<strong>BTC</strong> TANK TYPE HEATERS<br />

SERVICE WORKBOOK<br />

Stoichiometric or theoretical complete combustion requires 10 cubic feet of air per 1000 BTUH<br />

input of the gas input. The National Fuel Gas Code also recommends an additional 2.5 cu.ft. of<br />

"excess" air. This 12.5 cu.ft minimum supply air per 1000 BTUH input applies to natural and<br />

propane gas models.<br />

The National Fuel Gas Code also specifies minimum make-up air opening sizes for various<br />

building installations. (Ref: NFPA 54, ANSI Z223.1)<br />

A.O. <strong>Smith</strong> <strong>Water</strong> Products<br />

Irving, Texas ©1998<br />

5<br />

Service Workbook<br />

Training Department