Metasys Network Sales Resource Manual 635<br />
Application Specific Controllers Section<br />
Product Bulletin<br />
Issue Date 1000<br />
<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>,<br />
<strong>XPx</strong> Expansion <strong>Modules</strong><br />
The <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> extension modules<br />
used with <strong>XPx</strong> expansion modules combine<br />
intelligent processing power with exp<strong>and</strong>ed<br />
Input/Output (I/O). The <strong>XTM</strong>-<strong>105</strong> is intended for<br />
the N2 Bus, <strong>and</strong> the <strong>XTM</strong>-<strong>905</strong> works on the XT<br />
Bus of the DX controller series. Both support the<br />
<strong>XPx</strong> expansion modules to provide flexible,<br />
cost-effective point multiplexing <strong>and</strong> easy<br />
expansion for future retrofits. Light-Emitting Diode<br />
(LED) displays for diagnostics <strong>and</strong> manual<br />
override switches facilitate equipment startup <strong>and</strong><br />
testing, while magnetic or electric latching relays<br />
enable proper restart actions after a power outage.<br />
These modules offer an alternative to hardwiring<br />
many points from a remote location back to the<br />
controller, with the proven control <strong>and</strong> reliability<br />
typical of the Metasys® family of modular<br />
components.<br />
Note:<br />
The <strong>XTM</strong>-<strong>905</strong> supports a maximum of<br />
four <strong>XPx</strong> expansion modules.<br />
Figure 1: <strong>XTM</strong>-<strong>105</strong> <strong>Extension</strong> Module <strong>and</strong><br />
<strong>XPx</strong>-xxx Expansion <strong>Modules</strong><br />
❑ Modular Design<br />
❑ Status LEDs<br />
❑ H<strong>and</strong>/Off/Auto Switch<br />
❑ Built-in Line Voltage Relays<br />
❑ <strong>XTM</strong> Configurator<br />
(<strong>XTM</strong>-<strong>105</strong>)<br />
GX Tool (<strong>XTM</strong>-<strong>905</strong>)<br />
Features <strong>and</strong> Benefits<br />
Allows connection with expansion modules to<br />
provide I/O combinations for distributed or<br />
high-density monitoring <strong>and</strong> control.<br />
(The <strong>XTM</strong>-<strong>905</strong> has 16 I/O combinations, while<br />
the <strong>XTM</strong>-<strong>105</strong> has 40.)<br />
Provide an easy-to-read display for viewing<br />
I/O point status.<br />
Allows for direct manual override control of<br />
outputs for temporary on-site adjustments.<br />
Informs supervisory system of override<br />
conditions.<br />
Result in more economical installation <strong>and</strong><br />
maintenance; eliminates the installation costs<br />
of separately mounted relays. (Relay contacts<br />
rated 250 VAC at 3 Amperes maximum.)<br />
Provide user-friendly options for configuration<br />
to meet your system requirements. (Both are<br />
Windows®-based programs.)<br />
© 2000 Johnson Controls, Inc. 1<br />
Code No. LIT-635192<br />
www.johnsoncontrols.com
E R<br />
-<br />
F<br />
2 N<br />
+<br />
2 N<br />
N2 Bus<br />
<strong>XTM</strong>-<strong>105</strong>/<strong>XPx</strong> DX-9100 <strong>XTM</strong>-<strong>105</strong>/<strong>XPx</strong> DX-9100<br />
XT Bus<br />
UNT<br />
AHU/VAV/<br />
UNT/DX<br />
NCM350/361<br />
Notes: 1. Only models NCM300-2 <strong>and</strong><br />
NCM350-2 are Listed for UL 864<br />
smoke control applications.<br />
2. Up to eight total <strong>XTM</strong>-<strong>905</strong> <strong>and</strong><br />
XT-9100 extension modules per<br />
XT Bus.<br />
XT-9100/XP910x<br />
<strong>XTM</strong>-<strong>905</strong>/<strong>XPx</strong><br />
Ncmap<br />
Figure 2: Metasys Network Control Module (NCM) Application<br />
Operator<br />
Terminal<br />
N30<br />
N2 Bus<br />
XT Bus<br />
DX-9100<br />
UNT<br />
VAV<br />
<strong>XTM</strong>-<strong>105</strong>/<strong>XPx</strong><br />
<strong>XTM</strong>-<strong>905</strong>/<strong>XPx</strong><br />
N30app<br />
Figure 3: Metasys N30 Application<br />
2 Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong>
