PHT: The parts programme make flexibility<br />

PHT thermostatic expansion valves regulate the injection of refrigerant liquid into evaporators.<br />

Injection is controlled by the refrigerant superheat.<br />

Therefore the valves are especially suitable for liquid injection in ”dry“ evaporators where the superheat<br />

at the evaporator outlet is proportional to the evaporator load.<br />

Features<br />

Capillary tube and sensor in<br />

stainless steel.<br />

Vibration proof due to the<br />

strong capillary tube.<br />

Laser welded thermostatic element<br />

in stainless steel. Secure, stronger<br />

diaphram and longer lifetime.<br />

Easy adjustment of<br />

superheat<br />

Connection for<br />

external pilot<br />

Weld or solder flanges<br />

Weld: 1 to 2 in.<br />

Solder: 1 1/8 in (28 mm)<br />

to 1 3/8 in. (35 mm)<br />

Applications Advantages Facts<br />

· Traditional refrigeration and freezing<br />

applications<br />

· Water coolers and air conditioning<br />

· Interchangeable orifice assembly<br />

- easier stocking<br />

- easy capacity matching<br />

- better service.<br />

· Very tight main orifice<br />

Also used as solenoid valve<br />

(not PHT 300)<br />

· Superheat<br />

Static superheat SS can be adjusted<br />

with setting spindle ().<br />

· Permissible working pressure<br />

- PHT 85 and 125: PS / MWP = 28 bar<br />

- PHT 300: PS / MWP = 20 bar<br />

· Rated capacities from 105 to 1890 kW<br />

(30 to 540 TR) for R22<br />

· Can be supplied with MOP<br />

(Max. Operating Pressure)<br />

Protects the compressor motor<br />

against excessive evaporating pressure<br />

· Range: –40 to +50°C<br />