VHV and STF: 4-way reversing valves<br />
Pilot operated 4-way reversing valves allow an inversion of the refrigeration cycle, changing from cooling<br />
mode in summer to heating mode in winter. 4 way valves are also used in defrost cycles in order to allow<br />
hot gas to be sent into iced up evaporators. The cycle inversion is initiated by a small solenoid pilot valve,<br />
which controls the movement of a slider, and in turn governs the refrigerant flow path. The valve is connected<br />
to the discharge and suction of the compressor.<br />
Features<br />
discharge connection<br />
slider<br />
valve body<br />
connection to condenser/evaporator<br />
connection to evaporator/<br />
condenser<br />
suction connection<br />
Applications Advantages Facts<br />
· Heat pump applications<br />
· Reversing chillers<br />
· Packaged air conditioning systems<br />
· Room air conditioning systems<br />
· Each model can be used with R410A<br />
refrigerant as well as R407C, R134a,<br />
R404A, R22<br />
· Different tube diameters and configurations<br />
available<br />
· Designed for instantaneous changeover<br />
with minimum pressure differential<br />
· Minimized leakage in the valve<br />
· Reduced pressure drop due to unique<br />
design (shape of internal elements)<br />
· Wide application range for all commonly<br />
used refrigerants: (R134A,<br />
R404A, R407C, R22 and R410A)<br />
· Max. working pressure: 45 bar<br />
· Ambient temperature: -20 to 55ºC<br />
· Full capacity range up to 400 kW<br />
· Largest valve available on the market<br />
(VHV-6001)<br />
· 30 years of experience and know-how<br />
34