VHV and STF: 4-way reversing valves<br />

Pilot operated 4-way reversing valves allow an inversion of the refrigeration cycle, changing from cooling<br />

mode in summer to heating mode in winter. 4 way valves are also used in defrost cycles in order to allow<br />

hot gas to be sent into iced up evaporators. The cycle inversion is initiated by a small solenoid pilot valve,<br />

which controls the movement of a slider, and in turn governs the refrigerant flow path. The valve is connected<br />

to the discharge and suction of the compressor.<br />

Features<br />

discharge connection<br />

slider<br />

valve body<br />

connection to condenser/evaporator<br />

connection to evaporator/<br />

condenser<br />

suction connection<br />

Applications Advantages Facts<br />

· Heat pump applications<br />

· Reversing chillers<br />

· Packaged air conditioning systems<br />

· Room air conditioning systems<br />

· Each model can be used with R410A<br />

refrigerant as well as R407C, R134a,<br />

R404A, R22<br />

· Different tube diameters and configurations<br />

available<br />

· Designed for instantaneous changeover<br />

with minimum pressure differential<br />

· Minimized leakage in the valve<br />

· Reduced pressure drop due to unique<br />

design (shape of internal elements)<br />

· Wide application range for all commonly<br />

used refrigerants: (R134A,<br />

R404A, R407C, R22 and R410A)<br />

· Max. working pressure: 45 bar<br />

· Ambient temperature: -20 to 55ºC<br />

· Full capacity range up to 400 kW<br />

· Largest valve available on the market<br />

(VHV-6001)<br />

· 30 years of experience and know-how<br />

34