Technical data and ordering<br />

Technical data<br />

Supply voltage<br />

Power consumption<br />

Input signal<br />

Sensor input<br />

24 V a.c. +/-15% 50/60 Hz, 80 VA<br />

(the supply voltage is galvanically separated from the input and output signals)<br />

Controller<br />

Actuator<br />

Current signal<br />

Digital input from external contact function<br />

2 pcs. Pt 1000 ohm<br />

5 VA<br />

75 VA<br />

4-20 mA or 0-20 mA<br />

Output signal<br />

Current signal<br />

4-20 mA or 0-20 mA<br />

Max. load: 200 ohm<br />

Relay output 2 pcs. SPST a.c.-1: 4 A (ohmic)<br />

Alarm relay<br />

1 pcs. SPST<br />

a.c.-15: 3 A (inductive)<br />

Input<br />

Actuator<br />

Output<br />

Data communication<br />

Possible to connect a data communication module<br />

Ambient<br />

During operation<br />

temperature<br />

During transport<br />

Enclosure IP 20<br />

Weight<br />

300 g<br />

Mounting<br />

DIN rail<br />

Display<br />

LED, 3 digits<br />

Terminals<br />

max. 2.5 mm 2 multicore<br />

Approvals<br />

Temperature signal from sensor in the actuator<br />

Pulsating 24 V a.c. to actuator<br />

-10 - 55°C<br />

-40 - 70°C<br />

EU Low Voltage Directive and EMC demands re CE-marking complied with.<br />

LVD-tested acc. to EN 60730-1 and EN 60730-2-9<br />

EMC-tested acc. to EN50081-1 and EN 50082-2<br />

Ordering<br />

Type Description Code No.<br />

EKC 361 Evaporating pressure controller 084B7060<br />

Accessories<br />

EKA 173 FTT 10 LON 084B7092<br />

EKA 174<br />

Data communication module (accessories), (RS 485<br />

module) with galvanic separation<br />

084B7124<br />

EKA 175 RS485 LON 084B7093<br />

AKS 21M Pt 1000 Sensor 084N2003<br />

AKA 211 Cable filter * 084B2238<br />

* When cable lengths between controller and valve exceed 5 m, max. cable length with filter: 50 m<br />

The installation of data communications must comply with the requirements described in literature sheet no. RC8AC<br />