08.02.2014 Views

SUBMITTAL DATA: SEZ-KD12NA - Usair-eng.com

SUBMITTAL DATA: SEZ-KD12NA - Usair-eng.com

SUBMITTAL DATA: SEZ-KD12NA - Usair-eng.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>SUBMITTAL</strong> <strong>DATA</strong>: <strong>SEZ</strong>-<strong>KD12NA</strong><br />

12,000 BTU/H HORIZONTAL-DUCTED INDOOR UNIT FOR MXZ MULTI-ZONE HEAT-PUMP SYSTEMS<br />

Job Name: Location: Date:<br />

Purchaser:<br />

Engineer:<br />

Submitted to: For Reference Approval Construction<br />

System Designation:<br />

GENERAL FEATURES<br />

• Ceiling-concealed ducted indoor unit for residential applications<br />

• Ultra thin body: 7-7/8" high<br />

• Built-in drain mechanism for condensate removal; lifts to 21-11/16"<br />

• Air filter is included with indoor unit<br />

• Quiet operation ― as low as 23 dBA<br />

• PAR-21MAA wired remote controller is included<br />

• Indoor unit powered from outdoor unit using A-Control<br />

• Automatic fan speed control<br />

• Auto restart following a power outage<br />

• Limited warranty: one year on parts and defects<br />

OPTIONAL ACCESSORIES<br />

• M-NET Control Adapter (MAC-399IF)<br />

• External Heat Adapter (PAC-YU25HT)<br />

• CN24 Relay Kit (CN24RELAY-KIT-CM)<br />

• Three-pole Disconnect Switch (TAZ-MS303)<br />

Cooling*<br />

Rated Capacity. ..............................12,000 Btu/h<br />

Total Input. ........................................70 W<br />

Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.57 A<br />

Heating*<br />

Rated Capacity. ..............................13,600 Btu/h<br />

Total Input. ........................................50 W<br />

Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.46 A<br />

* Rating Conditions (Cooling) - Indoor: 80ºF (27ºC) DB / 67ºF (19ºC) WB.<br />

Outdoor: 95ºF (35ºC) DB / 75ºF (24ºC) WB.<br />

(Heating) - Indoor: 70ºF (21ºC) DB / 60ºF (16ºC) WB. Outdoor: 47ºF (8ºC) DB /<br />

43ºF (6ºC) WB.<br />

(For data on specific indoor units [all ducted, all non-ducted, and both ducted<br />

and non-ducted] <strong>com</strong>binations, see the MXZ Technical and Service Manual.)<br />

Electrical Requirements<br />

Power Supply ....................208 / 230V, 1-Phase, 60 Hz<br />

MCA .............................................. 1 A<br />

Voltage<br />

Indoor - Outdoor S1-S2 ......................AC 208 / 230V<br />

Indoor - Outdoor S2-S3 ............................DC 24V<br />

MXZ MULTI-ZONE HEAT-PUMP OUTDOOR UNITS<br />

Schedule No.:<br />

Indoor Unit: <strong>SEZ</strong>-<strong>KD12NA</strong><br />

Remote Controller: PAR-21MAA<br />

Fan<br />

Type x Quantity. ........................... Sirocco Fan x 2<br />

Motor .....................Direct-driven DC Brushless Motor<br />

Motor Output. ......................................96 W<br />

Airflow (Lo - Med - Hi). ..................247 - 317 - 388 CFM<br />

Air Filter ........................ Polypropylene Honey<strong>com</strong>b<br />

