30.10.2012 Views

Starters and Contactors - Access Elevator Supply

Starters and Contactors - Access Elevator Supply

Starters and Contactors - Access Elevator Supply

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Fuses: MeQ, HCLR<br />

Fuses MEQ, HCLR<br />

Type MeQ<br />

Description Time-delay<br />

Dimensions 1/4” dia. x 1-1/2” length<br />

Ratings Volts: 500Vac Amps: 0.1 – 30<br />

IR 10kA RMS Amps<br />

Cross reference FNQ (Bussman)<br />

ATQ (Gould Shawmut)<br />

FLQ (Littlefuse)<br />

Features <strong>and</strong> benefits Compact dimensions<br />

Fiber tube construction<br />

Time-delay allows harmless inductive surges to pass without needless<br />

fuse opening<br />

Applications Supplemental protection of transformers, solenoids, <strong>and</strong> other<br />

high inrush circuits<br />

For motor applications, refer to type EDCC<br />

part # Description<br />

MEQ.25 500VAC time-delay midget 0.25 amp<br />

MEQ1 500VAC time-delay midget 1 amp<br />

MEQ1.5 500VAC time-delay midget 1.5 amp<br />

MEQ10 500VAC time-delay midget 10 amp<br />

MEQ15 500VAC time-delay midget 15 amp<br />

MEQ2 500VAC time-delay midget 2 amp<br />

MEQ20 500VAC time-delay midget 20 amp<br />

MEQ25 500 VAC time-delay midget 25 amp<br />

Class CC Fuses<br />

Type HCLR<br />

Description Fast-acting<br />

Dimensions 13/32” dia. x 1 1/2” length<br />

Ratings Volts: HCLR-600Vac Amps: 0.1 – 30<br />

IR 200,000 RMS Symmetrical Amps<br />

Cross reference KTKP (Bussman)<br />

ATMR (Gould Shawmut)<br />

KLKR (Littlefuse)<br />

Current limiting Class CC Fuse<br />

Features <strong>and</strong> benefits Branch circuit rated for 600Vac<br />

Compact dimensions<br />

Fast-acting design responds quickly to both overload <strong>and</strong><br />

short-circuit current<br />

Applications Lighting <strong>and</strong> resistive heating loads<br />

part # Description<br />

HCLR8 600VAC fast acting class CC 8 amp<br />

part # Description<br />

MEQ3 500VAC time-delay midget 3 amp<br />

MEQ3.2 500VAC time-delay midget 3.2 amp<br />

MEQ4 500VAC time-delay midget 4 amp<br />

MEQ5 500VAC time-delay midget 5 amp<br />

MEQ6 500VAC time-delay midget 6 amp<br />

MEQ7 500VAC time-delay midget 7 amp<br />

MEQ8 500VAC time-delay midget 8 amp<br />

Fuses: MeQ, HCLR<br />

18 <strong>Access</strong> ElEvator supply • 800-266-8654 • Fax 510-652-5043 • www.aesupply.com<br />

<strong>Access</strong> ElEvator supply • 800-266-8654 • Fax 510-652-5043 • www.aesupply.com<br />

19<br />

Fuses: HCTR, eDCC<br />

Type HCTR<br />

Description Time-delay<br />

Dimension 13/32” dia. x 1 1/2” length<br />

Ratings Volts: HCTR-600VAC Amps: 0.25 – 30<br />

IR 200,000 RMS Symmetrical Amps<br />

Cross reference FNQR (Bussman)<br />

ATQR (Gould Shawmut)<br />

KLDR (Littlefuse)<br />

Current limiting Class CC Fuse<br />

Features <strong>and</strong> benefits Branch circuit rated for 600VAC<br />

Compact dimensions<br />

Time-delay design allows loser sizing for inductive loads such as control<br />

transformers <strong>and</strong> solenoids<br />

Applications Primary protection for control<br />

part # Description<br />

HCTR2 600 VAC Time-Delay class CC 2 amp<br />

HCTR3 600 VAC Time-Delay class CC 3 amp<br />

HCTR4 600 VAC Time-Delay class CC 4 amp<br />

HCTR6 600 VAC Time-Delay class CC 6 amp<br />

Type eDCC<br />

Description Time-delay<br />

Dimensions 13/32” dia. x 1-1/2” length<br />

Ratings Volts: EDCC-600VAC Amps: 0.5 – 30<br />

IR 200,000 RMS Symmetrical Amps<br />

Cross reference LP-CC (Bussman)<br />

ATDR (Gould Shawmut)<br />

CCMR (Littlefuse)<br />

Current limiting Class CC fuse<br />

UL listed DC rating Voltage rating: EDCC 0.5 – 2.8A, 20 – 30A 300VDC, 3 – 15A 150VDC<br />

IR 20,000 Amps DC<br />

Features <strong>and</strong> benefits Brunch circuit rated for 600VAC<br />

Time-delay for motor branch circuit protection<br />

Excellent current-limiting performance<br />

Upgrade for st<strong>and</strong>ard “midget” fuses<br />

Applications Use for protection of small horsepower motor circuit or other circuit<br />

requiring small dimension, time-delay fuses<br />

Can provide Type 2 “No damage” protection for IEC or NEMA starters/<br />

contactors<br />

Fuses HCTR, EDCC<br />

Fuses: HCTR, eDCC

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!