I ntroduction<br />
The <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong>, used with the <strong>XPx</strong><br />
expansion modules, are cost-effective devices for<br />
adding control points to the Building Automation<br />
System (BAS). This line of point extension <strong>and</strong><br />
expansion modules combines the functions of<br />
signal conditioners, relays, <strong>and</strong> manual overrides<br />
for controlling building operation. These modules<br />
simplify the selection of point types <strong>and</strong> provide<br />
greater functionality. The <strong>XTM</strong>-<strong>105</strong> can support<br />
8 Analog Input/Output (AI/AO) points <strong>and</strong><br />
32 Binary Input/Output (BI/BO) points, or 40 BI/BO<br />
points. The <strong>XTM</strong>-<strong>905</strong> can support 8 AI/AO points <strong>and</strong><br />
8 BI/BO points, or 16 BI/BO points.<br />
Modular Flexibility<br />
The <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> are designed for use<br />
in a variety of applications. These modules feature:<br />
• Voltage, current, <strong>and</strong> resistance options:<br />
analog input/output types 0-10V, 0/4-20 mA,<br />
5K ohm potentiometer, <strong>and</strong> passive<br />
Resistance Temperature Device (RTD)<br />
sensors:<br />
- Nickel (Ni) 1000 Regular (JCI)<br />
- Ni 1000 High Temperature (JCI)<br />
- Platinum (Pt) 1000 (DIN)<br />
- A99 (JCI)<br />
• Binary Output options: magnetic <strong>and</strong> electric<br />
latching relays for safe <strong>and</strong> efficient power<br />
restoration. Interlocked <strong>and</strong> staged relays for<br />
multispeed fan control.<br />
• BI counters for one or two <strong>XPx</strong> modules<br />
(when no analog modules are installed.<br />
Limited to eight maximum inputs.<br />
• Module designs that conform to DIN<br />
st<strong>and</strong>ards, allowing access to indicator lamps<br />
<strong>and</strong> controls, <strong>and</strong> providing protection from the<br />
internal wiring when mounted in st<strong>and</strong>ard DIN<br />
cabinets. Easy to retrofit existing devices.<br />
• Accumulator function applications support<br />
monitoring of devices that provide pulse<br />
outputs.<br />
Reliable Operation<br />
To reduce the possibility of equipment<br />
malfunctions or damage, the <strong>XTM</strong>-<strong>105</strong> <strong>and</strong><br />
<strong>XTM</strong>-<strong>905</strong> include the following features:<br />
• Durable case protects against physical<br />
damage <strong>and</strong> electrostatic discharge.<br />
• <strong>XPx</strong> debounce filter helps prevent false<br />
alarms or erroneous counts in accumulator<br />
points.<br />
• Self-checking diagnostics provide reliable<br />
system operation.<br />
• Cyclic redundancy check in all<br />
communication messages increases immunity<br />
to electromagnetic disturbances.<br />
Easy Installation <strong>and</strong> Maintenance<br />
To make operation of the <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong><br />
more user-friendly, these modules include the<br />
following features:<br />
• Economical way to connect points that are<br />
clustered at a distant location from the NCM<br />
or N30.<br />
• Minimizes the separate hardwiring of each<br />
I/O to the controller.<br />
• Manual override for temporary on-site<br />
adjustments, with LEDs to show point status.<br />
• Fast mounting on DIN rail.<br />
• Windows-based <strong>XTM</strong> Configurator<br />
software for <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> GX Tool software<br />
for <strong>XTM</strong>-<strong>905</strong>:<br />
- configures I/O module layout <strong>and</strong> setup<br />
parameters<br />
- indicates if there is a hardware<br />
configuration incompatibility in the <strong>XTM</strong><br />
after download<br />
- downloads to nine hardware devices via<br />
direct connection or over the network from<br />
the Operator Workstation (OWS)<br />
• LEDs on the module’s front panel display the<br />
status of each corresponding binary (I/O).<br />
Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong> 3
Product Comparison<br />
Table 1 compares the monitoring <strong>and</strong> control<br />
features of the <strong>XPx</strong>-xxx expansion modules.<br />
Table 1: Point Multiplexing Feature Comparison<br />
Product BI BO AI AO Manual<br />
Override<br />
Input<br />
LEDs<br />
Output<br />
LEDs<br />
Triac<br />
Output<br />
Relay<br />
Type<br />
Maximum<br />
Output<br />
Rating**<br />
XPA-821* -- -- 6 2 No No Yes -- -- --<br />
XPB-821 8 -- -- -- No Yes -- -- -- --<br />
XPL-401 4 3-single<br />
stage<br />
XPL-402*** 4 1-single<br />
stage,<br />
1-two<br />
stage<br />
XPL-403*** 4 1-three<br />
stage<br />
XPE-401 4 3-single<br />
stage<br />
XPE-402*** 4 1-single<br />
stage,<br />
1-two<br />
stage<br />
XPE-403*** 4 1-three<br />
stage<br />
-- -- Yes Yes Yes No Magnetic 250 VAC @ 3A<br />
250 VDC @<br />
30W<br />
-- -- Yes Yes Yes No Magnetic 250 VAC @ 3A<br />
250 VDC @<br />
30W<br />
-- -- Yes Yes Yes No Magnetic 250 VAC @ 3A<br />
250 VDC @<br />
30W<br />
-- -- Yes Yes Yes No Electric 250 VAC @ 3A<br />
250 VDC @<br />
30W<br />
-- -- Yes Yes Yes No Electric 250 VAV @ 3A<br />
250 VDC @<br />
30W<br />
-- -- Yes Yes Yes No Electric 250 VAC @ 30A<br />
250 VDC @<br />
30W<br />
XPE-404 4 4 -- -- Yes Yes Yes No Electric 250 VAC @ 1A<br />
250 VDC @<br />
10W<br />
XPT-401 4 4 -- -- Yes Yes Yes Yes -- 24 VAC @ 0.5A<br />
XPT-861 -- 8 -- -- No -- Yes Yes -- 24 VAC @ 0.5A<br />
*XPA-821 has AI types: V, mA, RTD; AO types: VDC, mA<br />
**For all <strong>XPx</strong> modules (except XPT), the maximum current rating at 120 VAC is 3A.<br />
***<strong>XTM</strong>-<strong>105</strong> only.<br />
Note: 25 Hz counters are available on up to eight BIs only when an analog module is not installed.<br />
4 Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong>
Ordering Information<br />
Refer to Tables 2 <strong>and</strong> 3 for <strong>XTM</strong>-<strong>105</strong>,<br />
<strong>XTM</strong>-<strong>905</strong>/<strong>XPx</strong>-xxx <strong>and</strong> accessory model codes.<br />
Table 2: <strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong>/<strong>XPx</strong>-xxx Model Codes<br />
Model Code<br />
<strong>XTM</strong>-<strong>105</strong>-5<br />
<strong>XTM</strong>-<strong>905</strong>-5<br />
XPA-821-5<br />
XPB-821-5<br />
XPL-401-5<br />
XPL-402-5*<br />
XPL-403-5*<br />
XPE-401-5<br />
XPE-402-5*<br />
XPE-403-5*<br />
XPE-404-5<br />
XPT-401-5<br />
XPT-861-5<br />
*<strong>XTM</strong>-<strong>105</strong> only.<br />
Description<br />
<strong>Extension</strong> Module, N2 Communications interface <strong>and</strong> 24 VAC supply<br />
<strong>Extension</strong> Module, XT Bus communication interface <strong>and</strong> 24 VAC supply<br />
Expansion Module Analog, six analog inputs, two analog outputs without manual override<br />
Expansion Module Binary, eight binary inputs<br />
Expansion Module Binary, four binary inputs, three binary outputs<br />
(latching relays with manual override)<br />
Expansion Module Multistate, four binary inputs, one 2-stage output, one binary output<br />
(latching relays with manual override)<br />
Expansion Module Multistate, four binary inputs, one 3-stage output,<br />
(latching relays with manual override)<br />
Expansion Module Binary, four binary inputs, three binary outputs<br />
(electrically maintained relays with manual override)<br />
Expansion Module Multistate, four binary inputs, one 2-stage output, one binary output,<br />
(electrically maintained relays with manual override)<br />
Expansion Module Multistate, four binary inputs, one 3-stage output<br />
(electrically maintained relays manual override)<br />
Expansion Module Binary, four binary inputs, four binary outputs (common supply)<br />
(electrically maintained relays with manual override, software configurable as On/Off or<br />
pulse type)<br />
Expansion Module Binary, four binary inputs, four binary outputs (24 VAC triacs with manual<br />
override)<br />
Expansion Module Binary, eight binary outputs (24 VAC triacs without manual override)<br />
Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong> 5
Table 3: Accessories Model Codes<br />
Model Code<br />
Description<br />
XST-101-0<br />
AS-ENC100-0<br />
EN-EWC10-0<br />
EN-EWC20-0<br />
EN-EWC30-0<br />
EN-EWC40-0<br />
EN-EWC15-0<br />
EN-EWC25-0<br />
EN-EWC35-0<br />
EN-EWC45-0<br />
AS-XFR050-0*<br />
AS-XFR010-1<br />
AS-XFR100-1*<br />
MW-MTOOL-0<br />
50 DIN A4 Sheets of Blank Stickers (12 per sheet) for Module Front Panel<br />
Generic Enclosure Kit, Sheet Metal<br />
Single Enclosure, Plastic Universal Packaging Module (UPM), without Transformer<br />
UPM Dual Unit without Power Components<br />
UPM Triple Unit without Power Components<br />
UPM Quad Unit without Power Components<br />
Single Enclosure, Plastic UPM with 50 VA Transformer<br />
UPM Dual Unit with Power Entry Box <strong>and</strong> 50 VA Power Transformer<br />
UPM Triple Unit with Power Entry Box <strong>and</strong> 100 VA Power Transformer<br />
UPM Quad Unit with Power Entry Box <strong>and</strong> 100 VA Power Transformer<br />
50 VA Transformer, Split Bobbin<br />
100 VA Transformer, 120 VAC with Circuit Breaker, Split Bobbin,<br />
UL® (Underwriters Laboratories) Recognized Class 2<br />
100 VA Transformer Kit, 120 VAC with Circuit Breaker, Split Bobbin<br />
M-Tool Package includes GX Tool Software <strong>and</strong> <strong>XTM</strong> Configurator software.<br />
MW-MTOOL-6 M-Tool Software Upgrade (The package upgrades customers from Configuration Tools to<br />
M-Tool.)<br />
*These are the only transformers approved for UL 864 smoke control applications. Any UL Recognized, Class 2<br />
transformer may be used in UL 916 energy management applications.<br />
6 Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong>
Notes<br />
Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong> 7
S pecifications Product<br />
Ambient Operating<br />
Conditions<br />
Ambient Storage<br />
Conditions<br />
Dimensions (H x W x D)<br />
Shipping Weight<br />
<strong>XTM</strong>-<strong>105</strong> <strong>Extension</strong> Module<br />
<strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> Module<br />
<strong>XPx</strong>-xxx-x Expansion <strong>Modules</strong><br />
+0 to + 50°C (+32 to +122°F)<br />
10–90% RH<br />
-40 to + 70°C (-40 to 158°F)<br />
118 x 70 x 57 mm (4.65 x 2.76 x 2.25 in.)<br />
<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong>, 150g (5.3 oz)<br />
XPA-821-5, 237g (8.4 oz)<br />
Other expansion modules (<strong>XPx</strong>-xxx-x) 163g (5.8 oz)<br />
Agency Listings UL Listed, CSA Certified, CE Mark Compliant, FCC Compliant<br />
Note: The <strong>XTM</strong>/<strong>XPx</strong> products are UL 864 Listed for smoke control (UUKL) with<br />
a complimentary UL Listing for Energy Management (PAZX). To comply<br />
with UL UUKL requirements for smoke control applications, all devices<br />
on the communication buses must be UL UUKL Listed. When the<br />
<strong>XTM</strong>/<strong>XPx</strong> products are connected to N30 or NCM 350 devices, the<br />
system will comply with the UL 916 PAZX Listing for Energy<br />
Management only. For details on smoke control applications, refer to the<br />
Smoke Control Technical Bulletin (LIT-636330) located in the Metasys<br />
Network Technical Manual (FAN 636) under the Smoke Control major<br />
tab.<br />
The performance specifications are nominal <strong>and</strong> conform to accepted industry st<strong>and</strong>ards. For applications at conditions beyond<br />
these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from<br />
misapplication or misuse of its products.<br />
Controls Group<br />
www.johnsoncontrols.com<br />
507 E. Michigan Street FAN 635<br />
P.O. Box 423<br />
Metasys Network Sales Resource Manual<br />
Milwaukee, WI 53201<br />
Printed in U.S.A.<br />
8 Application Specific Controllers—<strong>XTM</strong>-<strong>105</strong> <strong>and</strong> <strong>XTM</strong>-<strong>905</strong> <strong>Extension</strong> <strong>Modules</strong>, <strong>XPx</strong> Expansion <strong>Modules</strong>