br />

56<br />

56<br />

62<br />

59<br />

59<br />

59<br />

59<br />

61<br />

63<br />

41<br />

43<br />

43<br />

43<br />

43<br />

47<br />

48<br />

48<br />

50<br />

Airflow<br />

m 3 /h - Pa<br />

1150 - 72<br />

1400 - 96<br />

1500 - 80<br />

2200 - 96<br />

2200 - 96<br />

2300 - 80<br />

2400 - 94<br />

2500 - 76<br />

3000 - 140<br />

INSTALLATION SPECIFICATIONS. COOLING ONLY<br />

A<br />

02<br />

MODEL<br />

Outdoor unit Indoor unit<br />

AXCZ 251<br />

AXCZ 271<br />

AXCZ 351<br />

AXCZ 371<br />

AXCZ 401<br />

AXCZ 451<br />

AXCZ 501<br />

AXCZ 721<br />

FTBZ 251<br />

FTBZ 271<br />

FTBZ 351<br />

FTBZ 371<br />

FTBZ 401<br />

FTBZ 451<br />

FTBZ 501<br />

FTBZ 721<br />

Liquid<br />

line<br />

Ø (”)<br />

3/8<br />

3/8<br />

3/8<br />

1/2<br />

1/2<br />

1/2<br />

1/2<br />

1/2<br />

- Power supply Indoor unit 230-1 50 Hz~.<br />

Suction<br />

line<br />

Ø (”)<br />

5/8<br />

3/4<br />

3/4<br />

3/4<br />

3/4<br />

7/8<br />

7/8<br />

7/8<br />

Refriger.<br />

kg<br />

2,3<br />

2,4<br />

3,0<br />

3,5<br />

4,2<br />

5,1<br />

4,8<br />

6,0<br />

Dimensions (width x depth x height)<br />

Outdoor unit Indoor unit<br />

950 x 375 x 688<br />

950 x 375 x 688<br />

950 x 375 x 688<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

1560 x 450 x 1049<br />

Ø (”)<br />

925 x 660 x 275<br />

925 x 660 x 275<br />

925 x 660 x 275<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 805 x 364<br />

