HIGH RESISTANCE GROUNDING 2.4KV SYSTEM<br />

CALCULATION OF CHARGING CURRENTS<br />

1. SURGE CAPACITORS<br />

6<br />

3 ICO = 3(2πf CE/10 ) = 3(2π*60*.5X(2400V/3^1/2)= 3X.261= .783 AMPS<br />

10 6<br />

2. MOTORS<br />

HP<br />

3 ICO = [0.005X ( )] REF. ALVIN KNABLE<br />

RPM<br />

450<br />

1765<br />

200<br />

180<br />

100<br />

257<br />

125<br />

585<br />

450 HP MOTOR 0.05 X = .013AMPS<br />

200 HP MOTOR 0.05 X = .06AMPS<br />

100 HP MOTOR 0.05 X = .02AMPS<br />

125 HP MOTOR 0.05 X = .01AMPS<br />

3. ZIG-ZAG TRANSFORMER – APPROXIMATE VALUE .01 TO .001 MICRO FARAD<br />

__10^6 __<br />

XC= = 2.65 X 10^5 TO 2.65 X 10^6 OHMS<br />

377X10^-2<br />

3ICO= = .0156 TO .00156 AMPS. DISREGARD THIS VALUE<br />

2400/3^(1/2)<br />

2.65X10^5<br />