<strong>Pressure</strong> <strong>Regulator</strong><br />

<strong>133</strong> / <strong>233</strong><br />

Over-pressure function<br />

When the outlet pressure of a gas<br />

pressure regulator reaches an<br />

inadmissible value, the increased<br />

pressure is also transmitted through<br />

the pulse bore (13) to the comparator<br />

(9) of the SSV.<br />

When the force below the comparator<br />

(9) reaches the force of the load<br />

spring (10) against over-pressure, the<br />

comparator (9) with the lever system<br />

(11) (for SSV with upper switching<br />

point) and with the guide bush (28)<br />

(for SSV with upper and lower<br />

switching points) is pushed upwards.<br />

The lever system (11) is released so<br />

that the force of the closing spring<br />

(14) is set free, and the valve disk (12)<br />

is pushed against the orifice (7).<br />

Under-pressure function<br />

When the outlet pressure of the<br />

regulator falls to such a degree that<br />

the force below the comparator (9)<br />

becomes smaller than the force of the<br />

spring for under-pressure (30), the<br />

load spring (30) pushes the<br />

comparator downwards.<br />

(Against over-pressure (10), the load<br />

spring is mounted with the guide bush<br />

(28) at the retention shoulder (32)).<br />

The lever system is released so that<br />

the force of the closing spring (14) is<br />

also released and the valve disk (12)<br />

is pushed against the orifice.<br />

Commissioning<br />

The SSV is commissioned by pulling<br />

out the valve rod (26) and engaging<br />

the lever system (11). However, the<br />

SSV with upper and lower shut-off<br />

require that the pressure below the<br />

comparator (9) lies above the lower<br />

switching pressure against underpressure,<br />

and below the switching<br />

pressure against over-pressure, so<br />

that the lever (11) touches the arm<br />

(33) of the rocking lever (34).<br />

The cap (35) and the valve rod (26)<br />

are equipped with threads.<br />

Consequently, a slight resetting of the<br />

valve rod is possible.<br />

with upper<br />

switching point<br />

P so ≥ 400 mbar<br />

3<br />

6<br />

4<br />

7<br />

5 13<br />

14<br />

12<br />

34<br />

36<br />

11<br />

10<br />

9<br />

32<br />

33<br />

12<br />

limit of lift for<br />

upper shutoff<br />

14<br />

34 36 11 26 35<br />

with lower<br />

and upper<br />

switching points<br />

10<br />

30<br />

28<br />

9<br />

Schlumberger reserves the right to change these specifications without prior notice — EU - GA - 00026.0 - GB - 12.00<br />