Distance in-out<br />

Total Vertical<br />

m<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

Net weight<br />

Out. u. In. u.<br />

Kg<br />

73<br />

73<br />

83<br />

102<br />

108<br />

110<br />

120<br />

196<br />

39<br />

43<br />

44<br />

59<br />

59<br />

61<br />

61<br />

-<br />

TECHNICAL SPECIFICATIONS. HEAT PUMPS<br />

MODEL<br />

Outdoor unit Indoor unit<br />

AXCBZ 251<br />

AXCBZ 271<br />

AXCBZ 351<br />

AXCBZ 371<br />

AXCBZ 371<br />

AXCBZ 401<br />

AXCBZ 451<br />

AXCBZ 501<br />

AXCBZ 721<br />

FTBZ 251<br />

FTBZ 271<br />

FTBZ 351<br />

FTBZ 371<br />

FTBZ 371<br />

FTBZ 401<br />

FTBZ 451<br />

FTBZ 501<br />

FTBZ 721<br />

Cooling<br />

capacity<br />

kW<br />

7,0<br />

7,5<br />

9,8<br />

10,7<br />

10,7<br />

11,6<br />

12,8<br />

14,0<br />

18,6<br />

Heating<br />

capacity<br />

kW<br />

8,1<br />

8,3<br />

10,4<br />

12,5<br />

12,5<br />

14,0<br />

14,9<br />

15,9<br />

20,7<br />

Input<br />

power<br />

kW<br />

2,66<br />

2,86<br />

3,36<br />

3,90<br />

3,85<br />

4,25<br />

4,64<br />

4,91<br />

6,16<br />

Input<br />

current<br />

A<br />

5,2<br />

5,4<br />

11,4<br />

18,7<br />

12,0<br />

13,5<br />

16,0<br />

17,0<br />

18,7<br />

Power supply<br />

(50 Hz ~)<br />

V<br />

400-3<br />

400-3<br />

230-3<br />

230-1<br />

230-3<br />

230-3<br />

230-3<br />

230-3<br />

230-3<br />

Sound level<br />

Outdoor unit Indoor unit<br />

dB (A)<br />

56<br />

56<br />

62<br />

59<br />

59<br />

59<br />

59<br />

61<br />

63<br />

41<br />

43<br />

43<br />

43<br />

43<br />

47<br />

48<br />

48<br />

50<br />

Airflow<br />

m 3 /h - Pa<br />

1150 - 72<br />

1400 - 96<br />

1500 - 80<br />

2200 - 96<br />

2200 - 96<br />

2300 - 80<br />

2400 - 94<br />

2500 - 76<br />

3000 - 140<br />

INSTALLATION SPECIFICATIONS. HEAT PUMPS<br />

MODEL<br />

Outdoor unit Indoor unit<br />

AXCBZ 251<br />

AXCBZ 271<br />

AXCBZ 351<br />

AXCBZ 371<br />

AXCBZ 401<br />

AXCBZ 451<br />

AXCBZ 501<br />

AXCBZ 721<br />

FTBZ 251<br />

FTBZ 271<br />

FTBZ 351<br />

FTBZ 371<br />

FTBZ 401<br />

FTBZ 451<br />

FTBZ 501<br />

FTBZ 721<br />

Liquid<br />

line<br />

Ø (”)<br />

3/8<br />

3/8<br />

3/8<br />

1/2<br />

1/2<br />

1/2<br />

1/2<br />

1/2<br />

- Power supply Indoor unit 230-1 50 Hz~.<br />

Suction<br />

line<br />

Ø (”)<br />

5/8<br />

3/4<br />

3/4<br />

3/4<br />

3/4<br />

7/8<br />

7/8<br />

7/8<br />

Refriger.<br />

kg<br />

2,4<br />

2,5<br />

3,2<br />

3,7<br />

4,5<br />

5,4<br />

5,0<br />

6,5<br />

Dimensions (width x depth x height)<br />

Outdoor unit Indoor unit<br />

950 x 375 x 688<br />

950 x 375 x 688<br />

950 x 375 x 838<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

950 x 375 x 1241<br />

1560 x 450 x 1049<br />

Ø (”)<br />

925 x 660 x 275<br />

925 x 660 x 275<br />

925 x 660 x 275<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 750 x 310<br />

1250 x 805 x 364<br />

Distance in-out<br />

Total Vertical<br />

m<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

50<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

25<br />

Net weight<br />

Out. u. In. u.<br />

Kg<br />

73<br />

73<br />

83<br />

102<br />

106<br />

110<br />

120<br />

196<br />

39<br />

43<br />

44<br />

59<br />

59<br />

61<br />

61<br />

71<br />

OPERATION LIMITS<br />

COOLING<br />

Outdoor air<br />

Indoor air<br />

Dry bulb Wet bulb Dry bulb Wet bulb<br />

ºC ºC ºC ºC<br />

Standard 35 – 27 19<br />

Minimum 21 – 21 15<br />

Maximum 46 – 32 21<br />

HEATING<br />

Outdoor air<br />

Indoor air<br />

Dry bulb Wet bulb Dry bulb Wet bulb<br />

ºC ºC ºC ºC<br />

Standard 7 6 20 –<br />

Minimum -6 -7 20 –<br />

Maximum 24 18 26 –<br />

26<br />

Commitment HITECSA


A 02<br />

<strong>SPLIT</strong> <strong>SYSTEMS</strong> <strong>AIRCONDITIONERS</strong><br />

<strong>DUCTABLE</strong> INDOOR UNITS (alternative voltages)<br />

AXCZ/FTBZ - AXCBZ/FTBZ Series<br />

CONTROLLERS<br />

ETN<br />

KLR-E 7007/7035<br />

OPTIONS<br />

Head pressure control:<br />

Cooling operation below 18ºC outside air. Fan speed control<br />

pressure operated.<br />

Electric heaters:<br />

Nickel-chrome resistances.<br />

Hot water heating coils:<br />

For cooling only units. Two row copper tubing and aluminium fins<br />

coils.<br />

OPTIONS Indoor unit<br />

1. Air return plenum 90º<br />

2. Fresh air damper<br />

3. Air return plenum<br />

4. High efficiency filters<br />

5. Condensate pump<br />

6. Indoor unit<br />

Fresh air damper<br />

Special filters.<br />

Etc.<br />

7. Air discharge plenum<br />

8. Air discharge plenum 90º<br />

9. Tubular air discharge plenum 3 outlet<br />

10. Tubular air discharge plenum 5 outlet<br />

11. Hot water coil<br />

12. Electric heater<br />

A<br />

02<br />

27

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!