THE HIGH RESISTANCE GROUNDED<br />

POWER SYSTEM<br />

DAMAGE TO POWER SYSTEM COMPONENTS<br />

1. Thermal damage<br />

2. Mechanical damage<br />

( I RMS )2<br />

t<br />

( I p )2<br />

Comparison <strong>of</strong> solidly grounded <strong>and</strong> high resistance grounding<br />

methods – 2000 KVA transformer at 480 volts<br />

SYSTEM<br />

GROUNDING<br />

LINE-GROUND<br />

FAULT AMPS<br />

DAMAGE TO<br />

EQUIPMENT<br />

Hi – R 5 A 1 per unit<br />

Solidly 20,000 A 16 x 10 6<br />

(<br />

20,000 A<br />

)<br />

2<br />

Increase in damage = = 16,000,000<br />

5 A<br />

73