Applications manual<br />

<strong>GB125</strong> <strong>Concentric</strong> <strong>Vent</strong><br />

Design Manual<br />

3. Description of the systems<br />

3.1. Scope<br />

The concentric venting system described in this manual<br />

is used exclusively for the <strong>Buderus</strong> <strong>GB125</strong> boiler. No<br />

other venting system can be used with this boiler, and the<br />

venting system can not be used in conjunction with any<br />

other boiler.<br />

Do not replace or substitute any vent or combustion air<br />

pipe with another brand, make, model, or material.<br />

The <strong>Buderus</strong> <strong>GB125</strong> is designed for balanced flue<br />

operation only. All combustion air is drawn from the<br />

outdoors. Use of balancers or barometric dampers defies<br />

the system principle and is not permitted.<br />

HTK - Direct vent through<br />

side wall<br />

(See page 12)<br />

Part Number: 7747310386<br />

DO - Vertical vent through<br />

conditioned and unconditioned<br />

space (NOT -suitable<br />

for installation outdoors)<br />

(See page 13)<br />

Part Number: 7747200752<br />

Installation and service of <strong>Buderus</strong> concentric venting<br />

systems must be performed by a trained installer.<br />

CAUTION! Never connect this concentric vent to<br />

a common venting system<br />

3.2. Available systems<br />

GAK - Liner inside an existing<br />

chimney;<br />

Option 1: rigid pipe for a<br />

straight chimney;<br />

Option 2: flexible liner for<br />

chimneys with an offset or<br />

bend;<br />

(See page 15)<br />

Part Number: 7747200755<br />

The three types of systems that are available are shown<br />

in Fig. 1:<br />

Observe the maximum vent lengths for each boiler size<br />

as shown in Table 1.<br />

Fig.1<br />

Available systems<br />

Systems are available as prepackaged kits that include<br />

the essential components needed in every installation.<br />

Refer to the descriptions of the individual system for<br />

included items. For most systems extra straight pipe and<br />

additional elbows must be purchased as needed. See list<br />

of accessories for every system.<br />

Max. length of flue pipe, feet (m)<br />

<strong>Buderus</strong> flue pipe systems DN 80/125 Table 1<br />

Boiler Size HT-K direct<br />

vent<br />

DO<br />

vertical vent<br />

GAK<br />

chimney<br />

liner<br />

<strong>GB125</strong> - 22 17' (5.2 m) 51' (17 m) 51' (17 m)<br />

<strong>GB125</strong> - 30 17' (5.2 m) 64' (21 m) 64' (21 m)<br />

The GAK system draws combustion air from the<br />

roof and may not be suitable for installation in<br />

multi-flue chimneys, where a second flue vents a<br />

combustion appliance that is used on a regular<br />

basis. Flue gases could be drawn in with <strong>GB125</strong><br />

combustion air and cause system interruption.<br />

<strong>GB125</strong> - 35 17' (5.2 m) 71' (23 m) 71' (23 m)<br />

The overall lengths include two elbows for the HT-K, and<br />

one elbow for the DO and GAK kits. Every additional<br />

elbow (accessory) reduces the maximum vent length by 3<br />

ft (1 m).<br />

| 7<br />

<strong>GB125</strong> <strong>Concentric</strong> <strong>Vent</strong> Design Manual | 05.2009<br />

Technical specifications are subject to change without prior notice