External Static Pressure. ..........0.02 - 0.06 - 0.14 - 0.20"WG<br />

Sound Pressure Level (Lo - Med - Hi) . ........23 - 28 - 33 dB(A)<br />

DIMENSIONS<br />

UNIT INCHES / MM<br />

W 39 / 990<br />

D 27-9/16 / 700<br />

H 7-7/8 / 200<br />

Weight. ................................... 46 lbs. / 21 kg<br />

Field Drainpipe Size O.D.. ....................1-1/4" / 32 mm<br />

Wall-mounted Remote Controller ................. PAR-21MAA<br />

(See Data Submittal Sheet)<br />

Refrigerant Type .................................. R410A<br />

Refrigerant Pipe Size O.D.<br />

Gas Side .................................3/8" / 9.52 mm<br />

Liquid Side. ...............................1/4" / 6.35 mm<br />

Connection Method ................................Flared<br />

MXZ COMPATIBLE INDOOR UNITS AND REMOTE CONTROLLERS<br />

MXZ MULTI-ZONE SYSTEMS CAN INCLUDE:<br />

• All Horizontal-ducted Indoor Units:<br />

<strong>SEZ</strong>-KD09, 12, 15, 18NA<br />

• Select Wall-mounted Indoor Units:<br />

MSZ-A09, 12, 15, 17, 24NA<br />

and<br />

MSZ-FD09, 12NA<br />

• A <strong>com</strong>bination of both Horizontal-ducted<br />

and Wall-mounted Indoor Units<br />

Refer to the separate submittal forms for the<br />

MSZ-A and MSZ-FD Indoor Units and MXZ<br />

Outdoor Units.<br />

Wall-mounted Indoor Unit: MSZ-A09, 12, 15, 17, 24NA<br />

Wireless Remote Controller -<br />

Packaged with MSZ-A and MSZ-FD<br />

(Optional Wired Remote Controller<br />

PAR-21MAA)<br />

Outdoor Unit: MXZ-3A30NA<br />

Wall-mounted Indoor Unit: MSZ-FD-NA<br />

Horizontal-ducted Indoor Unit: <strong>SEZ</strong>-KD-NA<br />

Remote Controller<br />

PAR-21MAA -<br />

Packaged with <strong>SEZ</strong>


<strong>SEZ</strong>-<strong>KD12NA</strong> INDOOR FAN PERFORMANCE AND CORRECTED AIR FLOW CHARTS<br />

