Quick Selection
Quick Selection
Quick Selection
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Technical data and ordering<br />
Technical data<br />
Supply voltage<br />
Power consumption<br />
Input signal<br />
Sensor input<br />
24 V a.c. +/-15% 50/60 Hz, 80 VA<br />
(the supply voltage is galvanically separated from the input and output signals)<br />
Controller<br />
Actuator<br />
Current signal<br />
Digital input from external contact function<br />
2 pcs. Pt 1000 ohm<br />
5 VA<br />
75 VA<br />
4-20 mA or 0-20 mA<br />
Output signal<br />
Current signal<br />
4-20 mA or 0-20 mA<br />
Max. load: 200 ohm<br />
Relay output 2 pcs. SPST a.c.-1: 4 A (ohmic)<br />
Alarm relay<br />
1 pcs. SPST<br />
a.c.-15: 3 A (inductive)<br />
Input<br />
Actuator<br />
Output<br />
Data communication<br />
Possible to connect a data communication module<br />
Ambient<br />
During operation<br />
temperature<br />
During transport<br />
Enclosure IP 20<br />
Weight<br />
300 g<br />
Mounting<br />
DIN rail<br />
Display<br />
LED, 3 digits<br />
Terminals<br />
max. 2.5 mm 2 multicore<br />
Approvals<br />
Temperature signal from sensor in the actuator<br />
Pulsating 24 V a.c. to actuator<br />
-10 - 55°C<br />
-40 - 70°C<br />
EU Low Voltage Directive and EMC demands re CE-marking complied with.<br />
LVD-tested acc. to EN 60730-1 and EN 60730-2-9<br />
EMC-tested acc. to EN50081-1 and EN 50082-2<br />
Ordering<br />
Type Description Code No.<br />
EKC 361 Evaporating pressure controller 084B7060<br />
Accessories<br />
EKA 173 FTT 10 LON 084B7092<br />
EKA 174<br />
Data communication module (accessories), (RS 485<br />
module) with galvanic separation<br />
084B7124<br />
EKA 175 RS485 LON 084B7093<br />
AKS 21M Pt 1000 Sensor 084N2003<br />
AKA 211 Cable filter * 084B2238<br />
* When cable lengths between controller and valve exceed 5 m, max. cable length with filter: 50 m<br />
The installation of data communications must comply with the requirements described in literature sheet no. RC8AC<br />
Media temperature control – EKC 361<br />
119