HIGH RESISTANCE GROUNDING 2.4KV SYSTEM<br />

CALCULATION OF SYSTEM CHARGING CURRENT<br />

4. CABLE CAPACITANCE<br />

C=<br />

0.00735(SIC) _mfd_<br />

WHERE SIG= SPECIFIC INDUCTIVE CAPACITANCE =3<br />

LOG (D/d) 100 ft.<br />

D= DIAMETER OVER INSULATION<br />

d=DIAMETER OF CONDUCTOR<br />

AVERAGE LENGTH OF CABLE RUNS = 75 FT, #2 5KV UNSHIELDED.<br />

C= _0.00735*3_<br />

LOG (.56.34)<br />

_75 f_<br />

1000 ft<br />

_____10^6_____<br />

377 X 7.63x10^-3<br />

C= .1017 X = 7.63X10^-3 ufd<br />

Xc= =3.47x10^5 OHMS.<br />

3Ico= = .0119AMPS = .012AMPS PER FEEDER<br />

__2400/ 3^(1/2)__<br />

3.47X10^5 OHMS<br />