<strong>SEZ</strong>-<strong>KD12NA</strong><br />

(External static pressure 0.02[in.WG](5Pa)) 208/230V 60Hz<br />

40<br />

[0.16]<br />

<strong>SEZ</strong>-<strong>KD12NA</strong><br />

(External static pressure 0.06[in.WG](15Pa)) 208/230V 60Hz<br />

50<br />

[0.20]<br />

External static pressure [in.WG](Pa)<br />

30<br />

[0.12]<br />

20<br />

[0.08]<br />

10<br />

[0.04]<br />

Middle<br />

High<br />

Rated point<br />

Limit<br />

External static pressure [in.WG](Pa)<br />

40<br />

[0.16]<br />

30<br />

[0.12]<br />

20<br />

[0.08]<br />

10<br />

[0.04]<br />

Low<br />

Middle<br />

High<br />

Rated point<br />

Limit<br />

Low<br />

0<br />

6<br />

[212]<br />

7<br />

[247]<br />

8<br />

[282]<br />

9<br />

[318]<br />

10<br />

[353]<br />

11<br />

[388]<br />

12<br />

[424]<br />

Airflow rate(m 3 /min)[CFM]<br />

0<br />

6<br />

[212]<br />

7<br />

[247]<br />

8<br />

[282]<br />

9<br />

[318]<br />

10<br />

[353]<br />

11<br />

[388]<br />

12<br />

[424]<br />

Airflow rate(m 3 /min)[CFM]<br />

<strong>SEZ</strong>-<strong>KD12NA</strong><br />

(External static pressure 0.14[in.WG](35Pa)) 208/230V 60Hz<br />

External static pressure [in.WG](Pa)<br />

80<br />

[0.32]<br />

70<br />

[0.28]<br />

60<br />

[0.24]<br />

50<br />

[0.20]<br />

40<br />

[0.16]<br />

30<br />

[0.12]<br />

20<br />

[0.08]<br />

10<br />

[0.04]<br />

Low<br />

Middle<br />

0<br />

6<br />

[212]<br />

7<br />

[247]<br />

8<br />

[282]<br />

9<br />

[318]<br />

10<br />

[353]<br />

11<br />

[388]<br />

12<br />

[424]<br />

Airflow rate(m 3 /min)[CFM]<br />

Rated point<br />

Limit<br />

High<br />

<strong>SEZ</strong>-<strong>KD12NA</strong><br />

(External static pressure 0.20[in.WG](50Pa)) 208/230V 60Hz<br />

External static pressure [in.WG](Pa)<br />

80<br />

[0.32]<br />

70<br />

[0.28]<br />

60<br />

[0.24]<br />

50<br />

[0.20]<br />

40<br />

[0.16]<br />

30<br />

[0.12]<br />

20<br />

[0.08]<br />

10<br />

[0.04]<br />

Low<br />

Middle<br />

0<br />

6 7 8 9 10 11 12<br />

[212] [247] [282] [318] [353] [388] [424]<br />

Airflow rate(m 3 /min)[CFM]<br />

Limit<br />

Rated point<br />

High


DIMENSIONS: <strong>SEZ</strong>-<strong>KD12NA</strong><br />

345(13-19/32)<br />

Drain pipe(O.D.ø32(1-1/4))<br />

(Emergency draining)<br />

Unit : mm(in.)<br />

15(19/32)<br />

159(6-9/32)<br />

2XE-ø2.9(1/8)<br />

Suspension bolt hole<br />

4-14X30(9/16X1-3/16) Slot<br />

L-ø2.9(1/8)<br />

20(13/16)<br />

12(1/2)<br />

37(1-15/32)<br />

100(3-15/16)<br />

157.5(6-7/32)<br />

37(1-15/32)<br />

25(1)<br />

57(2-1/4)<br />

D (Duct)<br />

100(3-15/16)X(E-1)=F<br />

100(3-15/16)<br />

Air<br />

outlet<br />

Air<br />

inlet<br />

A<br />

N<br />

B (Suspension bolt pitch)<br />

C<br />

M<br />

88(3-15/32)<br />

88(3-15/32)<br />

H<br />

100(3-15/16)XJ=K<br />

100(3-15/16)<br />

Drain pipe(O.D.ø32(1-1/4))<br />

150(Duct)<br />

(5-29/32)<br />

20(13/16)<br />

30(1-3/16)<br />

23(29/32)<br />

100 25(1)<br />

(3-15/16)<br />

57(2-1/4)<br />

2X2-ø2.9(1/8)<br />

1 Refrigerant piping<br />

flare connection (gas)<br />

49 625(Suspension bolt pitch)<br />

(1-15/16) (24-5/8)<br />

23(29/32)<br />

10(13/32)<br />

116<br />

(4-19/32)<br />

10(13/32)<br />

70<br />

(2-25/32)<br />

270(10-21/32)<br />

700(27-9/16)<br />

677(26-21/32)<br />

2 Refrigerant piping<br />

flare connection (liquid)<br />

Control box<br />

102(4-1/32)<br />

90<br />

(3-9/16)<br />

170(6-23/32)<br />

200(7-7/8)<br />

23(29/32)<br />

Knockout hole ø27(1-3/32)<br />

(Indoor/outdoor connecting line)<br />

Knockout hole ø27(1-3/32)<br />

(Remote controller transmission line)<br />

Terminal block (Indoor/outdoor connecting line)<br />

Terminal block (Remote controller transmission line)<br />

Drain pipe(O.D.ø32(1-1/4))<br />

(Spontaneous draining)<br />

20(13/16)<br />

12(1/2)<br />

Air filter<br />

Note2<br />

50(1-31/32)<br />

50(1-31/32)<br />

G 450<br />

50 ~ 150<br />

(1-31/32 ~ 5-29/32)<br />

(17-23/32)<br />

450<br />

777<br />

(17-23/32)<br />

(30-19/32)<br />

(11-13/16)<br />

More than 300<br />

Access door<br />

Required space for service and maintenance<br />

175±5(6-29/32±7/32)<br />

(Actual l<strong>eng</strong>th)<br />

Less than 300<br />

(11-13/16)<br />

Less than 550<br />

(21-21/32)<br />

More than 10<br />

(13/32)<br />

More than 20<br />

(13/16)<br />

Drain hose (I.D.ø32(1-1/4))<br />

<br />

Ceiling surface<br />

Access door<br />

Make the access door at the appointed position properly<br />

for service maintenance.<br />

mm(in.)<br />

Model<br />

<strong>SEZ</strong>-KD09NA<br />

<strong>SEZ</strong>-<strong>KD12NA</strong><br />

<strong>SEZ</strong>-KD15NA<br />

<strong>SEZ</strong>-KD18NA<br />

A<br />

700<br />

(27-9/16)<br />

752<br />

(29-5/8)<br />

798<br />

(31-7/16)<br />

660<br />

(26)<br />

900 952 998 860<br />

(35-7/16) (37-1/2) (39-5/16) (33-7/8)<br />

1100<br />

(43-5/16)<br />

B<br />

1152<br />

(45-3/8)<br />

C<br />

1198<br />

(47-3/16)<br />

D<br />

1060<br />

(41-3/4)<br />

E<br />

7<br />

9<br />

11<br />

F<br />

600<br />

(23-5/8)<br />

800<br />

(31-1/2)<br />

H<br />

660<br />

(26)<br />

800 1000 860<br />

(31-1/2) (39-3/8) (33-7/8)<br />

1000<br />

(39-3/8)<br />

G<br />

1200<br />

(47-1/4)<br />

1060<br />

(41-3/4)<br />

J<br />

5<br />

7<br />

9<br />

K<br />

500<br />

(19-11/16)<br />

700<br />

(27-9/16)<br />

900<br />

(35-7/16)<br />

L<br />

16<br />

20<br />

24<br />

M<br />

839<br />

(33-1/16)<br />

1039<br />

(40-29/32)<br />

1239<br />

(48-25/32)<br />

N<br />

790<br />

(31-1/8)<br />

990<br />

(39)<br />

1190<br />

(46-7/8)<br />

Gas pipe<br />

1 2<br />

Liquid pipe<br />

ø9.52(3/8)<br />

ø6.35(1/4)<br />

ø12.7(1/2)<br />

Note1.Use M10 screw for the suspension bolt (field supply).<br />

2.Keep the service space for the maintenance at the bottom.<br />

3.This chart indicates for <strong>SEZ</strong>-KD15NA model,which has 3 fans.<br />

<strong>SEZ</strong>-KD09,12NA models have 2 fans.<br />

<strong>SEZ</strong>-KD18NA models have 4 fans.<br />

4.In case an inlet duct is used,remove the air filter(supply with<br />

the unit), then install the filter(field supply) at suction side.<br />

C SD - <strong>SEZ</strong>-<strong>KD12NA</strong> - 200903 © MITSUBISHI ELECTRIC / HVAC 2009<br />

3400 Lawrenceville Suwanee Rd<br />

Suwanee, GA 30024<br />

Tele: 678-376-2900 • Fax: 800-889-9904<br />

Toll Free: 800-433-4822 (#3)<br />

www.mehvac.<strong>com</strong><br />

Specifications are subject to change without notice.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!